background image

16

CONNECT THE BLUE WIRE TO:

FAN MOTOR

MEDIUM FACTORY SETTING

H FOR HIGH SPEED FAN
M FOR MEDIUM SPEED FAN
L FOR LOW SPEED FAN

H

M

L

BLU

3.8.4 - PSC (permanent split capacitor) blower speed
selection
All water-source heat pumps are factory-set to deliver rated air
flow at nominal static (37 Pa) on medium speed. Where higher
static is needed, high speed can be utilised (100 to 125 Pa). Low
speed will deliver approximately 85% of rated air flow (25 Pa).
The PSC blower fan speed can be changed on all units by
swapping wires connected to the relay contacts that control the
fan (see Table 4 and Fig. 14).

NOTE: Available air flow for all units is shown in Table 4.

Fig. 14 - 50RHE blower speed selection

Table 4 - Fan performance

50RHE blower performance

50RHE

Nominal

Minimum

Fan

Air flow, l/s

air flow

air flow

speed

External static pressure, Pa

l/s

l/s

0

25

50

75

100

125

006

81

61

High

133

123

112

 89

 78

-

Medium

110

 99

 87

 68

-

-

Low

 98

 90

 75

 60

-

-

009

113

85

High

165

151

142

118

 99

-

Medium

160

146

127

113

 94

-

Low

151

137

123

109

 90

-

012

140

104

High

170

165

151

137

123

109

Medium

165

151

142

127

118

-

Low

146

137

127

118

104

-

015

212

160

High

345

316

288

250

198

-

Medium

321

302

274

241

189

-

Low

293

278

255

222

179

-

019

264

198

High

326

311

283

250

203

-

Medium

302

288

260

227

189

-

Low

293

269

245

217

179

-

024

307

231

High

396

368

335

302

260

-

Medium

387

359

326

297

255

-

Low

368

340

311

278

231

-

030

349

264

High

529

496

463

425

378

330

Medium

510

477

448

415

368

326

Low

458

439

406

378

340

297

036

437

326

High

614

576

579

463

415

373

Medium

580

543

488

434

392

349

Low

505

472

429

387

349

-

042

530

396

High

743

691

629

566

501

435

Medium

637

593

539

485

429

-

Low

498

463

421

-

-

-

048

630

472

High

793

738

672

604

535

464

Medium

777

723

658

592

524

455

Low

762

709

645

580

514

446

High static
048

630

472

High

-

-

-

757

668

552

Medium

-

-

787

710

623

529

Low

-

797

748

690

612

516

060

790

595

High

896

866

833

796

755

710

Medium

818

803

779

747

707

658

Low

748

731

709

683

653

618

Legend

Shaded areas are below minimum air flow. This data is provided for troubleshooting information only.

Notes:
1.

Units factory-shipped on medium speed. Other speeds require field selection.

2.

For dual voltage units, air flow is rated at lowest voltage.

3.

Performance data shown is based on wet coil and clean air filter.

Connect the blue wire to:
H for high speed fan
M for medium speed fan
L for low speed fan

Fan motor

Medium factory setting

Blue

Содержание Aquazone 50RHE 006

Страница 1: ...ting in the Eurovent Certification Programme Products are as listed in the Eurovent Directory of Certified Products 50RHE 006 060 Water Source Heat Pumps Horizontal Units Installation OperationandMaintenanceInstructions TM ...

Страница 2: ...or rotation 21 6 3 Unit start up cooling mode 21 6 4 Unit start up heating mode 21 6 5 Flow regulation 21 6 6 Flushing 22 6 7 Anti freeze 23 6 8 Cooling tower boiler systems 23 6 9 Ground coupled closed loop and plateframe heat exchanger well systems 23 7 OPERATION 24 7 1 Power up mode 24 7 2 Units with Aquazone Complete C control 24 7 3 Units with Aquazone Deluxe D control 24 8 SYSTEM TEST 25 8 1...

Страница 3: ...ith each unit Before unit start up read all manuals and become familiar with the unit and its operation Thoroughly check out the system before operation Complete the inspections and instructions listed below to prepare a unit for installation See Table 1 for unit physical data Horizontal units are designed for indoor installation only Be sure to allow adequate space around the unit for servicing S...

Страница 4: ...tion isolators must have bolts loosened and shipping clamps removed 7 Remove any blower support cardboard from inlet of the blower 8 Locate and verify any accessory kit located in compressor section 9 Remove any access panel screws that may be difficult to remove once unit is installed Table 1 Physical data 50RHE 006 009 012 015 019 024 030 036 042 048 060 Cooling capacity kW 1 5 2 1 2 5 3 9 4 9 5...

Страница 5: ...t orientation is determined by looking at water connection side front N P M O 3 F K L 2 1 E A C V U B T S F N P M O 27 9 C V T S U B X Y Z A C R P Q O 82 6 O A C P Q R D 82 6 J 5 Left return 610 mm service access Front CSP Optional 610 mm service access Left return ASP Right discharge Back discharge Condensate 3 4 FPT Power supply 3 4 knockout 1 2 knockout Low voltage 1 2 knockout CAP Front view 8...

Страница 6: ...al for supply and return piping Water out Water in Low pressure drop water control valve optional field installedaccessory Balancing valve field installedand calibratedaccessory Water in Water out Supply loop Return loop Return air ductwork not shown 3 8 threaded rods by others Filter access Unit hanger isolation detail 3 8 threaded rod by others Vibration isolator white compressor end and red blo...

Страница 7: ...turn models in the field due to refrigerant piping changes Preparation The unit should be on the ground in a well lit area for conversion Hung units should be taken down to ground level before con verting Side to back discharge conversion 1 Remove screws to free the top and discharge panels see Fig 3 2 Remove the access panel and set aside 3 Lift the discharge panel from side of unit and rotate it...

Страница 8: ...y be required for the ventilating air supply If hard ducted ven tilation is not required be sure that a proper air path is provi ded for ventilation air to unit to meet ventilation requirement of the space Fig 5 Horizontal hanger bracket factory installed 50RHE Dimensions mm A B C D E 006 024 568 1095 619 1095 516 030 036 568 1349 619 1349 518 042 048 568 1577 619 1577 518 060 645 1806 695 1806 59...

Страница 9: ...flow verification In addition to complying with any applicable codes consider the following for system piping Piping systems using water temperatures below 10 C require 13 mm closed cell insulation on all piping surfaces to eliminate condensation Avoid all plastic to metal threaded fittings due to the potential to leak Use a flange fitted substitute Teflon tape thread sealant is recommended to min...

Страница 10: ... 12 for a schematic of the field connections which must be made by the installing or electrical contractor Refer to electrical data for fuse sizes Consult the unit wiring diagram located on the inside of the compressor access panel to ensure proper electrical hookup The installing or electrical contractor must make the field connections when using field supplied disconnect Operating voltage must b...

Страница 11: ...4 V alarm signal shown For dry alarm contact cut JW1 jumper and dry contact will be available between AL1 and AL2 7 Transformer secondary ground via microprocessor board stand offs and screws to control box Ground available from top two stand offs as shown 8 Fan motors factory wired for medium speed For high or low speed remove BLU wire from fan motor speed tap M and connect to H for high or L for...

Страница 12: ...to thermostat installation instructions for wiring to the unit 6 24 V alarm signal shown For dry alarm contact cut JW1 jumper and dry contact will be available between AL1 and AL2 7 Transformer secondary ground via microprocessor board stand offs and screws to control box Ground available from top two stand offs as shown 8 Fan motors factory wired for medium speed For high or low speed remove BLU ...

Страница 13: ...unit must comply with local codes 3 Transformer is wired to 240 V ORG lead for 240 1 50 units switch RED and ORG leads to PB 1 and insulate ORG lead for 220 1 50 4 FP1 thermistor provides freeze protection for water When using anti freeze solutions cut JW3 jumper 5 Check installation wiring information for specific thermostat hook up Refer to thermostat installation instructions for wiring to the ...

Страница 14: ...ia microprocessor board stand offs and screws to control box Ground available from top two stand offs as shown 8 Blower motor is factory wired for medium and high speeds For any other combination of speeds at the motor attach black wire to the higher of the two desired speed taps and the blue wire to the lower of the two desired speed taps 9 Blower motor is factory wired for high and low speeds No...

Страница 15: ...nit must be within voltage range indicated on unit nameplate On 3 phase units voltages under load between phases must be balanced within 2 Use the following formula to determine the percentage voltage imbalance voltage imbalance 100 x Example Supply voltage is 460 3 60 AB 452 Volts BC 464 Volts AC 455 Volts Average voltage 457 Determine maximum deviation from average voltage AB 457 452 5 V BC 464 ...

Страница 16: ... 118 104 015 212 160 High 345 316 288 250 198 Medium 321 302 274 241 189 Low 293 278 255 222 179 019 264 198 High 326 311 283 250 203 Medium 302 288 260 227 189 Low 293 269 245 217 179 024 307 231 High 396 368 335 302 260 Medium 387 359 326 297 255 Low 368 340 311 278 231 030 349 264 High 529 496 463 425 378 330 Medium 510 477 448 415 368 326 Low 458 439 406 378 340 297 036 437 326 High 614 576 57...

Страница 17: ...n Fig 17 Aslow closing valve may be required to prevent water hammer When using a slow closing valve consider special wiring conditions The valve takes approximately 60 seconds to open very little water will flow before 45 seconds and it activates the compressor only after the valve is completely opened by closing its end switch When wired as shown the valve will have the following operating chara...

Страница 18: ...emp to choose FP1 limit of 12 2 C or 1 1 C To select 1 1 C as the limit DO NOT clip the jumper To select 12 2 C as the limit clip the jumper Air coil freeze protection FP2 limit setting Select jumper 2 JW2 FP2 low temp to choose FP2 limit of 12 2 C or 1 1 C To select 1 1 C as the limit DO NOT clip the jumper To select 12 2 C as the limit clip the jumper Alarm relay setting Select jumper 1 JW1 AL2 ...

Страница 19: ...cooling stage 2 Select ON for normal mode The fan speed relay will turn on during cooling stage 2 in normal mode Switch 6 Not used Boilerless operation Switch 7 provides selection of boilerless operation and works in conjunction with switch 8 In boilerless operation mode only the compressor is used for heating when FP1 is above the boilerless changeover temperature set by switch 8 below Select ON ...

Страница 20: ...ir will adversely affect the unit performance reliability and service life Power supply A voltage variation of 10 of nameplate utilisation voltage is acceptable Unit starting conditions Depending on the model units start and operate in an ambient temperature of 7 2 C with entering air temperature at 4 4 C or 10 C entering water temperature at 6 7 C or 10 C and with both air and water at the flow r...

Страница 21: ... 8 Water temperature change through heat exchanger Water flow rate l s Cooling rise K Heating drop K Min Max Min Max For closed loop ground source or cooling boiler systems at 0 054 l s per kW 5 6 7 2 2 4 4 For open loop ground water systems 0 027 l s per kW 11 1 14 4 5 6 9 4 6 4 Unit start up heating mode NOTE Operate the unit in heating cycle after checking the cooling cycle Allow five minutes b...

Страница 22: ...12 3 11 7 0 568 26 9 25 4 23 6 22 4 0 757 44 0 41 0 38 3 36 5 060 0 473 33 5 31 4 29 3 27 8 0 713 58 3 54 4 50 8 48 4 0 947 88 5 82 8 77 1 73 3 6 6 Flushing Once the piping is complete units require final purging and loop charging A flush cart pump of at least 1 12 kW is needed to achieve adequate flow velocity in the loop to purge air and dirt particles from the loop Flush the loop in both direct...

Страница 23: ...lume l per 30 m of pipe Pipe Diameter in Volume l Copper 1 15 5 1 25 24 2 1 5 34 8 Rubber hose 1 14 7 Polyethylene 3 4 IPS SDR11 10 6 1 IPS SDR11 17 0 1 1 4 IPS SDR11 30 0 1 2 IPS SDR11 41 2 2 IPS SDR11 68 1 1 1 4 IPS SCH40 31 4 1 1 2 IPS SCH40 41 2 2 IPS SCH40 64 3 Legend IPS Internal pipe size SCH Schedule SDR Standard dimensional ratio Note Volume of heat exchanger is approximately 3 78 litres ...

Страница 24: ... fan enable and compressor relays are remain on The fan speed relay is turned on immediately and turned off immediately once the demand is removed The control reverts to heating stage 1 mode If there is a master slave or dual compressor application all compressor relays and related func tions will operate per their associated DIP switch 2 setting on S1 7 3 4 Heating stage 3 In heating stage 3 mode...

Страница 25: ...fast flashes followed by a 10 second pause This sequence will repeat continually until the fault is cleared Table 14 C control LED code and fault descriptions LED code Fault Description 1 No fault in memory There has been no fault since the last power down to power up sequence 2 High pressure switch HP open instantly 3 Low pressure switch LP open for 30 continuous seconds before or during a call b...

Страница 26: ...t system refrigerant circuit oil will remain in the compressor To avoid leakage of compressor oil the refrigerant lines of the compressor must be sealed after it is removed IMPORTANT All refrigerant discharged from this unit must be recovered without exception Technicians must follow industry accepted guidelines and all local state and federal statutes for the recovery and disposal of refrigerants...

Страница 27: ...ion acts faster but cold solution is just as effective if applied for a longer period 9 7 1 Gravity flow method Do not add solution faster than vent can exhaust the generated gases When condenser is full allow solution to remain overnight then drain condenser and flush with clean water Follow acid manufacturer s instructions see Fig 18 9 7 2 Forced circulation method Fully open vent pipe when fill...

Страница 28: ...ide motor bracket assembly to extreme right and lift out through space between fan scroll and side frame Rest motor on a high platform such as a step ladder Do not allow motor to hang by its power wires 10 TROUBLESHOOTING Figs 20 and 21 and Table 16 When troubleshooting problems with a water source heat pump consider the following 10 1 Thermistor A thermistor may be required for single phase units...

Страница 29: ...ture out of range Too much cold vent air Bring entering air temperature within design parameters X Improper freeze protect setting Normal airside applications will require 1 1 C only 1 1 C vs 12 2 C X X Bad thermistor Check temperature and impedance correlation Condensate fault code 6 X X Blocked drain Check for blockage and clean drain X X Improper trap Check trap dimensions and location ahead of...

Страница 30: ...ersized Recheck loads and sizing check sensible cooling load and heat pump capacity X X Scaling in water heat exchanger Perform scaling check and clean if necessary X X Inlet water too hot or cold Check load loop sizing loop backfill ground moisture High head pressure X Reduced or no airflow in heating Check for dirty air filter and clean or replace Check fan motor operation and airflow restrictio...

Страница 31: ...NSION VALVE C C AIR COIL C kPa C kPa LOOK UP PRESSURE DROP IN TABLE 10 TO DETERMINE FLOW RATE C LIQUID LINE kPa C DEW POINT Air coil Expansion valve Heat exchanger Look up pressure drop in Table 10 to determine flow rate Dew point Suction Compressor Discharge SUCTION COMPRESSOR DISCHARGE COAX EXPANSION VALVE C C AIR COIL C kPa C kPa LOOK UP PRESSURE DROP IN TABLE 10 TO DETERMINE FLOW RATE C LIQUID...

Страница 32: ... phase scroll compressor is present verify proper rotation per instructions Y N __________ Unit voltage cooling operation Phase AB Volts ________ Phase BC Volts ________ Phase CA Volts ________ if 3 phase if 3 phase Phase AB Amps ________ Phase BC Amps ________ Phase CAAmps ________ if 3 phase if 3 phase Control voltage Is the control voltage above 21 6 Volts Y N __________ If not check for proper...

Отзывы: