CB Svendsen A/S                                                    

 

 

 

 

Installation guide for FA-20:

 

 
For correct installation of a FA-20 Remote Reading Unit you must follow this installation guide 
carefully: 

 
1. Insertion of SIM-card into FA-20. 

 
Use a SIM-card that supports data V.110 + SMS and disable the PIN/PUK code in advance 
by means of a mobile phone.  
 
The FA-20´s GSM modem is placed to the left of the plastic column in the middle of the case. 
The SIM-card reader is placed on top of the GSM modem. The SIM-card reader is divided into 
two  (lid  and  bottom)  and  hinged  at  the  “top””.  You  push  the  “lid”  up  towards  the 
pushbutton/the antenna plug, after which the lid can be opened to 90 degrees (or more). The 
SIM-card  can  hereafter  be  pushed  into  the  slit  on  the  lid  with  the SIM-cards  beveled  corner 
upwards to the right. Then the lid is closed and the SIM-card is pushed into to lid just enough 
so that the lid can be closed in the bottom. Then the lid is pulled downwards until it locks. 

 

 
2. The physical location of FA-20: 

 
Typically  FA-20  is  placed  next  to  one  of  the  meters  that  are  to  be  logged.  The  most 
convenient location is against a wall, vertically and e.g. 1.6 meters over the floor. This location 
secures  a  convenient  working  position  for  the  user  when  pressing  the  pushbutton  and 
observing the two signal lamps.  

 
3. Wall-mounting of FA-20. 

 
FA-20 is specifically designed for wall mounting using 3 self-cutting screws (BN615: 3.5x30) 
and raw plugs (HFC365: Ø6). When applying raw plugs please note: 
 
Place  the  FA-20  unit  with  the  cover  detached  against  the  wall  and  mark  the  precise  drilling 
position on the wall.  Drill holes (ø6, 40 mm deep) and attach the unit to the wall. 

 
 
4. Installation of pulse-inputs. 

 
FA-20  features  2  pulse-inputs  used  to  receive  pulse  signals  from  the  potential-free  contact 
(relay) S01 or from the optocoupler. The cable should have an outside diameter of 4.5 mm ± 
0.5 mm in order to secure maximum of pull relief.  
 
Terminals for the 2 pulse inputs are  
1+2 and 3+4. 

 

 
 

 
 

Specifications are subject to revision without notice

 

Содержание FA-20

Страница 1: ...RS SMS based remote metering 1 FA 20 in brief 2 Product information 3 Installation Instructions Rev 2013 02 01 CB Svendsen A S Kirke Vaerloesevej 22 24 DK 3500 Vaerloese Denmark Phone 45 4448 5286 Fax...

Страница 2: ...lses can be freely mixed FA 20 is delivered preprogrammed with a number of serial meter drivers supporting different serial manufacturer protocols Changing between the drivers is easily done trough SM...

Страница 3: ...3 FA 20 Product information...

Страница 4: ...is exceeded these conditions will be transmitted to the main station through an extraordinary data communication programmable Furthermore the FA 20 saves 3 sets of serial readings The latest reading...

Страница 5: ...o of days 24 h 1h logging 31 27 24 22 20 18 The FA 20 is remotely programmed from the main station logging parameters set up and selection of buffers to which data is logged Logging of pulses and seri...

Страница 6: ...a random number of minutes within a time window which is programmable from the IT centre FA 20 also supports dial back at absolute time where it is the main station who chooses the time including date...

Страница 7: ...can preserve its content Log data and for example the latest monthly reading is always stored in the F RAM which does not need a battery to preserve its memory FA 20 features a special integrated cir...

Страница 8: ...4 band GSM module Temperature range 20 to 45 Relative humidity 15 to 95 not condensing Density class IP54 Dimensions 105 x 180 x 50 mm W x H x D without antenna Remember 30 mm clearance for cable entr...

Страница 9: ...ultical 801 via data module an without compatability module KM6 data module is mounted internally in 801 8 Div Multical with M bus module mounted internally in Multical Max M bus 9 Unigas 61E via data...

Страница 10: ...10 FA M2000 GSM main station modem...

Страница 11: ...s ready for use and special settings of parameters can be installed and stored permanently in the GSM modems memory FA M2000 supports V 110 data communications which allow data to be transferred at sp...

Страница 12: ...12 Installation guide FA 20...

Страница 13: ...n the lid is pulled downwards until it locks 2 The physical location of FA 20 Typically FA 20 is placed next to one of the meters that are to be logged The most convenient location is against a wall v...

Страница 14: ...y sending FA 20 a SMS FA 20 with firmware 1 30 or later contains as minimum the following software drivers KMX handles various Multical with 3 wire data module i e Multical III 66C Compact 401 and 601...

Страница 15: ...to terminal 10 in FA 20 Brown wire Reg pin 5 in Unigas is connected to terminal 11 in FA 20 It is recommended to connect FA 20 directly to the internal plug in Unigas and let the plug with the RPG co...

Страница 16: ...with M bus L G WSD and WSF L G 2WR4 2WR5 and UH50 with G2 or G4 Sensus Mechanical water meter with M bus Hydrometer Sharkey with M bus and Infocal 5 with M bus ABB Type Delta with M bus Use Fa 20 conn...

Страница 17: ...n communication with the GSM GPRS modem the big red LED Top right corner visible through the lid will after a few seconds flash quickly and stable to indicate errors Common log operation is stopped 9...

Страница 18: ...will light constantly during the communication and in case of error the red LED will report the error by a 3 second long flash Note Automatic readout after power up Approximately 2 3 min after power...

Страница 19: ...ed LED is ON for 3 sec Failure without any permanent influence on normal operation 1 A serial reading of a meter failed 2 Data communication with the main station failed 3 Brief power failure More aty...

Страница 20: ...If there is no power error like in point 1 and the little green internal LED is turned off then it is properly an error in the GSM modem and the FA 20 should be taken down and sent to service If the...

Страница 21: ...eadout from serial meters then you can test the communication between the FA 20 and serial meters by pushing the key After a keystroke the big green LED will flash once briefly per second by readout o...

Страница 22: ...002000 Pulse counter stand for pulse input no 2 In 1 OFF 2 OFF Signal on digital input no 1 on off and no 2 on off In 3 OFF 4 OFF Signal on digital input no 3 on off and no 4 on off Out 1 OFF 2 OFF Re...

Страница 23: ...nd for M1 Volume 839 Volume counter stand for M1 Mbus2 90012312 Serial no read from meter connected to M2 Energy 3552 25 Energy counter stand for M2 Volume 88243 88 Volume counter stand for M2 Multi 3...

Страница 24: ...variants Above is the fully wired version with 4 pulses or digital S01 inputs 2 relay outputs and 2 x 0 4 20 mA inputs Below is a variant only with 4 pulses or digital inputs Relay outputs Max 27Vdc...

Страница 25: ...Ds in the middle column shows pulses from pulse input 5 to 8 and the orange LEDs in the right column shows pulse inp Pulse input 9 to 12 in connector In the middle to the right NOTE Pulse input 1 and...

Страница 26: ...cates the current status of the output Light in the LED means output is active closed loop Specification These are 2 electrically isolated optocoupler outputs Max applied voltage is 27Vdc open loop Ma...

Отзывы: