9
Unit Configuration Screen
Fig. 11 —Unit Configuration Screen
Table 3 —Unit Configuration
Description
Point
R/W
States
Control Mode
wc_or_tstat
R/W
Wall T-Stat (0) / I-Vu / BAS (1)
Unit Commanded State
unit_cmd_state
R/W
Off (0) / On (1)
Mode Control
zone_mode_ctrl
R/W
Auto (1) / Heat (2) / Cool (3)
Manual Op Mode Control
op_mode_cmd
R/W
Heat (1) / Cool (2) / Fan (3) / Dry (4) / Auto (5) / Inactive (6)
Manual Fan Speed Control
fan_spd_cmdx
R/W
Auto (1) / High (2) / Medium (3) / Low (4)
Louver Setting
luvr_set
R/W
Stop (1) / Swing (2) / Down (3) / 25% Up (4) / 50%
Up (5) / 75% Up (6) / 100% Up (7) Se
Min Setpoint Separation
min_stpt_sep
R/W
2 Deg F – 10 Deg F
(5 Deg F)
Cooling Lockout
Temperature
oat_cl_lockout
R/W
-65 deg F - 80 deg F
(45 Deg F)
Heating Lockout
Temperature
oat_ht_lockout
R/W
35 deg F - 150 deg F
(65 Deg F)