Table 12 —Unit Configuration Screen
Table 13 —Alarm Configuration Screen
Table 14 —Service Configuration Screen
Name
Description
Control Mode
Use to monitor the operation of the zone when set to Wall T-Stat. When
set to i-Vu / BAS, it allows the ability to utilize the occupancy and
setpoint schedule programming to operate the zone.
Unit Commanded State
When the Control Mode is set to i-Vu / BAS, this option is used to
enable the zone control or disable any control operation.
Mode Control
When the Control Mode is set to i-Vu / BAS, this decision is used to
determine and set the allowable mode of operation for automatic
control.
Manual Op Mode Control
When the Control Mode is set to i-Vu / BAS, this decision is used to
manually initiate any specific mode and hold that mode unless
overridden by the local user interface.
Manual Fan Speed Control
When the Control Mode is set to i-Vu / BAS, this decision is used to
manually initiate a specific fan speed and hold that mode unless
overridden by the local user interface.
Louver Setting
When the Control Mode is set to i-Vu / BAS, this decision is used to
manually position the louver if so equipped.
Min Setpoint Separation
Use to determine the minimum amount of separation (deadband)
between the heating and cooling setpoints when the setpoint schedule
is being used.
Cooling Lockout Temperature
Specifies the temperature at which when the OAT falls below, cooling
will no longer be available to operate.
Heating Lockout Temperature
Specifies the temperature at which when the OAT rises above, heating
will no longer be available to operate.
Name
Description
High Temperature Alarm Limit
Use to determine the maximum allowable zone temperature that can
occur in this zone at any time. If a zone temperature above this value
occurs for more than 1 minute, an alarm is generated.
Low Temperature Alarm Limit
Use to determine the minimum allowable zone temperature that can
occur in this zone at any time. If a zone temperature below this value
occurs for more than 1 minute, an alarm is generated.
Name
Description
Zone Temp Sensor Location
Use to set the location of the sensor used to sense the zone’s
temperature. It will be used to properly display that position on the
graphic.
Unit Type
Displays the unit type
Local Unit ON/OFF Control
Use to allow or prohibit the local user from setting the unit to On or Off
through the local user interface device.
Local Op Mode Control
Use to allow or prohibit the local user from changing the unit mode
through the local user interface device.
Local Setpoint Control
Use to allow or prohibit the local user from changing the setpoint
through the local user interface device.
System Outdoor Air Temperature
Displays the address and value received from the network OA
temperature sensor (if used).
System Fire / Smoke
Displays the address and value received from the network Fire /
Smoke Detector point (if used).