TROUBLESHOOTING 

PROBLEM 

PROBABLE CAUSE 

SOLUTIONS 

Giving a command with the 

radiotransmitter or with the key-

switch, the gate does not open.or 

not clos 

230 volt mains voltage absent 

Check master switch 

Emergency STOP present 

Check for any STOP commands 

connected to the 25 input. 

There is no jumper between the 25 

input and the common. 

If not used, check if there is a 

jumper on the 25 input. 

One of the fuses is burnt out. 

Replace the fuse with one of the 

same value. 

Motor power cable not connected or 

faulty. 

Check the connection of the cable 

in the terminal board or replace it. 

The flashing led L2 or L3 points out 

the condition of triac TH1 (pilot 

motor 1) or TH2 (pilot motor 2) in 

damage. 

Remove current to the plant for any 

second and subsequently fit the 

control panel EQ2006 

The automation performs only the 

manoeuvre of opening or closing 

The photocell, if present, is 

obstructed or not functioning. 

Check, clean the photocell or 

remove the obstacle. 

The photocell is missing and there 

is no jumper between the 18 19 

input and the common. 

Check the accessory connections 

and the presence of the “jumper”. 

The safety edge is missing or the 

bridge is not present among the 

entry 15 and 16 and the commune. 

Verify the connections accessories or 

the presence of the "bridge." 

The bridge is missing among the 

input 37-38 

Verify the presence of the "bridge." 

The motors limit switches are  

missing of is not present the bridge 

among the input 20, 21, 23, 24 and 

the commune. 

Verify the limit switches of the motor 

or the presence of the "bridge." 

A key selector NC contact has been 

used instead of an NO contact to 

connect to the 26 input 

Check the connections. 

The operator functions by wire but 

not with the radiotransmitter. 

The radiotransmitter has not been 

memorised or is broken or the 

battery is flat. 

Check/change the battery. 

Carry out the radiotransmitter 
acknowledgement procedure. 

The electrical limit switch activates 

but the motor does not stop. 

The opening and closing limit 

switches have been exchanged. 

An NO contact has been used 

instead of an NC. 

Check the connections. 

The gate moves then stops, both in 

opening and closing. 

The motor force is insufficient 

and/or the trigger threshold of the 

REVERSE is too low. 

Check if the leaves are in axis, 

lubricate if necessary. 

Increase the trigger threshold by 

turning the P2 P3 trimmer clockwise. 

If it is not sufficient, increase the P1 

trimmer clockwise and reprogram. 

When commanded, the motor starts 

but the gate does not move. 

There is an obstacle in front of the 

gate; the hinges are blocked; a 

motor fixing bracket has detached. 

Remove any obstacles from the 

gate; restore the hinges, replace or 

lubricate them. 

Fix the motor fixing bracket. 

N.B.: If the problem persists, contact your supplier  or the  installer. 

WARNING: Before sending a radiotransmitter to be repaired, check that the batteries are not flat. 50% of all 
radiotransmitters that return for servicing only have flat batteries. 

Содержание EQ2006

Страница 1: ...F DIP 2 ON S1 DIP 1 ON DIP 3 ON ON When the contact of the timer is released the gate close after the time selected SLOW DOWN MOTORS it is possible to set the slow down motor in opening and closing du...

Страница 2: ...common to the clamp 9 closing to the clamp 10 M6 11 12 Light of courtesy clean contact N O max 230V 4 Amp see S3 dip 8 M7 13 14 Output 12Vdc max 200 mA 14 15 Input N C SAFETY EDGE 1 In opening it arre...

Страница 3: ...o the intervention of the safety edge 1 The flashing led L2 points out the condition of triac TH1 pilot motor 1 in damage L3 SAFETY EDGE 2 it switch on to the intervention of the safety edge 2 The fla...

Страница 4: ...en the gate is closed and foto 1 obscurated the gate not open during the closing and foto 1 obscurated the gate stop and reopen when the foto1 is liberated in this operation is activated also the elec...

Страница 5: ...e memorization involves to repeat the procedure of the first setting because the times of work and the setting of the reverse changes S2 dip 9 according to the used motors ON two motors OFF one motor...

Страница 6: ...nal portion of the stroke in deceleration release the key PS1 in the point in which you desire to continue with the low speed If you want to effect the whole stroke with normal speed maintain pressed...

Страница 7: ...aintain pressed PS1 and release it just at the end of the opening when limit switch is working FCA 1 Hold pressed the key PS1 to plan the last portion of opening for motor 1 in deceleration and releas...

Страница 8: ...motor 1 WARNING If you want to plan the final portion of the stroke in deceleration release the key PS1 in the point in which you desire to continue with the low speed If you want to effect the whole...

Страница 9: ...TIME BRAK Inside the planning menu press the push button PS3 to go in the parameter Pedestrian time break The state of the leds represented to the left side points out that it is in the menu related t...

Страница 10: ...onnect the positive pole of the leds to the source of feeding and the negative pole of every leds to the clamp F of the relative terminal block Naturally the negative one of the source of feeding must...

Страница 11: ...celeration ON strength range high OFF strength range low respectively on motors 1 and 2 During the reverse intervention a short flash red is gotten on the led REV 1 if it intervenes on the motor 1 or...

Страница 12: ...the bridge The motors limit switches are missing of is not present the bridge among the input 20 21 23 24 and the commune Verify the limit switches of the motor or the presence of the bridge A key se...

Страница 13: ...th several wires and always separate the power from the low tension Connect wires to the control box from the bottom through pass cables only MAINTENANCE To ensure product efficiency it is essential t...

Страница 14: ...Page 14 of 14 EQ2006 R 1 5 Rev 02 dated 09 11 2007...

Отзывы: