Table 9 — Keypad Directory (cont)
SET POINT
To read a set point, go to proper subfunction and read desired set point. To change a set point, enter new set point value, then press
.
LOCAL/ENABLE-STOP-CCN switch must be in LOCAL/ENABLE or STOP position.
SUBFUNCTION
KEYPAD ENTRY
DISPLAY
COMMENT
1 SET POINTS
SET POINT
Unit Set Point
CSP1 X
Chiller Fluid Set Point 1 (F)
CSP2 X
Chiller Fluid Set Point 2 (F)
HSPA X
Head Pressure Set Point Circuit A (F)
HSPB X
Head Pressure Set Point Circuit B (F)
CRAMP X
Cooling Ramp Loading Rate (F)
2 RESET SET POINTS
RESET
Reset Set Points
CRT1 X
Cooling reset at 20 mA (F)
CRT2N X
Reference Temperature at No Reset (F)
CRT2F X
Reference Temperature at Full Reset (F)
CRT2D X
Total Degrees of Reset (F)
CRT3N X
Chiller Fluid
D
T at No Reset (F)
CRT3F X
Chiller Fluid
D
T at Full Reset (F)
CRT3D X
Total Degrees of Reset (F)
3 DEMAND SET POINTS
DEMAND
Demand Set Points
DLS1 X†
Demand Switch 1 Set Point (percent)
DLS2 X†
Demand Switch 2 Set Point (percent)
DL20 X
Demand Limit at 20 mA (percent)
DLGN X
Loadshed Group Number
LSDD X
Loadshed Demand (percent)
TIME X
Minimum Loadshed Time (minutes)
4 DATE AND TIME
DATE.TIME
Date, Time and Day of Week
DOW.HR.MIN
Day 1 = Mon, 2 = Tues. . .7 = Sun
Hours are displayed in 24-hr time. Decimal point serves as colon.
MM.DD.YR
Month.Day.Year. When entering date, enter a decimal
point between entries. Each entry must be two numbers.
5 LEAVING CHILLER
FLUID ALERT LIMIT
LMT X
Leaving Chiller Fluid Alert Limit (F)
LEGEND
CCN — Carrier Comfort Network
EXV
— Electronic Expansion Valve
MOP — Maximum Operating Pressure
*Will read ALARM or ALERT as appropriate.
†Must be configured.
**If applicable.
††Not manually resettable.
NOTE: If metric option is selected under
, temperature
expressed as Celsius and pressure will be expressed as kPa.
35