12
Aquazone
Thermostat
M
ORG
(230V)
AL
—
Alarm Relay Contacts
BR
—
Blower Relay
CB
—
Circuit Breaker
CC
—
Compressor Contactor
CO
—
Sensor, Condensate Overflow
FP1
—
Sensor, Water Coil Freeze Protection
FP2
—
Sensor, Air Coil Freeze Protection
HP
—
High-Pressure Switch
JW1 —
Jumper, Alarm
LOC —
Loss-of-Charge Pressure Switch
NOTES:
1. Compressor and blower motor thermally protected internally.
2. All wiring to the unit must comply with NEC and local codes.
3. Transformer is wired to 265 v (BRN) lead for 265/1/60 units, or
208 v (RED) lead for 208/1/60. For 230/1/60 switch RED and
ORG leads at L1 and insulate RED lead. Transformer is energy
limiting or may have circuit breaker.
4. FP1 thermistor provides freeze protection for water. When
using antifreeze solutions, cut JW3 jumper.
5. Typical Aquazone thermostat wiring shown. Refer to thermostat
installation instructions for wiring to the unit. Thermostat wiring
must be Class 1 and voltage rating equal to or greater than unit
supply voltage.
LEGEND
NEC
—
National Electrical Code
P1
—
Field Wiring Terminal Block
PM
—
Performance Monitor
RVS
—
Reversing Valve Solenoid
TFRMR —
Transformer
Field Line Voltage Wiring
Printed Circuit Trace
Relay/Contactor Coil
Solenoid Coil
Thermistor
Ground
Wire Nut
Pressure Switch
6. 24-v alarm signal shown. For dry alarm contact, cut JW1
jumper and dry contact will be available between AL1 and AL2.
7. Transformer secondary ground via control board standoffs and
screws to control box. (Ground available from top two standoffs
as shown.)
8. Transformer wired to 460 v (BLK/RED) lead for 460/3/60 units
and 575 v (GRY) lead for 575/3/60. Transformer is energy limit-
ing or may have circuit breaker.
9. 208/230 v transformers will be wired for 208 v operation. For
230 v operation, disconnect RED lead at L1 and attach ORG
lead to L1. Close open end of RED lead with insulating tape.
Fig. 6A — Typical Aquazone™ Complete C Control Wiring (50RWS036, 060 Units)