T-365
4–42
AL17
COMPRESSOR PRESSURE DELTA FAULT
Cause:
Compressor has attempted to start in both directions and fails to generate sufficient pressure dif-
ferential between SPT and DPT.
Component
N/A
Troubleshooting
Controller will attempt restart every 20 minutes and deactivate the
alarm if successful.
Corrective Action
Resume normal operation.
Component
Discharge Pressure Transducer (DPT)
Troubleshooting
Confirm accurate DPT pressure readings, refer to MANIFOLD
GAUGE SET
.
Corrective Action
Replace DPT if defective.
Component
Suction Pressure Transducer (SPT)
Troubleshooting
Confirm accurate SPT pressure readings, refer to MANIFOLD
GAUGE SET
.
Corrective Action
Replace SPT if defective.
Component
Monitor unit
Troubleshooting
Alarm is display only the alarm may clear itself during operation.
Corrective Action
If alarm remains active or is repetitive replace compressor at next
available opportunity.