background image

8

3.4 - Mounting the unit

Horizontal units should be mounted using the factory-installed
hangers. Proper attachment of hanging rods to building structure
is critical for safety (see Figs. 2 and 5). Rod attachments must
be able to support the weight of the unit. See Table 1 for unit
operating weights.

3.5 - Duct system

Size the duct system to handle the design airflow quietly.

NOTE: Depending on the unit, the fan wheel may have a
shipping support installed at the factory. This must be removed
before operating unit.

3.5.1 - Sound attenuation
To eliminate the transfer of vibration to the duct system, a flexible
connector is recommended for both discharge and return air
duct connections on metal duct systems. The supply and return
plenums should include internal duct liner of fibreglass or be
made of duct board construction to maximise sound attenuation
of the blower. Installing the water-source heat pump unit to un-
insulated ductwork in an unconditioned space is not recommended
since it will sweat and adversely affect the unit performance.

To reduce air noise, at least one 90

°

 elbow could be included in

the supply and return air ducts, provided system performance is
not adversely impacted. The blower speed can also be changed
in the field to reduce air noise or excessive airflow, provided
system performance is not adversely impacted.

3.5.2 - Existing duct system
If the unit is connected to existing ductwork, consider the
following:

Verify that the existing ducts have the proper capacity to
handle the unit airflow. If the ductwork is too small, install
larger ductwork.

Check existing ductwork for leaks and repair as necessary.

NOTE: Local codes may require ventilation air to enter the
space for proper indoor air quality. Hard-duct ventilation may
be required for the ventilating air supply. If hard ducted ven-
tilation is not required, be sure that a proper air path is provi-
ded for ventilation air to unit to meet ventilation requirement
of the space.

Fig. 5 - Horizontal hanger bracket (factory-installed)

50RHE

Dimensions, mm
A

B

C

D

E

006-024

568

1095

619

1095

516

030, 036

568

1349

619

1349

518

042, 048

568

1577

619

1577

518

060

645

1806

695

1806

594

3.6 - Condensate drain

Slope the unit toward the drain at a 6.5 mm per 300 mm pitch
(see Fig. 6). If it is not possible to meet the required pitch, install a
condensate pump at the unit to pump condensate to building
drain.

Horizontal units are not internally trapped; therefore an external
trap is necessary. Install each unit with its own individual trap
and means to flush or blowout the condensate drain line. Do not
install units with a common trap or vent. For typical condensate
connections see Fig. 7.

NOTE: Never use a pipe size smaller than the connection.

3.6.1 - Venting
Install a vent in the condensate line of any application that may
allow dirt or air to collect in the line. Consider the following:

Always install a vent where an application requires a long
horizontal run.

Always install a vent where large units are working against
higher external static pressure and to allow proper drainage
for multiple units connected to the same condensate main.

Be sure to support the line where anticipated sagging from
the condensate or when “double trapping” may occur.

If condensate pump is present on unit, be sure drain
connections have a check valve to prevent back flow of
condensate into other units.

Fig. 6 - Horizontal unit pitch

Fig. 7 - Trap condensate drain

Note: Trap should be deep enough to offset maximum unit static difference.
A 102 mm trap is recommended.

B

A

C

E

D

D

Air handler
section

Compressor
section

Pitch toward
drain

Drain connection

Minimum pitch
25 mm per 3 m
of line

Open vent

To unit

See note

Drain plug

65 mm pitch
for drainage

Содержание Aquazone 50RHE 006

Страница 1: ...ting in the Eurovent Certification Programme Products are as listed in the Eurovent Directory of Certified Products 50RHE 006 060 Water Source Heat Pumps Horizontal Units Installation OperationandMaintenanceInstructions TM ...

Страница 2: ...or rotation 21 6 3 Unit start up cooling mode 21 6 4 Unit start up heating mode 21 6 5 Flow regulation 21 6 6 Flushing 22 6 7 Anti freeze 23 6 8 Cooling tower boiler systems 23 6 9 Ground coupled closed loop and plateframe heat exchanger well systems 23 7 OPERATION 24 7 1 Power up mode 24 7 2 Units with Aquazone Complete C control 24 7 3 Units with Aquazone Deluxe D control 24 8 SYSTEM TEST 25 8 1...

