Table 16 — Alarm and Alert Codes
DISPLAY
ALARM
DESCRIPTION
ACTION TAKEN
CIRCUIT
RESET
PROBABLE CAUSE
OR
ALERT
BY CONTROL
PUMPDOWN METHOD
0
—
No Alarms or Alerts Exist
—
—
—
—
1
Alert
Compressor A1 failure
Circuit A shut down
No
Manual
High-pressure switch trip, or wiring
error.
2, 3, 4
Compressor A2, A3, A4 failure
Compressor shut down
Yes
Manual
CPCS Ground Fault Protection
5
Compressor B1 failure
Circuit B shut down
No
Manual
6, 7, 8
Compressor B2, B3, B4 failure
Compressor shut down
Yes
Manual
9
Alarm
Leaving fluid thermistor failure
Unit shut down
Yes
Auto.
Thermistor or transducer failure
or wiring error.
10
Entering fluid thermistor failure
Unit shut down
Yes
Auto.
19
Alert
Compressor A1 sensor failure
Circuit A shut down
Yes
Auto.
20
Compressor B1 sensor failure
Circuit B shut down
Yes
Auto.
21
Reset thermistor failure
Normal set point used
No
Auto.
22
Alert
Discharge pressure transducer failure, circuit A Circuit A shut down
Yes
Auto.
Transducer failure or wiring error.
23
Discharge pressure transducer failure, circuit B Circuit B shut down
Yes
Auto.
24
Suction pressure transducer failure, circuit A
Circuit A shut down
No
Auto.
25
Suction pressure transducer failure, circuit B
Circuit B shut down
No
Auto.
26
Oil pressure transducer failure, circuit A
Circuit A shut down
No
Auto.
27
Oil pressure transducer failure, circuit B
Circuit B shut down
No
Auto.
28
Alarm
Transducer supply voltage low
Unit shut down
No
Auto.
Unit voltage low or PS1 faulty.
29
LOCAL/ENABLE-STOP-CCN
Unit shut down
No
Manual
Switch failure or wiring error.
30
Alert
4-20 mA reset input failure
Normal set point used
No
Auto.
31
4-20 mA demand limit failure
Demand limit ignored
No
Auto.
32
Alarm
Loss of communication with DSIO-LV
Unit shut down
No
Auto.
Wiring error or faulty module
or improper address code.
33
Loss of communication with DSIO-EXV
Unit shut down
No
Auto.
34
Loss of communication with 4 In/4 Out module
Unit shut down
Yes
Auto.
35
—
Not used
—
—
—
—
36
Alert
Low refrigerant pressure circuit A
Circuit A shut down
No
*
Low refrigerant charge, plugged filter
drier, faulty expansion valve.
37
Low refrigerant pressure circuit B
Circuit B shut down
No
*
Low refrigerant charge, plugged filter
drier, faulty expansion valve.
38
Alert
Failure to pump out circuit A
Circuit A shut down
No
Manual
Faulty expansion valve, transducer,
or thermistor.
39
Failure to pump out circuit B
Circuit B shut down
No
Manual
Faulty expansion valve, transducer,
or thermistor.
40
Alert
Low oil pressure circuit A
Circuit A shut down
No
Manual
Low oil level, circuit breaker trip,
faulty expansion valve, crankcase
heater, or pressure transducer.
41
Low oil pressure circuit B
Circuit B shut down
No
Manual
Low oil level, circuit breaker trip,
faulty expansion valve, crankcase
heater, or pressure transducer.
42
Alarm
Cooler freeze protection
Unit shut down
No
*
Low fluid flow or faulty thermistor.
43
Low cooler fluid flow
Unit shut down
No
Manual
Chilled fluid pump failure
or faulty thermistor.
44
Alert
Low suction temperature circuit A
Circuit A shut down
after 10 minutes
No
Manual
Faulty expansion valve or thermistor.
45
Low suction temperature circuit B
Circuit B shut down
after 10 minutes
No
Manual
Faulty expansion valve or thermistor.
46
Alert
High suction superheat circuit A
Circuit A shut down
Yes
Manual
Low charge, faulty expansion valve or
thermistor, or plugged filter drier.
47
High suction superheat circuit B
Circuit B shut down
Yes
Manual
Low charge, faulty expansion valve or
thermistor, or plugged filter drier.
48
Alert
Low suction superheat circuit A
Circuit A shut down
Yes
Manual
Faulty EXV or thermistor.
49
Low suction superheat circuit B
Circuit B shut down
Yes
Manual
Faulty EXV or thermistor.
50
Alarm
Illegal configuration
Unit cannot start
—
Manual
Configuration error.
51
Initial configuration required
Unit cannot start
—
Manual
Configuration omitted.
52
Emergency stop by CCN command
Unit shut down
Yes
CCN
Network command.
53
Alarm
Cooler pump interlock failure
Unit shut down
No
Manual
Failure of cooler pump or controls
54
Cooler pump interlock failure
Unit shut down
No
Manual
Failure of cooler pump or controls
55
Cooler pump interlock failure
Cooler pump shut down
—
Manual
Failure of cooler pump relay or interlock
56
Alert
WSM communication failure
WSM forces removed
—
Auto.
Wiring fault or module failure
57
Alert
Calibration required for discharge pressure
transducer, circuit A
Circuit cannot start
—
Auto.
Transducer not calibrated
58
Calibration required for discharge pressure
transducer, circuit B
Circuit cannot start
—
Auto.
59
Calibration required for suction pressure
transducer, circuit A
Circuit cannot start
—
Auto.
60
Calibration required for suction pressure
transducer, circuit B
Circuit cannot start
—
Auto.
61
Calibration required for oil pressure
transducer, circuit A
Circuit cannot start
—
Auto.
62
Calibration required for oil pressure
transducer, circuit B
Circuit cannot start
—
Auto.
49