7–39
T-365
7.25.4
Sensors RRS and RTS Re-Installation
Reinstall the return sensor (Return Temperature Sensor RTS or Return Recorder Sensor RRS), as shown in
. For proper placement of the return sensor, be sure to position the enlarged positioning section of the sen-
sor against the side of the mounting clamp.
Figure 7.25 Return Sensor Positioning
7.25.5
Sensor DTS Re-Installation
The Defrost Temperature Sensor (DTS) must have insulating material placed completely over the sensor to ensure
the coil metal temperature is sensed.
7.25.6
Sensors ETS1 and ETS2 Re-Installation
The Evaporator Temperature Sensors, ETS1 and ETS2 are located in a tube holder under insulation, as illustrated
in
. When the combo sensor is removed and reinstalled, it must be placed in a tube holder by applying
thermal grease. Insulating material must completely cover the sensor to ensure the correct temperature is sensed.
Figure 7.26 Evaporator Temperature Sensor Positioning
7.25.7
Sensor, CPDS Re-Installation
To replace the Compressor Discharge Temperature Sensor, see
1. Ensure the unit is disconnected from the power source and that ST is in OFF position.
2. Remove the existing sensor. Clean all silicone sealer and dielectric compound from the sensor well. Ensure
well is clean and dry. The top of the compressor, where the sensor seals, must also be clean and dry.
1.50 in.
(38.1cm)
Mounting
Clamp
Return
Sensor
1.00 in.
(25.4cm)
Wire Tie
ETS1 and ETS2
ETS Tube Holder
Insulation
Содержание 69NT40-561-300
Страница 2: ......
Страница 4: ......
Страница 10: ......
Страница 14: ......
Страница 22: ......
Страница 34: ......
Страница 108: ......
Страница 116: ......
Страница 164: ...T 365 8 2 Figure 8 2 Unit Wiring Diagram Based on Drawing 62ï11755 ...
Страница 165: ...8 3 T 365 Figure 8 3 Wiring Diagram Based on Drawing 62ï11755 ...
Страница 166: ...T 365 8 4 Figure 8 4 Wiring Diagram Based on Drawing 62ï11755 ...
Страница 168: ......
Страница 172: ......
Страница 173: ......