Страница 3: ...ith each unit Before unit start up read all manuals and become familiar with the unit and its operation Thoroughly check out the system before operation Complete the inspections and instructions listed below to prepare a unit for installation See Table 1 for unit physical data Horizontal units are designed for indoor installation only Be sure to allow adequate space around the unit for servicing S...

Страница 4: ...tion isolators must have bolts loosened and shipping clamps removed 7 Remove any blower support cardboard from inlet of the blower 8 Locate and verify any accessory kit located in compressor section 9 Remove any access panel screws that may be difficult to remove once unit is installed Table 1 Physical data 50RHE 006 009 012 015 019 024 030 036 042 048 060 Cooling capacity kW 1 5 2 1 2 5 3 9 4 9 5...

Страница 5: ...t orientation is determined by looking at water connection side front N P M O 3 F K L 2 1 E A C V U B T S F N P M O 27 9 C V T S U B X Y Z A C R P Q O 82 6 O A C P Q R D 82 6 J 5 Left return 610 mm service access Front CSP Optional 610 mm service access Left return ASP Right discharge Back discharge Condensate 3 4 FPT Power supply 3 4 knockout 1 2 knockout Low voltage 1 2 knockout CAP Front view 8...

Страница 6: ...al for supply and return piping Water out Water in Low pressure drop water control valve optional field installedaccessory Balancing valve field installedand calibratedaccessory Water in Water out Supply loop Return loop Return air ductwork not shown 3 8 threaded rods by others Filter access Unit hanger isolation detail 3 8 threaded rod by others Vibration isolator white compressor end and red blo...

Страница 7: ...turn models in the field due to refrigerant piping changes Preparation The unit should be on the ground in a well lit area for conversion Hung units should be taken down to ground level before con verting Side to back discharge conversion 1 Remove screws to free the top and discharge panels see Fig 3 2 Remove the access panel and set aside 3 Lift the discharge panel from side of unit and rotate it...

Страница 8: ...y be required for the ventilating air supply If hard ducted ven tilation is not required be sure that a proper air path is provi ded for ventilation air to unit to meet ventilation requirement of the space Fig 5 Horizontal hanger bracket factory installed 50RHE Dimensions mm A B C D E 006 024 568 1095 619 1095 516 030 036 568 1349 619 1349 518 042 048 568 1577 619 1577 518 060 645 1806 695 1806 59...

Страница 9: ...flow verification In addition to complying with any applicable codes consider the following for system piping Piping systems using water temperatures below 10 C require 13 mm closed cell insulation on all piping surfaces to eliminate condensation Avoid all plastic to metal threaded fittings due to the potential to leak Use a flange fitted substitute Teflon tape thread sealant is recommended to min...

Страница 10: ... 12 for a schematic of the field connections which must be made by the installing or electrical contractor Refer to electrical data for fuse sizes Consult the unit wiring diagram located on the inside of the compressor access panel to ensure proper electrical hookup The installing or electrical contractor must make the field connections when using field supplied disconnect Operating voltage must b...

Страница 11: ...4 V alarm signal shown For dry alarm contact cut JW1 jumper and dry contact will be available between AL1 and AL2 7 Transformer secondary ground via microprocessor board stand offs and screws to control box Ground available from top two stand offs as shown 8 Fan motors factory wired for medium speed For high or low speed remove BLU wire from fan motor speed tap M and connect to H for high or L for...

Страница 12: ...to thermostat installation instructions for wiring to the unit 6 24 V alarm signal shown For dry alarm contact cut JW1 jumper and dry contact will be available between AL1 and AL2 7 Transformer secondary ground via microprocessor board stand offs and screws to control box Ground available from top two stand offs as shown 8 Fan motors factory wired for medium speed For high or low speed remove BLU ...

Страница 13: ...unit must comply with local codes 3 Transformer is wired to 240 V ORG lead for 240 1 50 units switch RED and ORG leads to PB 1 and insulate ORG lead for 220 1 50 4 FP1 thermistor provides freeze protection for water When using anti freeze solutions cut JW3 jumper 5 Check installation wiring information for specific thermostat hook up Refer to thermostat installation instructions for wiring to the ...

