Carrier OPN-MTCC Скачать руководство пользователя страница 5

5

Step 5 — Powering on the Unit

1.

Verify all the connections are correct and as per the
wiring diagram shown in Fig. 5.

2.

Set the main breaker in the unit to 

ON

 position.

3.

Secure the latches, and use the four screws provided to secure
the top cover on the enclosure.

4.

Supply 115V-1Ph-60Hz power to the i-Vu® interface.

NOTE: For a complete guide to setting up the i-Vu

OPenlink router, please refer to the i-Vu Open Link
Installation Guide: http://dms.hvacpartners.com/docs/
1000/public/03/11-808-462-01.pdf

Step 6 — To obtain an IP address using DHCP

1.

Turn the i-Vu® Open Link's power off.

2.

Set the IP Addr DIP switch to OFF (DHCP).

3.

Turn the i-Vu® Open Link's power on. The DHCP server 
assigns an IP address to the i-Vu® Open Link.

To assign a custom IP address:

1.

Obtain the IP address, subnet mask, and default gateway 
address for the controller from the facility network 
administrator.

2.

Set the IP Addr DIP switch #2 to OFF (DHCP).

3.

Turn the i-Vu® Open Link's power off.Set the i-Vu® Open
Link's IP Addr DIP switch to ON (assigned).

4.

Set the i-Vu® Open Link's IP Addr DIP switch to ON 
(assigned).

5.

Configure the i-Vu® Open Link by setting the Router Config
Mode set DIP switch #1 to (Console):

a.

ON

 for a terminal program, such as 

HyperTerminal

b.

OFF

 for Carrier software

NOTE!: The DIP switch on older models was labeled
“HyperTerminal”.

6.

Turn the i-Vu® Open Link's power on.

7.

Connect to the Links local access port with the USB-L cable
from the USB-TKIT kit or the cable can be purchases
separately. (p/n USB-L). The connection is on the left side of the
Link. Connect the other end of the cable to a computer’s USB
port and install the driver for the USB-L if needed.

8.

Once this cable is connected to the computer, check the Device
Manager to see what COM port the CP210x is connected to, in
the example below it is connected to 

COM3

.

9.

Configure HyperTerminal® or PuTTY® to communicate
serially to that COM port at a baud of 115200. Make sure the
flow control is set to 

NONE

.

10.

Once your PuTTY® or HyperTerminal ® is setup, start it, hit
the enter key once the communications window is open.

11.

Access the different menu items to change the I.P., subnet and
default gateway at a minimum.

12.

When done changing the information, type 1 to reset the link to
lock the values in.

13.

After resetting, hit the enter key again to verify the changes have
been changed and locked in.

14.

Progress to Verifying the i-Vu server can communicate with the
i-Vu Interface.

Step 7 — Verifying the i-Vu server can
Communicate with the i-Vu Interface

1.

Power on the i-Vu server.

2.

Select the router on the main page and then click 

Upload

 (see

Fig. 6).

Fig. 6 —Technician Tool

3.

Expand the router on the far left and see all the Indoor Units programs up to 64. Select one of possible 64 programs and then along the top, select
the 

PROPERTIES

  tab,  then  select  the 

NETWORK

 

POINTS

 tab and the following message appears. “

Review the Error column, the

messages should be “0 No Error

”.

Содержание OPN-MTCC

Страница 1: ...t editions of the National Electrical Code NEC ANSI NFPA American National Standards Institute National Fire Protection Association 70 In Canada refer to the current editions of the Canadian Electrical Code CSA Canadian Standards Association C22 1 Understand the signal words DANGER WARNING and CAUTION DANGER identifies the most serious hazards which will result in severe personal injury or death W...

Страница 2: ...onments such as rain snow or extreme temperature theft vandalism and debris on job site Equipment covered in this manual is not suitable for outdoor installations Failure to do so may have serious adverse effects on unit operation and in the case of circuit board assembly may result in immediate or premature failure Failure of any unit caused by deposits of foreign material will not be covered by ...

Страница 3: ...condensing unit of the Toshiba Carrier VRF system 2 Feed the communication cables through the pre drilled hole for low voltage wiring 3 Secure the U1U2 communication cable to the cabinet per the local code Fig 3 i Vu Enclosure 1 Use the following wiring materials to connect the field supplied communication cable Line specification A Type 2 core shielded wires B Wire size 16 gage 330 ft max C 14 ga...

