10
Setpoint Screen
Fig. 12 —Setpoint Screen
Table 4 —Unit Configuration
Description
Point
States
Occupied Cooling
Setpoint
occ_cl_stpt
R/W
60 deg F - 99 deg F
(76 deg F)
Occupied Heating
Setpoint
occ_ht_stpt
R/W
55 deg F - 90 deg F
(70 deg F)
Unoccupied Cooling
Setpoint
unocc_cl_stpt
R/W
65 deg F - 99 deg F
(85 deg F)
Unoccupied Heating
Setpoint
unocc_ht_stpt
R/W
50 deg F - 80 deg F
(65 deg F)
Effective Cool Setpoint
effective_cl_stpt
R
deg F
Effective Heat Setpoint
effective_ht_stpt
R
deg F
Optimal Start
optm_star
R/W
1 hour – 4 hours
(4 hours)