Table 13 — Factory Configuration Keystrokes
To change a configuration enter the new configuration
and press
while on the correct configuration.
SUB-
KEYPAD
DISPLAY
COMMENTS
FUNCTION
ENTRY
3 FACTORY
CFG
FACT CFG
FACTORY
CONFIGURATION
CODES
XXXXXXXX
Configuration
Code 1
XXXXXXXX
Configuration
Code 2
XXXXXXXX
Configuration
Code 3
XXXXXXXX
Configuration
Code 4
XXXXXXXX
Configuration
Code 5
XXXXXXXX
Configuration
Code 6
XXXXXXXX
Configuration
Code 7
5 SERVICE
CFG
SRV CFG
SERVICE
CONFIGURATION
CODES
XXXXXXXX
Configuration
Code 8
XXXXXXXX
Configuration
Code 9
REFRIG X
Refrigerant Type
TDTYPE X
Pressure Transducer Select
OPS X
Oil Pressure Set Point
LPS X
Low Pressure Set Point
FANTYP X
Fan Staging Select
SH X
EXV Superheat Set Point
MOP X
EXV MOP Superheat
ZM X
Z Multiplier
LEGEND
MOP — Maximum Operating Pressure
EXV
— Electronic Expansion Valve
When unit is configured for dual set point, chilled liquid
pump relay is energized continuously, in both occupied and
unoccupied modes. Occupied mode places occupied chilled
water set point into effect; unoccupied mode places unoc-
cupied chilled water set point into effect.
Scheduling —
is used to override any current sched-
ule in effect (for 0-4 hours).
is used to activate a
clock for the scheduling function.
-
are used
to program schedules for specific occupied and unoccupied
periods.
The schedule consists of from one to 8 occupied time pe-
riods, set by the operator. These time periods can be flagged
to be in effect or not in effect on each day of the week. The
day begins at 00.00 and ends at 24.00. The machine is in
unoccupied mode unless a scheduled time period is in effect.
If an occupied period is to extend past midnight, it must be
programmed in the following manner: occupied period must
end at 24:00 hours (midnight); a new occupied period must
be programmed to begin at 00:00 hours.
Table 14 — Adjustable Field Configurations
FIELD CONFIGURATION
ITEM AND CODES
FACTORY
SERVICE
CONFIGURATION
REPLACEMENT
CODE
CODE
CCN element address
(Entered by CCN Technician)
001
001
CCN Bus Number
(Entered by CCN Technician)
000
000
CCN Baud Rate
(Entered by CCN Technician)
9600
9600
Cooler Fluid Select
1 = Water (38 to 70 F
[3.3 to 21 C] Set Point)
2 = Medium Brine (15 to 70 F
[–9 to 21 C] Set Point)
1 = Standard Models
2 = Brine Models
1
Display Unit Select
0 = English
1 = Metric SI
0
0
Delay at Power Up
0
0
No. Circuit A Unloaders
0 = No Unloaders
1 = One Unloader
2 = Two Unloaders
0 = 30GN190-210*
1 = 30GN040-170*
0
No. Circuit B Unloaders
0 = No Unloaders
1 = One Unloader
2 = Two Unloaders
0 = 30GN040-070,
190-210*
1 = 30GN080-170*
0
Hot Gas Bypass Select
0 = No Valve
0
0
Loading Sequence Select
1 = Equal Circuit Loading
2 = Staged Circuit Loading
1
1
Lead/Lag Sequence Select
1 = Automatic
2 = Manual, Circuit A Leads
3 = Manual, Circuit B Leads
1
1
Oil Pressure Switch Select
0 = Not Used
1 = Air Cooled
0
0
Head Pressure Control Type
0 = Not Used
1 = Air Cooled
1
0
Head Pressure Control Method
1 = EXV Controlled
2 = Set Point Control for
Both Circuits
3 = Set Point Control for
Circuit A; EXV Control
for Circuit B
4 = Set Point Control for
Circuit B; EXV Control
for Circuit A
1
2 = 040,045
Brine Units
1
Motormaster
T
Select
0 = None
2 = Indirect Control
0
0
Cooling Set Point
Control Select
0 = Single Set Point Control
1 = External Switch
Controlled Set Point
2 = Clock Controlled
Set Point
0
0
Cooling Reset Control Select
0 = No Reset
1 = 4-20 mA, Internally Powered
2 = External Temperature
Reset
3 = Return Fluid Reset
4 = 4-20 mA, Externally Powered
0
0
External Reset Sensor Select
0 = Thermistor Connected to
Options Module
1 = Obtained Through CCN
0
0
Outdoor-Air Sensor Select
0 = Not Selected
1 = Selected
0
0
Demand Limit Control Select
0 = No Demand Limiting
1 = Two External Switch Inputs
2 = Internal 4-20 mA Input
3 = CCN Loadshed
4 = External 4-20 mA Input
0
0
Ramp Load Select
(Pulldown Control)
0 = Disabled
1 = Enabled
1
0
Cooler Pump Interlock Select
0 = No Interlock
1 = With Interlock
1
0
Cooler Pump Control Select
0 = Not Controlled
1 = ON/OFF Controlled
1
0
Remote Alarm Option Select
0 = Not Selected
1 = Selected
0
0
Local/Enable-Stop-CCN
Switch Usage†
0 = Not Allowed
1 = Allowed
1
1
LEGEND
CCN — Carrier Comfort Network
EXV
— Electronic Expansion Valve
*And associated modular units.
†For reset of alarms.
45