T-365
4–40
AL08
HIGH COMPRESSOR PRESSURE RATIO
Cause:
Controller detects discharge pressure to suction pressure ratio is too high.
The controller will attempt to correct the situation by restarting the compressor.
Component
Discharge Pressure Transducer (DPT)
Troubleshooting
Confirm accurate DPT pressure readings, refer to MANIFOLD
GAUGE SET
.
Corrective Action
Replace DPT if defective.
AL10
CO
2
SENSOR FAILURE
Cause:
Alarm 10 is triggered when the C
O
2
sensor voltage is operating outside of the 0.9 v to 4.7 v range,
or if the sensor is out of range.
Component
This is a display alarm and has no associated failure action.
Troubleshooting
Refer to eAutoFresh manual.
Corrective Action
The alarm is triggered off when voltage is within operating range.
AL14
PHASE SEQUENCE DETECT FAULT
Cause:
Controller is unable to determine the correct phase relationship.
Component
N/A
Troubleshooting
Power cycle the unit.
Corrective Action
Resetting the unit may correct problem, monitor the unit.
Component
Wiring
Troubleshooting
Check unit wiring.
Confirm pressure readings during start-up; suction pressure should
decrease and discharge pressure should increase.
Corrective Action
Correct wiring.
Component
Current Sensor
Troubleshooting
Check Cd41, right most digit:
If display is 3 or 4 check compressor / sensor wiring.
If display is 5 the current sensor is defective.
Corrective Action
Replace current sensor if defective.
Содержание 69NT40-561-300
Страница 2: ......
Страница 4: ......
Страница 10: ......
Страница 14: ......
Страница 22: ......
Страница 34: ......
Страница 108: ......
Страница 116: ......
Страница 164: ...T 365 8 2 Figure 8 2 Unit Wiring Diagram Based on Drawing 62ï11755 ...
Страница 165: ...8 3 T 365 Figure 8 3 Wiring Diagram Based on Drawing 62ï11755 ...
Страница 166: ...T 365 8 4 Figure 8 4 Wiring Diagram Based on Drawing 62ï11755 ...
Страница 168: ......
Страница 172: ......
Страница 173: ......