13
The user displays maintenance tables using ComfortWORKS, the
Building Supervisor or a Network Service Tool. The values dis-
played in these tables are read-only displays of dynamic values.
You cannot enter data into any maintenance fields except to force a
manual diagnostic alert. For instructions on accessing these tables
and for descriptions of the fields within each table, refer to the
Maintenance section.
When an alarm or alert is generated by a system element at the
monitored site and the TeLINK buffer is not full, the monitored
site’s TeLINK will perform a sequence of operations.
Refer to the Monitoring Center Definition (MONTRDEF) Table and
to the flowchart in Appendix A.
The TeLINK distinguishes between alarm messages and alert
messages that originate on its CCN.
1.
When an alarm is identified, the TeLINK determines the
occupancy state and whether the beeper feature is enabled. If
so, and the alarm priority level is equal to or greater than the
beeper threshold, the TeLINK dials the configured beeper
number.
2.
If the TeLINK is configured to report alarms to a monitoring
center, the alarm is added to the buffer. The alarm priority
level is compared to the Alarm Threshold decision and the
TeLINK attempts to transmit the alarm using the primary
number.
If the alarm priority level is lower than the alarm threshold, it
is treated as an alert, which is described on the next page.
3.
If the connection to the monitoring site is unsuccessful, the
TeLINK dials the secondary number (if one is configured).
This process continues until a successful connection is made.
Note:
The state of occupancy is checked each time an
attempt is made to dial a different phone number.
Sequence of
Operation
How the Monitored Site
Transmits Alarm(s)/
Alert(s) to the
Monitoring Site
Alarm
Содержание TeLINK
Страница 1: ...Overview and Configuration Manual TeLINK ...
Страница 2: ...Overview and Configuration Manual TeLINK ...
Страница 5: ...iv ...
Страница 9: ...viii ...
Страница 10: ...Introduction ...
Страница 14: ...4 ...
Страница 15: ...Operating Characteristics ...
Страница 17: ...6 Figure 2 TeLINK front and back views Back Front ...
Страница 27: ...16 ...
Страница 28: ...Configuration ...
Страница 39: ...Maintenance ...
Страница 46: ...Configuration Sheets ...
Страница 52: ...38 ...
Страница 53: ...Appendixes ...
Страница 60: ...Index ...
Страница 65: ...Printed in U S A 808 971 Rev 11 99 ...