31
F20
FUNCTION : Measurement Mode
DISPLAY
DESCRIPTION
F20 0
Do not use.
F20 1
Normal batching
F20 2
Customer Programmed
Control mode
Loss-in-Weight batching
F20 3
Normal batching
Set value
( 0 ~ 4 )
F20 4
Built-in automatic
Program mode
Loss-in-Weight batching
F21
FUNCTION : Timer – Start Delay Time of Finish Signal
DISPLAY
DESCRIPTION
F21 00
No delay time
F21 10
1.0 sec
Set value
( 00 ~ 99 )
F21 99
9.9 sec
Note 1. This function is used to decide the delay time of start- signal of output which the batching
operation is completed
F22
FUNCTION : Off Range of Finish Signal
DISPLAY
DESCRIPTION
F22 00
Do not use
F22 01
Finish signal is off when the weight is within one division
Set value
( 00 ~ 99 )
F22 99
Finish signal is off when the weight is within ninety nine
division
Note 1. This function is used to decide the size of output signal which batching- operation is
completed.
Note 2. You have to set F19 to 00 if you want to use the F22 function.
If F19 & F22 are set any values at the same time, F22 is disregarded.
Because the priority of F19 is high
Содержание CI-6000A Series
Страница 1: ...2 ...
Страница 8: ...9 4 Measure of Appearance ...
Страница 22: ...23 5 Sealing Method Sealing method of cal switch Sealing method of Load Cell Connector ...
Страница 51: ...52 Normal Batching Diagram Loss in Weight Batching Diagram ...
Страница 52: ...53 USER PROGRAM CONTROLMODE Normal Batching ...
Страница 54: ...55 USER PROGRAM CONTROLMODE Loss in Weight ...
Страница 56: ...57 AUTOMATIC PROGRAM CONTROLMODE Normal Batching ...
Страница 58: ...59 AUTOMATIC PROGRAM CONTROLMODE Loss in Weight ...
Страница 71: ...72 MEMO ...
Страница 72: ...73 MEMO ...
Страница 73: ...74 MEMO ...
Страница 74: ...75 ...