Table 3 — 50RWS Electrical Data
LEGEND
*Time-delay fuse or HACR circuit breaker.
†Units come standard with 75 va transformer and connections for
loop panel and HWG. HWG pump FLA is 0.4. External loop pump
FLA is 4.0.
UNIT
50RWS
VOLTAGE
(V-Ph-Hz)
VOLTAGE RANGE
MIN/MAX
COMPRESSOR
TOTAL
FLA
MCA
MOCP*
RLA
LRA
QTY
036
208/230-1-60
187/254
15.0
73.0
1
15.0
18.8
30
265-1-60
239/292
14.3
71.0
1
14.3
17.9
30
208/230-3-60
187/254
10.7
63.0
1
10.7
13.4
20
460-3-60
414/506
5.0
31.0
1
5.0
6.3
15
036 w/HWG†
208/230-1-60
187/254
15.0
73.0
1
19.4
23.2
35
060
208/230-1-60
187/254
28.0
169.0
1
28.0
35.0
60
208/230-3-60
187/254
19.3
123.0
1
19.3
24.1
40
460-3-60
414/506
7.5
49.5
1
7.5
9.4
15
575-3-60
518/633
6.4
40.0
1
6.4
8.0
15
060 w/HWG†
208/230-1-60
187/254
28.0
169.0
1
32.4
39.4
60
120
208/230-1-60
187/254
28.0
169.0
2
56.0
63.0
90
208/230-3-60
187/254
19.3
123.0
2
38.6
43.4
60
460-3-60
414/506
7.5
49.5
2
15.0
16.9
20
575-3-60
518/633
6.4
40.0
2
12.8
14.4
20
360
208/230-3-60
187/254
41.0
350.0
2
82.0
92.3
125
460-3-60
414/506
21.8
158.0
2
43.6
49.0
70
575-3-60
518/633
17.3
125.0
2
34.6
38.9
50
FLA
—
Full Load Amps
HACR —
Heating, Air Conditioning, and Refrigeration
HWG
—
Hot Water Generator
LRA
—
Locked Rotor Amps
MCA
—
Minimum Circuit Amps
MOCP —
Minimum Overcurrent Protection
RLA
—
Rated Load Amps