12
The time schedule contains eight user-configurable periods that
determine the current state of the occupancy table. The state can be
either occupied or unoccupied. When the current time in the
TeLINK falls within any of the configured periods, the state of
occupancy will be occupied, otherwise the state will be unoccupied.
The Alarm Processing Definition Table allows you to decide during
which state(s) of occupancy to send alarms. The Monitoring Center
Definition Table allows you to configure the occupied and unoccu-
pied telephone numbers to be used by the monitored site’s TeLINK
when reporting alarms to a remote monitoring site.
Figures 3a and 3b illustrate the use of time schedules for alarm
reporting during occupied and unoccupied states. In the example
shown, the TeLINKs in Buildings 2, 3, and 4 are configured so that
during occupied states (typically during the day when the service
person is on duty), alarms are transmitted to Building 1. During
unoccupied states (typically during the night when the service
person is off duty), the TeLINKs are configured to send alarms to a
different monitoring site. The alarms’ destination during unoccu-
pied states may be another monitoring site belonging to the same
customer with round-the-clock staffing, or it may be a regional
monitoring center.
The user can display three TeLINK maintenance tables:
•
The alarm maintenance (ALARMMNT) table displays data for
all the alarms currently stored in the TeLINK (maximum of
four).
•
The monitoring center maintenance table (MONCTMNT) shows
status data for the occupied and unoccupied centers.
•
The TeLINK maintenance table (RCSI_MNT) displays modem,
connection, and alarm data, along with time and holiday infor-
mation.
All of the data in these tables is continually changing and being
updated on the screen.
TeLINK
Maintenance
Tables
Содержание TeLINK
Страница 1: ...Overview and Configuration Manual TeLINK ...
Страница 2: ...Overview and Configuration Manual TeLINK ...
Страница 5: ...iv ...
Страница 9: ...viii ...
Страница 10: ...Introduction ...
Страница 14: ...4 ...
Страница 15: ...Operating Characteristics ...
Страница 17: ...6 Figure 2 TeLINK front and back views Back Front ...
Страница 27: ...16 ...
Страница 28: ...Configuration ...
Страница 39: ...Maintenance ...
Страница 46: ...Configuration Sheets ...
Страница 52: ...38 ...
Страница 53: ...Appendixes ...
Страница 60: ...Index ...
Страница 65: ...Printed in U S A 808 971 Rev 11 99 ...