11
2. 40VCAR17FQEE address setting
Control single split or multi type
One indoor unit needs to be configured with one 40VCAR17FQEE converter. The
address of 40VCAR17FQEE can be set as below
SW01
define
[1]
[2]
[3]
[4]
[5]
[6] [7] [8]
0
--
--
--
--
--
-- --
Single mode
1
--
--
--
--
--
-- --
Dual units switching mode
--
0
0
--
--
--
--
--
Switching time1: 8 hours
--
0
1
--
--
--
--
--
Switching time2: 10 hours
--
1
0
--
--
--
--
--
Switching time3: 12 hours
--
1
1
--
--
--
--
--
Switching time1: 24 hours
--
--
--
0
--
--
--
--
Dual units
running temp
26℃
--
--
--
1
--
--
--
--
Dual units
running temp
24℃
1
--
--
--
0
0
0
0
Dual mode address= 1
1
--
--
--
0
0
0
1
Dual mode address= 2
----
1
--
--
--
1
1
1
0
Dual mode address= 15
1
--
--
--
1
1
1
1
Dual mode address= 16
0
0
0
0
0
0
0
0
Single mode address =1
0
0
0
0
0
0
0
1
Single mode address =2
----
----
0
1
1
1
1
1
1
0
Single mode address =127
0
1
1
1
1
1
1
1
Single mode address =128