Local OAT/OARH Sensor
Enabled
R/W
local_oa_sens_en
BV
1115
Read/write to Enable the Local OAT/OARH sensor.
LPS #1 Status
R
lps1_stat
BV
225
Low Pressure Switch #1 Status.
LPS #2 Status
R
lps2_stat
BV
228
Low Pressure Switch #2 Status.
LPS1 ALARM
R
lps1_alarm
BV
869
The current Low Pressure Switch #1 Alarm Status.
LPS1 STOP
R
lps1_stop_alarm
BV
870
The current Low Pressure Switch #1 Stop Alarm Status.
LPS2 ALARM
R
lps2_alarm
BV
883
The current Low Pressure Switch #2 Alarm Status.
LPS2 STOP
R
lps2_stop_alarm
BV
884
The current Low Pressure Switch #2 Stop Alarm Status.
LSAT ALARM
R
low_sat_alarm
BV
898
The current Low Supply Air Temperature Alarm Status.
MARH FAIL
R
marh_failure
BV
828
The current MARH Sensor Alarm status.
MA-RH Status
R
marh_stat
AV
224
The Current Mixed Air Relative Humidity Status (MARH).
MAT FAIL
R
mat_failure
BV
827
The current MAT Sensor Alarm status.
MAT Status
R
mat_stat
AV
223
The current Mixed Air Temperature (MAT).
Mixed Air Dew Point
R
ma_dewpoint
AV
264
The current Mixed Air Dew Point Status
Mixed Air Enthalpy
R
ma_enthalpy
AV
265
The current Mixed Air Enthalpy Status
Night Setback Mode ON
R
nsb_on
BV
219
This point displays the status of the Night Setpoint Mode.
NOT ECON
R
not_econ_fdd
BV
961
The current FDD Alarm is not Economizing when it should.
OA AMS SP
R/W
oa_ams_sp
AV
306
The setpoint for Outdoor Air Monitoring Station (Default is
800cfm)
OA Damper Enable
R
oada_en
BV
242
Outdoor Air Damper Enable Code Status
OADA ALARM
R
oada_alarm
BV
950
The current Outside Air Damper Actuator Alarm Status.
OADA HAND
R
oada_hand_alarm
BV
951
The current Outside Air Damper Actuator Hand Alarm Status.
OADA Minimum Position
R/W
oada_min_pos_cm
d
AV
607
Read/write Outside Air Damper Minimum Position.
OADA PID Output
Override
R/W
oada_pid_ovrd
AV
609
Read/write OADA PID Output for CAV (Percentage)
OADA PID Output
Override Lock
R/W
oada_pid_ovrd_loc
k
BV
601
Read/write Outside Air Damper PID Output in Constant Air
Volume (CAV) Status.
OADA Position
R
oada_pos
AV
204
The current Outside Air Damper Position Feedback.
OADA Status
R
oada_stat
BV
220
Outdoor Air Damper Actuator Auxiliary Status.
OARH FAIL
R
oarh_failure
BV
836
The current MAT Sensor Alarm status.
OARH from BAS
R/W
bas_oarh
AV
1106
Read/write Outside Air Relative Humidity Supplied By BAS.
OA-RH Status
R
oarh_stat
AV
229
The Current Outdoor Air Relative Humidity Sensor Status
(OARH).
OAT FAIL
R
oat_failure
BV
835
The current OAT Sensor Alarm status.
OAT from BAS
R/W
bas_oat
AV
1104
Read/write Outside Air Temperature Supplied by BAS.
OAT Status
R
oat_stat
AV
227
The Current Outside Air Temperature Status (RAT).
Occupancy Control
Options
R/W
occ_ctrl_opts
MSV
101
Read/write point will set the unoccupied/occupied control to
local,BAS,24/7,S/S switch, CO
2
mode.
Occupancy Status
R
occ_status
BV
105
This point gives you the unoccupied/occupied status of the unit.
Occupied Cooling Mode
Low Limit
R/W
clg_llim
AV
319
The setpoint for Occupied Low Limit Cooling Temperature.
(Default is 55°F)
OD Command
R
od_cmd
BV
1120
Outside Damper Start Command (BO-6).
Operating Condition
R
op_cond
AV
111
This point is a multistat and Table 1 must be used to cross
reference the number to Condition.
Operating Mode
R
op_mode
AV
112
This point is a multistat and Table 2 must be used to cross
reference the number to Operating Mode.
Optimal Start On
R
opt_start_on
BV
902
The current Optimal Start Status.
Outside Air Dew Point
R
oa_dewpoint
AV
266
The current Outside Air Dew Point Status
Outside Air Enthalpy
R
oa_enthalpy
AV
267
The current Outside Air Enthalpy Status
RADA NOT
R
rada_not_mod_fdd
BV
963
The current FDD Alarm the Dampers are Mechanically
Disconnected.
RADA Position
R
rada_pos
AV
601
The current Return Air Damper Actuator Position.
RADA Status
R
rada_stat
AV
283
The current Return Air Damper Actuator Position Status
RARH FAIL
R
rarh_failure
BV
834
The current RARH Sensor Alarm status.
RA-RH Status
R
rarh_stat
AV
226
The current Return Air Humidity (RARH).
RAT FAIL
R
rat_failure
BV
833
The current RAT Sensor Alarm status.
RAT Status
R
rat_stat
AV
225
The current Return Air Temperature Sensor Status (RAT).
Return Air Damper
Status
R
rada_cmd
BV
503
The current Return Air Damper Status
Return Air Dew Point
R
ra_dewpoint
AV
268
The current Return Air Dew Point Status
Return Air Enthalpy
R
ra_enthalpy
AV
269
The current Return Air Enthalpy Status
RH CMD
R
rh_cmd
BV
564
HGRH Start Command (BO-4).
RH in Cooling
R/W
rh_clg_mode
BV
561
Read/write point Enables Reheat in Cooling Mode.
RV CMD
R
rv_cmd
BV
550
The Reversing Valve Start Command (BO-5).
S/S Switch Status
R
ss_sw_stat
BV
236
Start/Stop Switch Status (N.O.).
SARH FAIL
R
sarh_failure
BV
840
The current SARH Sensor Alarm status.
SARH Status
R
sarh_stat
AV
237
The current Supply Air Relative Humidity Sensor Status (SARH).
SAT FAIL
R
sat_failure
BV
839
The current SAT Sensor Alarm status.
SAT Heat Fail SP
R/W
sat_heat_fail_sp
AV
361
The setpoint for Supply Air Temperature Heat Failure Alarm
(Default is 50°F).
Table C — Mapping Points - Carrier 62X Rev. H - 100% Outdoor Air Air-to-Air (cont)