Страница 4: ...ow Voltage Wiring CLASS 2 Y W GREEN WHITE YELLOW W WHITE STRIPE GRN COLOR IDENTIFICATION RED YEL RED Legend BR BARE Terminal Factory installed Wiring Field installed wiring Wire color See color identification chart for refe BLK BLACK YELLOW 115VAC 60Hz 1Ph Power supply 0 5A Circuit Breaker Main Bus U1 U2 Y W 5VDC 6A Transformer Ground Terminal Block Line Terminal Block Ground Terminal Block BLK WH...

Страница 5: ...nect to the Links local access port with the USB L cable from the USB TKIT kit or the cable can be purchases separately p n USB L The connection is on the left side of the Link Connect the other end of the cable to a computer s USB port and install the driver for the USB L if needed 8 Once this cable is connected to the computer check the Device Manager to see what COM port the CP210x is connected...

Страница 6: ...nd check for the message No Error in the Error column This program displays the status of the Modbus registers that reside in the TCC Link All Toshiba Carrier Unit X programs have points that reside only in the Controllers and are sent to the TCC Link when requested Use the System Info tab to get the values from the Toshiba Carrier VRF System to verify that the i Vu Open Link is communicating with...

Страница 7: ...7 Fig 9 Technician Tool ...

Страница 8: ... Alarm Code alarm_code R 1 to 255 1 FSD Alarm 0 255 unit alarms Operation Mode op_mode_stat R Heat 1 Cool 2 Fan 3 Dry 4 Auto Heat 5 Auto Cool 6 Off 7 Zone Temp suc_tmp R deg F Temp Setpoint tmp_mon R deg F Fan Speed fan_spd_mon R Stop 1 Auto 2 High 3 Medium 4 Low 5 Very Low 6 Filter Status filt R Clean 0 Dirty 1 Shutdown Shutdown R W Inactive 0 Active 1 ...

Страница 9: ...t 2 Cool 3 Manual Op Mode Control op_mode_cmd R W Heat 1 Cool 2 Fan 3 Dry 4 Auto 5 Inactive 6 Manual Fan Speed Control fan_spd_cmdx R W Auto 1 High 2 Medium 3 Low 4 Louver Setting luvr_set R W Stop 1 Swing 2 Down 3 25 Up 4 50 Up 5 75 Up 6 100 Up 7 Se Min Setpoint Separation min_stpt_sep R W 2 Deg F 10 Deg F 5 Deg F Cooling Lockout Temperature oat_cl_lockout R W 65 deg F 80 deg F 45 Deg F Heating L...

Страница 10: ...Occupied Heating Setpoint occ_ht_stpt R W 55 deg F 90 deg F 70 deg F Unoccupied Cooling Setpoint unocc_cl_stpt R W 65 deg F 99 deg F 85 deg F Unoccupied Heating Setpoint unocc_ht_stpt R W 50 deg F 80 deg F 65 deg F Effective Cool Setpoint effective_cl_stpt R deg F Effective Heat Setpoint effective_ht_stpt R deg F Optimal Start optm_star R W 1 hour 4 hours 4 hours ...

Страница 11: ...ig 13 Alarm Configuration Screen Table 5 Alarm Configuration Description Point States High Temperature Alarm Limit spt_alrm_hi_lm R W 40 deg F 100 deg F 95 deg F Low Temperature Alarm Limit spt_alrm_lo_lmt 35 deg F 90 deg F 45 deg F ...

Страница 12: ... Unit Type unit_type R Air Conditioning 1 Ventilator 2 Local Unit ON OFF Control unit_onoff_ena R W Allow 0 Prohibit 1 Local Op Mode Control op_mode_ena R W Allow 0 Prohibit 1 Local Setpoint Control setpoint_ena R W Allow 0 Prohibit 1 System Outdoor Air Temperature bacnet AV 80001 deg F System Fire Smoke bacnet Off 0 On 1 Fire Smk Shutdown BBV Normal Mode Control Source Normal BAS Controlling Mode...

Страница 13: ...in Cool Mod deg F Min Permitted Temp Setting in Cool Mode deg F Max Permitted Temp Setting in Dry Mode deg F Min Permitted Temp Setting in Dry Mode deg F Max Permitted Temp Setting in Auto Mode deg F Min Permitted Temp Setting in Auto Mode deg F Permitted Fan Speed Setting BIT1 Off 0 L 1 Permitted Fan Speed Setting BIT2 Off 0 H 1 Permitted Fan Speed Setting BIT3 Off 0 HH 1 Permitted Fan Speed Sett...

Страница 14: ...hen OFF no heating cooling or fan operation is provided Mode must be on for any local or BAS control Alarm Status Indicates if any alarms are currently active Alarm Code If the Alarm Status above is in alarm then this value represents the alarm code received from the zone control Operation Mode Displays the current operational mode used by the zone control Zone Temp Displays the zone temperature o...

