27
CV072018-1
Interaction table
The configuration parameters, set points, input signals, states and alarms are accessible as “retention registers” (word access 16 bits). BXX is the
XXth bit of a word (XX is a value of 00 to 15). R indicates that the word is only readable, R / W in turn indicates that the word is both readable
and writable. The R / W values are reset to the values set by the web server if the access time to the registers is exceeded or the unit is switched
off. The most significant bit is represented by the highest value, for example, between B00 and B15, the latter represents the most significant.
ADDRESS
WORD
ID
FORMAT
R/W
DESCRIPTION VALUES AT IGNITION
OR TO DISCONNECT
CONFIGURATION
1
SW_PN_0
SW TYPE 0
R
MODEL SW
2
SW_PN_1
SW TYPE 1
R
MODEL SW
3
SW_PN_2
SW VER 0 (AAMM)
R
VERSION SW
4
SW_PN_3
SW VER 1 (DDPP)
R
VERSION SW
5
REMOTE_CONTROL
B00: R/W DEVICE_RESET (1=RESET)
BIT NOTICE RESET CARD:
BY DEFAULT = 1, IF IT IS ADJUSTED TO 0 AND AF-
TER IT IS IN 1 IT MEANS THAT THERE HAS BEEN A
RESET OF THE CARD.
B01: R TERMINAL_ACTIVE (1=ACTIVE)
TERMINAL CONNECTION.
B02: R TERM_RS485_ACTIVE (1=ACTIVE)
TERMINAL CONNECTION. RS485.
B04: R/W CONNECTION_LOST 1=LOST)
BIT NOTICE DISCONNECT: DEFAULT = 0, IF BELOW
IT IS IN 1 IT MEANS THAT THERE HAS BEEN A
DISCONNECT
B13: R/W CMD DEVICE RESET (1=RESET)
DEFAULT = 0; IF IT IS ADJUSTED TO 1 THE CARD
RESTS
B14: R/W WR_APP_CONF (1=WRITE PEN-
DING)
BIT TO MEMORIZE THE CONFIGURATION IN NO-
VRAM (YES = 1)
B15: R/W WR_SP (1=WRITE PENDING)
BIT TO MEMORIZE IN NOVRAM THE ADJUSTMENT
POINTS (YES = 1)
20
PARAMETER_FLAGS
B00- 01: R/W SEASON
0: SEASON_ND
1: SEASON_WINTER
2: SEASON_SUMMER
B02- 03: R/W BYPASS
0: BYPASS_AUTO
1: BYPASS_OFF
2: BYPASS_ON
R/W
ADJUSTMENT BYPASS STATION (B00 B01)
0=NON DEF.\AUTO
1=WINTER W
2=SUMMER
UNIVERSAL(B02 B03)
0=NON DEF.\AUTO
1=OFF
2=ON
24
UNIT_1_MAX_FILT_
HOURS
0- 199 (500h)
R/W THRESHOLD ALARM FILTERS HOURS UNIT 1
25
UNIT_2_MAX_FILT_
HOURS
0- 199 (500h)
R/W THRESHOLD ALARM FILTERS HOURS UNIT 2
26
UNIT_3_MAX_FILT_
HOURS
0- 199 (500h)
R/W THRESHOLD ALARM FILTERS HOURS UNIT 3
27
UNIT_4_MAX_FILT_
HOURS
0- 199 (500h)
R/W THRESHOLD ALARM FILTERS HOURS UNIT 4