Fig. 10 - Typical Aquazone Complete C control wiring (three-phase unit)
Legend
AL
Alarm relay contacts
BR
Blower relay
CAP
Compressor capacitor
CB
Circuit breaker
CC
Compressor contactor
CO
Sensor, condensate overflow
COMP
Compressor
FP1
Sensor, water coil freeze protection
FP2
Sensor, air coil freeze protection
GND
Ground
HP
High pressure switch
JW
Clippable field selection jumper
LOC
Loss of charge pressure switch
P1
Field wiring terminal block
PB
Power block
PM
Performance Monitor
PSC
Permanent split capacitor
RVS
Reversing valve solenoid
TRANS
Transformer optional wiring
Field line voltage wiring
Field low voltage wiring
Printed circuit trace
Optional wiring
Relay/contactor coil
Thermistor
Condensate pan
Circuit breaker
Relay contacts - NC
Solenoid coil
Relay contacts - NO
Switch temperature
Switch low pressure
Ground
Wire nut
Splice cap
* Optional wiring
Notes:
1.
Compressor and blower motor thermally protected internally.
2.
All wiring to the unit must comply with local codes.
3.
Transformer is wired to 240 V (ORG) lead for 240-1-50 units, switch RED and
ORG leads to PB(3) and insulate ORG lead.
4.
FP1 thermistor provides freeze protection for water. When using anti-freeze
solutions, cut JW3 jumper.
5.
Typical heat pump thermostat wiring shown. Refer to thermostat installation
instructions for wiring to the unit.
6.
24-V alarm signal shown. For dry alarm contact, cut JW1 jumper, and dry
contact will be available between AL1 and AL2.
7.
Transformer secondary ground via microprocessor board stand-offs and
screws to control box. (Ground available from top two stand-offs as shown.)
8.
Fan motors factory-wired for medium speed. For high or low speed remove
BLU wire from fan motor speed tap ‘M’ and connect to ‘H’ for high or ‘L’ for low.
(
LUG
T3
T2
T1
CC
PB
BR1
BR2
TRANS
CXM
Y
O
G
R
C
L
Y
O
G
R
C
AL1
W
AL2
A
P1
Y
R
C
JW1
JW3
FP1
JW2
FP2
G
1
0
BR
GRY
BRN
BR
BRG
CCG
CC
BRN YEL
CC
1
2
3
4
5
6
7
8
9
10
12
HP
LOC
FP1
FP2
RV
CO
P2
P3
CO
24V
DC
EH1
EH2
RED
RED
BLU
BRN
GRY
GRY
HP
LOC
FP1
FP2
RVS
CO
BRN
ORG
YEL
VIO
VIO
VIO
CB* TRANS
RED
(220V)
L3
L2
L1
BLK
BLK
G/Y
BLK
BLK
BLK
BLK
ORG
(240V)
YEL OR
WHT
BRN
YEL
BLK
BLK
BLK
BLK
L3
L2
L1
T3
T2
T1
CC
CC
G/Y
G/Y
BLK
BLU
RED
BM
H
M
L
6
7
8
BR2
T3
T2
T1
6
5
4
3
2
1
PB
OFF
ON
1
2
3
4
5
Power supply
Refer to data plate
Use copper
conductors only
Earth (GRD)
N (Neutral)
Component location
Lug
Compr.
Ground lug
See note 2
See note 3
See note 5
Typical
T-stat
Compr.
Cooling
Fan
24 V a.c.
Common
Alarm
See note 6 for
dry alarm contact
Test pins
See
note 4
Low temp.
Low temp.
Alarm
relay
See
note 5
Compressor
relay
Dip switch
PM
Stages
Not used
Not used
1 or 3
Tree
Off
On
See note 7
Status
LED
CXM
Microprocessor
control logic
See note 7
See note 4
TXV units
Not used
Cap. tube
units