Страница 14: ...ia microprocessor board stand offs and screws to control box Ground available from top two stand offs as shown 8 Blower motor is factory wired for medium and high speeds For any other combination of speeds at the motor attach black wire to the higher of the two desired speed taps and the blue wire to the lower of the two desired speed taps 9 Blower motor is factory wired for high and low speeds No...

Страница 15: ...nit must be within voltage range indicated on unit nameplate On 3 phase units voltages under load between phases must be balanced within 2 Use the following formula to determine the percentage voltage imbalance voltage imbalance 100 x Example Supply voltage is 460 3 60 AB 452 Volts BC 464 Volts AC 455 Volts Average voltage 457 Determine maximum deviation from average voltage AB 457 452 5 V BC 464 ...

Страница 16: ... 118 104 015 212 160 High 345 316 288 250 198 Medium 321 302 274 241 189 Low 293 278 255 222 179 019 264 198 High 326 311 283 250 203 Medium 302 288 260 227 189 Low 293 269 245 217 179 024 307 231 High 396 368 335 302 260 Medium 387 359 326 297 255 Low 368 340 311 278 231 030 349 264 High 529 496 463 425 378 330 Medium 510 477 448 415 368 326 Low 458 439 406 378 340 297 036 437 326 High 614 576 57...

Страница 17: ...n Fig 17 Aslow closing valve may be required to prevent water hammer When using a slow closing valve consider special wiring conditions The valve takes approximately 60 seconds to open very little water will flow before 45 seconds and it activates the compressor only after the valve is completely opened by closing its end switch When wired as shown the valve will have the following operating chara...

Страница 18: ...emp to choose FP1 limit of 12 2 C or 1 1 C To select 1 1 C as the limit DO NOT clip the jumper To select 12 2 C as the limit clip the jumper Air coil freeze protection FP2 limit setting Select jumper 2 JW2 FP2 low temp to choose FP2 limit of 12 2 C or 1 1 C To select 1 1 C as the limit DO NOT clip the jumper To select 12 2 C as the limit clip the jumper Alarm relay setting Select jumper 1 JW1 AL2 ...

Страница 19: ...cooling stage 2 Select ON for normal mode The fan speed relay will turn on during cooling stage 2 in normal mode Switch 6 Not used Boilerless operation Switch 7 provides selection of boilerless operation and works in conjunction with switch 8 In boilerless operation mode only the compressor is used for heating when FP1 is above the boilerless changeover temperature set by switch 8 below Select ON ...

Страница 20: ...ir will adversely affect the unit performance reliability and service life Power supply A voltage variation of 10 of nameplate utilisation voltage is acceptable Unit starting conditions Depending on the model units start and operate in an ambient temperature of 7 2 C with entering air temperature at 4 4 C or 10 C entering water temperature at 6 7 C or 10 C and with both air and water at the flow r...

Страница 21: ... 8 Water temperature change through heat exchanger Water flow rate l s Cooling rise K Heating drop K Min Max Min Max For closed loop ground source or cooling boiler systems at 0 054 l s per kW 5 6 7 2 2 4 4 For open loop ground water systems 0 027 l s per kW 11 1 14 4 5 6 9 4 6 4 Unit start up heating mode NOTE Operate the unit in heating cycle after checking the cooling cycle Allow five minutes b...

Страница 22: ...12 3 11 7 0 568 26 9 25 4 23 6 22 4 0 757 44 0 41 0 38 3 36 5 060 0 473 33 5 31 4 29 3 27 8 0 713 58 3 54 4 50 8 48 4 0 947 88 5 82 8 77 1 73 3 6 6 Flushing Once the piping is complete units require final purging and loop charging A flush cart pump of at least 1 12 kW is needed to achieve adequate flow velocity in the loop to purge air and dirt particles from the loop Flush the loop in both direct...

