background image

5. The CO

2

and stack temperature instruments enable you to

obtain data required to determine thermal efficiency of fur-
nace.

6. An oil filter should be installed as close to burner as possible

with ALL oil burners and is essential on lower firing rate
burners. We recommend the use of a low pressure drop oil
filter such as the General Filter, Inc. model #1A-25A or
equivalent.

7. The oil pressure regulator is factory set to give nozzle oil

pressures of 100 psig. The firing rates noted on nameplate may
be obtained using nozzles listed in Table 5.

8. On a new installation, air entrapped in oil line leading from

tank to nozzle must be thoroughly purged in order to prevent
excessive after drip. The oil pump is provided with a special
fitting which allows purging of any air between tank and oil
pump. The proper procedure for performing this operation is
as follows:

a. Place a piece of clear plastic 1/4 in. diameter tubing over

purge fitting on oil pump.

b. Start oil burner, then open purge fitting and allow burner to

run until purge tube is completely free of air bubbles.

c. Tighten purge fitting. Allow oil to run to nozzle and fire

burner.

d. If purging takes longer than 15 sec and no flame has been

established, burner stops. Push reset button on top of
primary control to restart burner.

e. For detailed information on operation of primary control,

refer to instructions included with furnace.

After all the setup procedures mentioned above have been com-
pleted, the burner should be allowed to operate and an inspection
mirror should be used to observe the flame pattern at tip of nozzle.
Any irregularities such as burning to 1 side or pulsating flame
patterns should be corrected by changing nozzle.

Step 3—Fan Adjustment Check

This furnace is equipped with a 4-speed direct-drive motor to
deliver a temperature rise within range specified on rating plate,
between return and supply plenums, at external duct static pressure
noted on rating plate.

When operating furnace in heating mode, static pressure and
temperature rise (supply-air temperature minus return-air
temperature) must be within those limits specified on rating
plate. Failure to follow this warning could lead to severe
furnace damage.

Adjust fan speed ACCORDING TO OIL INPUT SELECTED so
that temperature rise is within rise range specified on rating plate.
(See Table 6.) Consult wiring diagram for speed changes on
direct-drive motor.

To adjust fan off time, set DIP switches on control board to obtain
desired timing. (See Fig. 5.)

Step 4—Limit Control Check

After furnace has been in operation for at least 15 minutes, restrict
return-air supply by blocking filters or closing return registers and
allow furnace to shut down on high limit. The burner should shut
off, and main blower should continue to run.

Remove restriction, and burner should come back on in a few
minutes.

Step 5—For Year-Round Air Conditioning

This furnace is designed for use in conjunction with cooling
equipment to provide year-round air conditioning. The blower has
been sized for both heating and cooling, however, fan motor speed
may need to be changed to obtain necessary cooling airflow.

Step 6—Heating

The blower speed is factory set to deliver required airflow at
normal duct static pressure.

Step 7—Cooling

The blower speed may be field adjusted to deliver required airflow
for cooling application. (See Table 7.)

Step 8—Constant Blower Switch

This furnace is equipped with a constant low-speed blower option.
Whenever room thermostat is not calling for heating or cooling,
blower runs on low speed in order to provide air circulation. If
constant blower option is not desired, the rocker switch on side of
control box may be used to turn off constant speed.

Table 5—Burner Input and Nozzle Size

(At 100 psig Pump Pressure)

FURNACE

INPUT

(BTUH)

FIRING

RATE

GAL/HR (US)

BECKETT OIL BURNER

Model

Nozzle

70,000

0.50

AFG-F3

0.50 gph

70-W

91,000

0.65

AFG-F3

0.65 gph

70-W

105,000

0.75

AFG-F3

0.75 gph

70-B

119,000

0.85

AFG-F3

0.85 gph

70-B

140,000

1.00

AFG-F3

1.00 gph

70-W

154,000

1.10

AFG-F6*

1.10 gph

70-W

* Requires field supplied and replacement burner firing head.

Table 6—Speed Selection

UNIT

SIZE

FURNACE

INPUT

(BTUH)

RECOMMENDED

BLOWER

SPEED

105-12/

120-20

70,000/119,000

Med-Low

91,000/140,000

Med-High

105,000/154,000

High

Fig. 5—Fan Off Time DIP Switch Settings

(Black Box Represents Switch Position)

A95115

1

2

60 Sec

1

2

90 Sec

DELAY  OFF  DIP  SWITCH  SETTINGS

1

2

1

2

1

2

120 Sec

1

2

150 Sec

10

Содержание OIL FURNACE 58CMA

Страница 1: ...ck 10 For Year Round Air Conditioning 10 Heating 10 Cooling 10 Constant Blower Switch 10 MAINTENANCE 11 12 General 11 Oil Burner 11 Heat Exchanger and Flue Pipe 11 Blower Removal 12 SAFETY CONSIDERATI...

Страница 2: ...nd are available from either The National Fire Protection Agency Batterymarch Park Quincy MA 02269 or The Canadian Stan dards Association 178 Rexdale Blvd Rexdale Ontario M9W 1R3 Recognize safety info...

Страница 3: ...oved subbase is used Also since flue pipe is in a down flow position Downflow Conversion Vent Guard Kit MUST be used Also read page 9 When installed in a horizontal position furnace may be suspended b...

Страница 4: ...e into consideration the overall volume of unconfined space the number of windows and ventilation openings the number of doors to the outside internal doors which can close off unconfined space and ov...

Страница 5: ...uctwork should be attached to either side bottom or side and bottom of furnace See Fig 2 for dimensions of these openings NOTE The back should not be cut out for return air The following recommendatio...

Страница 6: ...ange is fixed to burner air tube and no adjustment is required for insertion length OIL CONNECTIONS Complete instructions for installing fuel oil piping can be found in oil burner Installation Instruc...

Страница 7: ...H U M 4 5 6 N 7 2 S E A C C O N T C O O L H E A T CAPACITOR WHITE RED BLUE BLACK R99G001 ST9103 CONSTANT LOW SPEED SWITCH CIRCULATING FAN BLACK WHITE UNUSED LO ML MH HI C LEADS 1 2 3 3 H U M 4 5 6 N...

Страница 8: ...4 5 6 N 7 2 S E A C C O N T C O O L H E A T CAPACITOR WHITE RED BLUE BLACK R99G001 ST9103 CONSTANT LOW SPEED SWITCH CIRCULATING FAN BLACK WHITE UNUSED LO ML MH HI C LEADS 1 2 3 3 H U M 4 5 6 N 7 2 S E...

Страница 9: ...d set above room temperature If all of the above items have been performed set main electrical switch to ON position and burner should start When burner starts proceed to Combustion Check section Step...

Страница 10: ...ed on rating plate Failure to follow this warning could lead to severe furnace damage Adjust fan speed ACCORDING TO OIL INPUT SELECTED so that temperature rise is within rise range specified on rating...

Страница 11: ...FOR AN EXTENDED PERIOD OF TIME Step 2 Oil Burner For optimum performance oil burner nozzle should be replaced once a year Contact your service technician if you are unsure of this procedure The proce...

Страница 12: ...luding Unit Familiarization Maintenance Installation Overview Operating Sequence A large selection of product theory and skills programs is available using popular video based formats and materials Al...

Отзывы: