29
CV072018-1
86
STATUS_FLAGS
DIGITAL INPUT:
R
ESTADO ENTRADA DIGITAL (1=ACTIVO):
B00: BYPASS
BYPASS STATUS: 1 = OPEN; 0 = CLOSED
B01: SUPPLY_SPEED_REM_CONT_ACTIVE
ENABLING CONTROL
INDEPENDENT IMPULSION FAN
ACTIVE
B02: EXHAUST_SPEED_REM_CONT_ ACTIVE
ENABLING CONTROL
INDEPENDENT FAN RETURN
ACTIVE
B03: DEHUM_ON
ACTIVE DEHUMIDIFICATION
B04: NOFROST_ACTIVE
ANTIFREEZE STATE
B05: EXT_DI_HUMIDITY
STATE DIGITAL ENTRY: HUMIDITY
B06: EXT_DI_PIR_MIN
STATE DIGITAL ENTRY: PIR
B07: EXT_DI_REMOTE_OFF
STATE DIGITAL ENTRY: REMOTE
B08: HEAT\COOL_1
STATE 1 POSCALENT / REFRIG.
B09: HEAT_2
STAGE 2 POSCALENT.
B10: TEMP_WATER_LOW
ANTIFREEZE STATE WATER BATTERY
B11: EXT_DI_SUMMER
STATE DIGITAL ENTRY: STATION
B12: EXT_DI_FIRE
STATE DIGITAL ENTRY: FIRE
B13: EXT_DI_WATER_NOFROST
ANTIFREEZE WATER BATTERY
B14: EXT_DO_AUTO_COMPARE
DIGITAL OUT STATUS: AUTO COMPARE
87
SPEED_C_VALUE
IF FANS_FAIL_TACH (REG 7 –B08) IS SET TO
1 RPM, OTHERWISE %
R
SPEED FAN IN RETURNS OR PERCENTAGE (SEE
REGISTER 7- B08)
88
SPEED_D_VALUE
IF FANS_FAIL_TACH (REG 7 –B08) IS SET TO
1 RPM, OTHERWISE %
R
SPEED FAN RETURN RETURNS OR PERCENTAGE
(SEE REGISTER 7- B08)
89
AUTO_INPUT_VALUE
%
R
PERCENTAGE READING VALUE: PROBE
AIR QUALITY (=% 2000 PPM) HUMIDITY
EXTERNAL SIGN
90
ALARMS 1
B00: COMM_X540_FAIL
R
COMMUNICATION ERROR CARD X540.
B01: TE_FAIL
FAULT LINE EXTERNAL PROBE.
B02: TR_FAIL
FAULT LINE RETURN PROBE.
B03: TX_FAIL
FAULT LINE EXPULSION PROBE.
B04: FILTERS_FAIL
ALARM FILTERS STAMPED.
B05: FANS_FAIL
FAN FAILURE.
B06: AUTO_FAIL
FAILURE PROBE AIR / HUMIDITY.
B07: TI_FAIL
FAULT LINE ADMISSION PROBE.
B08: COMM_X531_FAIL
COMMUNICATION ERROR CARD X531.
B09: TW_FAIL
ICE ALARM WATER BATTERY.
B10: TW_LOW
ALARM TIME WAITING PROBE QUALITY
AIR / MOISTURE.
B11: AUTO_TO_FAIL
COMMUNICATION ERROR CARD
X570 IMPULSION.
B12: COMM_X570_DPS_FAIL
COMMUNICATION ERROR CARD X570
RETURN.
B13: COMM_X570_DPE_FAIL
PRESSURE SENSOR FAILURE IMPULSION.
B14: DPSUPPLY_FAIL
PRESSURE SENSOR FAILURE RETURN.