17
TeLINK operation is controlled by decisions entered in a group of
configuration tables. Each TeLINK contains the following configu-
ration tables:
ALARMDEF
Alarm Processing Definition Table
Ctlr-ID
Controller Identification Table
MODEMCFG
Modem Configuration Table
MONTRDEF
Monitoring Center Definition Table
RCSI_CFG
TeLINK Configuration Table
OCCPC01S
Occupancy Configuration Table
Figure 4 illustrates this table. An explanation of each configuration
decision follows.
This decision allows you to control whether alarms are processed on
days configured as holiday in the time schedule.
Allowable Entries
Yes/No
Default Value
Yes
Configuration
Alarm Processing
Definition
(ALARMDEF) Table
Figure 4
Alarm
Processing
Definition
(ALARMDEF)
Table
ALARMDEF
Description
Holiday Alarm Reporting
Alarm When Occupied?
Alarm When Unoccupied?
Alarm Threshold
Beeper When Ocucpied?
Alarm Services
Value
Units
Name
Notes
Beeper When Unoccupied?
Beeper Threshold
Alarm Acknowledger?
Diag. Alert Target Hour
Building Number
Customer Code
No
No
7
No
No
7
SEND_OCC
SENDUNOC
ALMTHRSH
SENDUNOC
ALMTHRSH
ALARMACK
BLDG_NUM
CUSTCODE
Alarm Services
Yes
Yes
0
1
1
HOL_ALMS
SEND_OCC
ALRTHOUR
Holiday Alarm
Reporting
Содержание TeLINK
Страница 1: ...Overview and Configuration Manual TeLINK ...
Страница 2: ...Overview and Configuration Manual TeLINK ...
Страница 5: ...iv ...
Страница 9: ...viii ...
Страница 10: ...Introduction ...
Страница 14: ...4 ...
Страница 15: ...Operating Characteristics ...
Страница 17: ...6 Figure 2 TeLINK front and back views Back Front ...
Страница 27: ...16 ...
Страница 28: ...Configuration ...
Страница 39: ...Maintenance ...
Страница 46: ...Configuration Sheets ...
Страница 52: ...38 ...
Страница 53: ...Appendixes ...
Страница 60: ...Index ...
Страница 65: ...Printed in U S A 808 971 Rev 11 99 ...