Alarms
Fig. 15 —Alarms
Table 10 —Alarms
Table 11 —Status Screen
Description
Point
States
Link Comm Connection
uconn_alm
R
Normal / Connect (0) / Alarm / Comm Failure (1)
Fire / Smoke Shutdown
fire_alarm
R
Normal (0) / Alarm (1)
Unit Alarm Status
det_alarm
R
No Alarm (0) / In Alarm (1)
Comm Status
comm_error
R
Normal (0) / Comm Error (1)
Zone Temperature
spt_alarm
R
Normal (0) / Alarm (1)
Outdoor Air Temp Sensor
oat_fail
R
Normal (0) / Alarm (1)
Filter
filter_alarm
R
Clean (0) / Dirty (1)
Name
Description
Unit Status
Displays the operational status of this zone. When OFF, no heating,
cooling, or fan operation is provided. Mode must be on for any local or
BAS control.
Alarm Status
Indicates if any alarms are currently active.
Alarm Code
If the Alarm Status above is in alarm, then this value represents the alarm
code received from the zone control.
Operation Mode
Displays the current operational mode used by the zone control.
Zone Temp
Displays the zone temperature of the zone.
Temp Setpoint
Displays the current setpoint used by the zone controller.
Fan Speed
Displays the current fan operating speed.
Filter Status
Displays the current condition of the filter.
Shutdown
When the Control Mode is set to i-Vu / BAS, this point may be set to
Shutdown to stop the equipment operation in this zone.