Table 9 — Keypad Directory (cont)
STATUS (cont)
SUBFUNCTION
KEYPAD ENTRY
DISPLAY
COMMENT
4 STAGE
STAGE
Capacity Staging Information
COOL X
Number of Requested Stages
CAPT X
Percent of Total Capacity
CAPA X
Percent Circuit A Total Capacity
CAPB X
Percent Circuit B Total Capacity
AVAIL X
Percent Available Capacity
AV A X
Percent Circuit A Available Capacity
AV B X
Percent Circuit B Available Capacity
LMT X†
Demand Limit Set Point (percent)
CIRA X
Circuit A Compressor Relay Status
CIRB X
Circuit B Compressor Relay Status
SMZ X
Load/Unload Factor for Compressors
Factor = 1
Unloader Factor = 0.6
5 SET POINT
SETPOINT
Fluid Set Point Information
SET X
Set Point (F)
MSP X
Modified Set Point = Set Point + Reset (F)
TW X
Actual Control Temperature (F)
6 TEMPERATURE
TEMPS
Temperature Information (F)
EWT X
Cooler Entering Fluid Temperature (F)
LWT X
Cooler Leaving Fluid Temperature (F)
SCTA X
Circuit A Saturated Condenser Temperature (F)
SSTA X
Circuit A Saturated Suction Temperature (F)
CTA X
Compressor A1 Suction Temperature (F)
SHA X
Circuit A Suction Superheat (F)
SCTB X
Circuit B Saturated Condenser Temperature (F)
SSTB X
Circuit B Saturated Suction Temperature (F)
CTB X
Compressor B1 Suction Temperature (F)
SHB X
Circuit B Suction Superheat (F)
SPC X
Space Temperature (F)
OAT X
Outdoor-Air Temperature (F)
LEGEND
CCN — Carrier Comfort Network
EXV
— Electronic Expansion Valve
MOP — Maximum Operating Pressure
*Will read ALARM or ALERT as appropriate.
†Must be configured.
**If applicable.
††Not manually resettable.
NOTE: If metric option is selected under
, temperature
expressed as Celsius and pressure will be expressed as kPa.
28