Страница 23: ...lume l per 30 m of pipe Pipe Diameter in Volume l Copper 1 15 5 1 25 24 2 1 5 34 8 Rubber hose 1 14 7 Polyethylene 3 4 IPS SDR11 10 6 1 IPS SDR11 17 0 1 1 4 IPS SDR11 30 0 1 2 IPS SDR11 41 2 2 IPS SDR11 68 1 1 1 4 IPS SCH40 31 4 1 1 2 IPS SCH40 41 2 2 IPS SCH40 64 3 Legend IPS Internal pipe size SCH Schedule SDR Standard dimensional ratio Note Volume of heat exchanger is approximately 3 78 litres ...

Страница 24: ... fan enable and compressor relays are remain on The fan speed relay is turned on immediately and turned off immediately once the demand is removed The control reverts to heating stage 1 mode If there is a master slave or dual compressor application all compressor relays and related func tions will operate per their associated DIP switch 2 setting on S1 7 3 4 Heating stage 3 In heating stage 3 mode...

Страница 25: ...fast flashes followed by a 10 second pause This sequence will repeat continually until the fault is cleared Table 14 C control LED code and fault descriptions LED code Fault Description 1 No fault in memory There has been no fault since the last power down to power up sequence 2 High pressure switch HP open instantly 3 Low pressure switch LP open for 30 continuous seconds before or during a call b...

Страница 26: ...t system refrigerant circuit oil will remain in the compressor To avoid leakage of compressor oil the refrigerant lines of the compressor must be sealed after it is removed IMPORTANT All refrigerant discharged from this unit must be recovered without exception Technicians must follow industry accepted guidelines and all local state and federal statutes for the recovery and disposal of refrigerants...

Страница 27: ...ion acts faster but cold solution is just as effective if applied for a longer period 9 7 1 Gravity flow method Do not add solution faster than vent can exhaust the generated gases When condenser is full allow solution to remain overnight then drain condenser and flush with clean water Follow acid manufacturer s instructions see Fig 18 9 7 2 Forced circulation method Fully open vent pipe when fill...

Страница 28: ...ide motor bracket assembly to extreme right and lift out through space between fan scroll and side frame Rest motor on a high platform such as a step ladder Do not allow motor to hang by its power wires 10 TROUBLESHOOTING Figs 20 and 21 and Table 16 When troubleshooting problems with a water source heat pump consider the following 10 1 Thermistor A thermistor may be required for single phase units...

Страница 29: ...ture out of range Too much cold vent air Bring entering air temperature within design parameters X Improper freeze protect setting Normal airside applications will require 1 1 C only 1 1 C vs 12 2 C X X Bad thermistor Check temperature and impedance correlation Condensate fault code 6 X X Blocked drain Check for blockage and clean drain X X Improper trap Check trap dimensions and location ahead of...

Страница 30: ...ersized Recheck loads and sizing check sensible cooling load and heat pump capacity X X Scaling in water heat exchanger Perform scaling check and clean if necessary X X Inlet water too hot or cold Check load loop sizing loop backfill ground moisture High head pressure X Reduced or no airflow in heating Check for dirty air filter and clean or replace Check fan motor operation and airflow restrictio...

Страница 31: ...NSION VALVE C C AIR COIL C kPa C kPa LOOK UP PRESSURE DROP IN TABLE 10 TO DETERMINE FLOW RATE C LIQUID LINE kPa C DEW POINT Air coil Expansion valve Heat exchanger Look up pressure drop in Table 10 to determine flow rate Dew point Suction Compressor Discharge SUCTION COMPRESSOR DISCHARGE COAX EXPANSION VALVE C C AIR COIL C kPa C kPa LOOK UP PRESSURE DROP IN TABLE 10 TO DETERMINE FLOW RATE C LIQUID...

Страница 32: ... phase scroll compressor is present verify proper rotation per instructions Y N __________ Unit voltage cooling operation Phase AB Volts ________ Phase BC Volts ________ Phase CA Volts ________ if 3 phase if 3 phase Phase AB Amps ________ Phase BC Amps ________ Phase CAAmps ________ if 3 phase if 3 phase Control voltage Is the control voltage above 21 6 Volts Y N __________ If not check for proper...

Отзывы: