16
Table 15 —Service Configuration Screen
Name
Description
Fire/Smk Shutdown
Displays the state of the Fire/Smoke detector input.
Mode Control Source
Displays the source of the operating mode control.
Controlling Mode Output
Displays the value of the control mode being sent to the local unit
control from the application.
Setpoint Control Source
Displays the source of the setpoint control.
Controlling Temp Output
Displays the value of the setpoint being sent to the local control from
the application.
Effective Heat Setpoint
Displays the current heating setpoint.
Effective Cool Setpoint
Displays the current cooling setpoint.
Fan Speed Output
Displays the value of the fan speed being sent to the local control from
the application.
Louver Position
Displays the position of the louver (valid only if equipped)
Comm Status
Displays whether or not there is a communication error between the
TCC Link and the individual VRF units
Unit Connection
Displays whether the individual VRF unit is powered on or off
Refrigerant System Address
Displays the address of the refrigeration system.
Indoor Unit Number
Displays the address of this indoor unit
Max Permitted Temp Setting in Heat Mode
Displays the maximum allowable temperature setting in heat mode
Min Permitted Temp Setting in Heat Mode
Displays the minimum allowable temperature setting in heat mode
Max Permitted Temp Setting in Cool Mode
Displays the maximum allowable temperature setting in cool mode
Min Permitted Temp Setting in Cool Mode
Displays the minimum allowable temperature setting in cool mode
Max Permitted Temp Setting in Dry Mode
Displays the maximum allowable temperature setting in dry mode
Min Permitted Temp Setting in Dry Mode
Displays the minimum allowable temperature setting in dry mode
Max Permitted Temp Setting in Auto Mode
Displays the maximum allowable temperature setting in auto mode
Min Permitted Temp Setting in Auto Mode
Displays the minimum allowable temperature setting in auto mode
Permitted Fan Speed Setting BIT1
Displays if low speed fan operation is permitted
Permitted Fan Speed Setting BIT2
Displays if medium speed fan operation is permitted
Permitted Fan Speed Setting BIT3
Displays if high speed fan operation is permitted
Permitted Fan Speed Setting BIT4
Displays if auto fan speed operation is permitted
Permitted Operation Heat
Displays if Heat mode operation is permitted
Permitted Operation Cool
Displays if Cool mode operation is permitted
Permitted Operation Fan
Displays if Fan mode operation is permitted
Permitted Operation Dry
Displays if Dry mode operation is permitted
Permitted Operation Auto
Displays if Auto mode operation is permitted
ON / OFF Permit/Prohibit Monitoring
Displays if ON /OFF control is permitted at the local user interface
Op Mode Permit/Prohibit Monitoring
Displays if Op Mode changes are permitted at the local user interface
Set Temp Permit/Prohibit Monitoring
Displays if Setpoint adjustments/ changes are permitted at the local
User interface
Reset Filter
Provides the ability to reset the filter status alarm after the filter has
been cleaned or replaced