Страница 15: ...cifies the temperature at which when the OAT falls below cooling will no longer be available to operate Heating Lockout Temperature Specifies the temperature at which when the OAT rises above heating will no longer be available to operate Name Description High Temperature Alarm Limit Use to determine the maximum allowable zone temperature that can occur in this zone at any time If a zone temperatu...

Страница 16: ...ol mode Min Permitted Temp Setting in Cool Mode Displays the minimum allowable temperature setting in cool mode Max Permitted Temp Setting in Dry Mode Displays the maximum allowable temperature setting in dry mode Min Permitted Temp Setting in Dry Mode Displays the minimum allowable temperature setting in dry mode Max Permitted Temp Setting in Auto Mode Displays the maximum allowable temperature s...

Страница 17: ...ame Description Occupancy Status Displays the current occupancy state Local BACnet Schedule Displays the current state of the occupancy schedule where OFF is unoccupied and ON is occupied Name Description Link Comm Connection Displays whether the TCC Link is communicating to the VRF unit Fire Smoke Shutdown Displays when the operation has been disabled due to an active Fire Smoke condition Unit Al...

Страница 18: ...during automatic address 55 E21 Header thermal storage units quantity error 56 E22 Decease of No of thermal storage units 57 E23 Sending error in communication between outdoor units 58 Reserved 59 E25 Duplicated follower outdoor address 5A E26 Decrease of No of connected outdoor units 5C E28 Follower outdoor unit error 5F E31 IPDU communication error 61 F01 Indoor TCJ sensor error 62 F02 Indoor TC...

Страница 19: ...torage units DB L27 Thermal storage units quantity error DC L28 Maximum number of outdoor units exceeded DD L29 No of IPDU error DE L30 Auxiliary interlock in indoor unit DF L31 IC error E1 P01 Indoor fan motor error E3 P03 Discharge temp TD1 error E4 P04 High pressure switch detection error E5 P05 Phase missing detection Phase order error E7 P07 Heat sink overheat error EA P10 Indoor overflow err...

Страница 20: ...oling or allows the unit to automatically switch modes as required if the Auto mode is selected Additionally the Manual Op Mode Control provides the ability to lock the unit in a specific mode must be set to Inactive for normal operation Additional manual overrides are provided for fan speed Manual Fan Speed Control and Louver positioning Louver Setting if applicable During the occupied period the...

Страница 21: ...g mode temperature range air direction and airflow of the indoor units differ according to the unit type 8 When the power to the outdoor units of a multi air conditioning system is interrupted or when the system is being re booted the TCC LINK board cuts TCC LINK communication The response to communication break is Exception Response 0 x 06 9 The register TCC LINK bus error will be Error 1 when al...

Страница 22: ...T UP Central Control Address Setting Group Address M M M M M ME E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E EN N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N NU U U U C C C C C C C C C C C C CA A A A A AN N N N N N N N NC C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C CE E E E E E E E E E E EL L M M M M M ME E E E E E E E E ...

Страница 23: ...button to display the menu screen 2 Push and hold the MENU button and the button at the same time to display the Field setting menu M M M M M ME E E E E E E E E E E E E E E E E E E E E E E E E E E E E E EN N N N N N N N N N N N N N N N N N N N N N N N N N NU U U M ME E E E E E E E E E E E E E E E E E E E EN N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N NU U U U U U U U U U 2 ...

Страница 24: ... T ET SET C C C CL L L CL L C CL L L CL L C CL TIME ME ME E ME E E T TIMER TI IMER TIMER TI IMER R T TIMER TIMER S SET SET SET S S SET T S S SE FAN F FAN FA A A AN FAN N FAN FAN FA A A AN FA A A FA AN FA A AN SWING SWING SWING SWING WING WING SWING FIX FIX FIX FIX UNIT UNIT UNIT UNIT U UN VEN NT MOD DE ST TE E SET S TIME E TEMP TEM EMP EM EMP P P EMP P P P EMP P P P P P P P MP MP CODE No TEM MP P ...

Страница 25: ...rietary Information Not for Further Distribution STEP 5 TEST button FINISH Push button to exit DN menu START UP Control Wire Addressing Group Address T T T T T T T T T T T T T T T T T T T T T T T T T T T T T TE ES ES S E E E E E E E T T b b b button MANUAL ADDRESS SETTING 4 ...

Страница 26: ...t to discontinue or change at any time specifications or designs without notice and without incurring obligations Catalog No 18 OPNMTCC 001 Printed in U S A Form OPN MTCC 3SI Pg 26 02 18 Replaces OPN MTCC 2SI Carrier Corporation 2018 ...

Отзывы: