background image

 
EQ400I                                                

ENGLISH 

 

 

5. 

CONTROL UNIT SETTING UP 

 

 

Attention!!

 

POSITION THE DIPSWITCHES TO OFF DURING THE 

1

ST

 

SETTING

-

UP PHASE EXCEPT FOR THE 

D

IP 

NR 

8,

 

(

MAN 

P

RESENT

),

 THAT MUST BE SET TO 

“ON”.

 

5.1 

FUNCTIONS OF THE SWITCHES MOUNTED ON THE CARD

 

 

SW1 

Re-closing operating logic 

ON = Automatic 

OFF = Manual 

SW2 

Final thrust 

ON = Enabled 

OFF = Disabled 

SW3 Photocell 

test 

ON 

= Enabled 

OFF = Disabled 

SW4 

Motor absorption check 

ON = Enabled 

OFF = Disabled 

SW5 

Slow-down start limit-stop 

ON = Enabled 

OFF = Disabled 

SW6 

Flashing light logic 

ON = Steady Light 

OFF = Flashing light 

SW7 

Selects safety edge type 

ON = Resistance edge 

OFF = Mechanical edge 

SW8 

Man present 

ON = Active 

OFF = Inactive 

 

5.2 

SWITCHING ON THE CARD AND INSERTING THE PROGRAMMER/DISPLAY 

 

 

Insert the programmer and power up the card.  

 

The red mains present LED lights up and the  

 

FW version appears on the display 

5.3 

 USING THE PROGRAMMER AND PARAMETER MANAGEMENT. 

Press OK to  

  Select the with  

                                                   Press 

 

 to scroll until 

proceed with the 

  the 

 

arrows Setup 

 

                   the parameters of 

Input

 

 

         

programming. 

  Base menu and press 

OK.    

                   diagnostics

 (

ACPS)

 

Note:

 This function is for checking the state of the inputs on the board. Move in the pages and display all the inputs 

with the arrows:  

 to go forward to the end and 

 to go back

 

 

 

Page

 P2.1:

 Buttons: 

A

pre (Start), 

Close

P

edestrian and 

S

top 

 

 

 A

=Apre (Start), 

C

=Close, 

P

=Pedestrian, 

S

=Stop 

 Values: 

1

 = Input closed, connected and active. 

= Input open, not connected or deactivated.    

 

Press 

 

 

 

Page

 P2.2: 

Limit stop

: RA

: Opening slow-down,

 RC

:

 

Closing slow-down,

 FA

: Opening

, FC

: Closing

 

 RA

= Opening slow-down start. (

FC Ral Start

), 

RC

= Closing slow-down start (

FC Ral Close

 FA

= Opening limit stop. (

FC Start

), 

FC

= Closing limit stop (

FC Closing

)

 

                 Values: 

1

 = Input closed, connected and active. 

= Input open, not connected or deactivated.    

 

Press 

 

  

 

Page

 P2.3: 

Safety edges

: CSAP=000

 Edge opening Input. 

CSCH=000 

Edge Closing Input 

 

 Values: 

255

=Input open, 

0

= Input closed, Edge NC connected or resistance activated,  

              

xxx

=resistance value of the type of edge connected (0 < value < 255).    

 

 

Press 

 

 

 

Page

 P2.4. 

Status of the DIP SWITCH present on the board: 

12345678 

 

Values: 

0

 switch off (OFF), 

1

 

switch 

on 

(ON) 

    Press 

 

 

 

 

Page

 P2.5    

L1

 PAUS=XXX: 

Pause time set. Displays the time adjusting the trimmer

 TR1 (Pause) 

  

      

L2

 PAUS=xxx

= During the pause, shows the remaining time, that decreases starting from the set value until 

reaching 

0. 

 

      Press 

 

  

 

Page

 P2.6. FT = 

Status of photocell input.

 

 Values: 

0

 = Input open or photocell not connected, 

1

 = Input short circuited or photocell connected   

Press 

 

 

 

 

 Page

 P2.7

 = Information on the slow-down point and thrust status (Internal information)    

Press 

 

 
 
 Page

 P2.8

 = Relative position (Sec)  

 Values:  

0.0

 = Door closed, Limit stop activated. Decrease to closing 

                                             SS.s

 = Door open, Limit stop activated. Increase to opening until reaching the value 

              set in RunTime (

P2.24

)         

 

Pagina 4 di 9                                                                                                                                                              Rev. 00 del 30/11/2009

 

 

Содержание EQ400I

Страница 1: ...rtita IVA 0050659 001 7 Reg Trib Torino N 654 62 C C I A A 333122 M T0024777 Sito www casit it E Mail info casit it INSTALLER TECHNICAL MANUAL GB ELECTRONIC CONTROL PANEL ONE THREE PHASE MOTOR EQ400I...

Страница 2: ...n on voltage and frequency Settable starting boost thrust Personalised partial opening pedestrian Stop time adjustable from 0 to 60 seconds with trimmer Personalised slow downs Personalised accelerati...

Страница 3: ...d DIPSW5 in OFF FC Ra Close 22 common at 24 Closing slow down limit stop NC or NA If not used leave open and set NA in P5 8 and SW5 in OFF Brake 27 NO 28 NC 29 C Relay switched Motor brake Rest Motor...

Страница 4: ...A Apre Start C Close P Pedestrian S Stop Values 1 Input closed connected and active 0 Input open not connected or deactivated Press Page P2 2 Limit stop RA Opening slow down RC Closing slow down FA Op...

Страница 5: ...ance connected photocell autotest failed etc This type of error prevents entering into programming See display P4 1 to show alarm produced 5 7 SETTINGS AND OPERATING LOGIC 5 7 1 Operating with automat...

Страница 6: ...play P2 18 Photocell behaviour in opening Press Values 0 performs immediate opening 1 performs opening when photocell is free 6 1 10 INV T AP Display P2 19 Inversion time of the motor in case obstacle...

Страница 7: ...the parameter from NO to NC and vice versa Display P5 1 Display P5 2 Display P5 3 Start Button Chiude Close Button Pedonale Pedestrian Default N Open Default N Open Button Default N Open Display P5 4...

Страница 8: ...EQ400I ENGLISH 7 DISPLAY FOR SHOWING AND PROGRAMMING THE CONTROL UNIT RESET display to start from the panel with the OK button pressed 0 Normal 1 Alarm Pagina 8 di 9 Rev 00 del 30 11 2009...

Страница 9: ...facturer and by current legislation All installation maintenance repairs and cleaning operations must be documented This documentation must be preserved by the user and made available to the personnel...

Отзывы: