T-365
4–50
AL61
HEATER CURRENT DRAW FAULT
Cause:
Improper current draw during heat or defrost mode.
Component
Heater(s)
Troubleshooting
While in heat or defrost mode, check for proper current draw at heat-
er contactors, refer to ELECTRICAL DATA
Corrective Action
Replace heater(s) if defective, refer to
Evaporator
Heater Removal and Replacement.
Component
Contactor
Troubleshooting
Check voltage at heater contactor on the heater side. If no voltage
present:
Corrective Action
Replace heater contactor if defective.
AL63
CURRENT LIMIT
Cause:
Unit operating above current limit.
Component
Refrigeration System
Troubleshooting
Check unit for air flow restrictions.
Corrective Action
Clean or remove any debris from coils.
Troubleshooting
Check unit for proper operation.
Corrective Action
Repair as needed.
Component
Power supply
Troubleshooting
Confirm supply voltage/frequency is within specification and bal-
anced according to ELECTRICAL DATA
.
Corrective Action
Correct power supply.
Component
Current limit set too low.
Troubleshooting
Check current limit setting Code Cd32.
Corrective Action
The current limit can be raised (maximum of 23 amps) using Cd32.
AL64
DISCHARGE TEMPERATURE SENSOR (CPDS)
Cause:
Discharge Temperature sensor out of range.
Component
Discharge temperature sensor (CPDS).
Troubleshooting
Test the CPDS; refer to Sensor Checkout Procedure,
Corrective Action
Replace the CPDS if defective, refer to Sensor Replacement
.
Содержание 69NT40-561-300
Страница 2: ......
Страница 4: ......
Страница 10: ......
Страница 14: ......
Страница 22: ......
Страница 34: ......
Страница 108: ......
Страница 116: ......
Страница 164: ...T 365 8 2 Figure 8 2 Unit Wiring Diagram Based on Drawing 62ï11755 ...
Страница 165: ...8 3 T 365 Figure 8 3 Wiring Diagram Based on Drawing 62ï11755 ...
Страница 166: ...T 365 8 4 Figure 8 4 Wiring Diagram Based on Drawing 62ï11755 ...
Страница 168: ......
Страница 172: ......
Страница 173: ......