9
Gateway address setting
For the units connected to centralized controller, it is required to use indoor units’ dip switch
or address setting remote controller to set the indoor units address, which is convenient for
inspection and maintenance.
Control VRF models
For every system of VRF, address starts from No.1 to last indoor unit of the system. If totally
20 indoor units are connect in one system, address should be 1-20. If there are 50 indoor
units in one system, address should be 1-50. The maximum indoor unit address cannot
exceed 64
Note: The indoor unit address setting of each VRF system starts from 1
The gateway address setting range is 1-32
Gateway address setting
SW01
SW02
address
0
1
address=1
0
2
address=2
0
3
address=3
0
4
address=4
0
5
address=5
0
6
address=6
0
7
address=7
0
8
address=8
0
9
address=9
1
0
address=10
1
1
address=11
1
2
address=12
1
3
address=13
1
4
address=14
1
5
address=15
1
6
address=16
1
7
address=17
1
8
address=18
1
9
address=19
2
0
address=20
2
1
address=21
2
2
address=22
2
3
address=23
2
4
address=24
2
5
address=25
2
6
address=26
2
7
address=27
2
8
address=28
2
9
address=29
3
0
address=30
3
1
address=31
3
2
address=32