MANUAL OCC CONTROL
Manually overrides the current occupancy level. The Occupancy
Control setting must be set to BAS control for manual occupancy
control to function.
• Off - no occupancy override
• Occupied - unit will be in occupied mode regardless of oc
-
cupancy control command
• Unoccupied - unit will be in unoccupied mode regardless
of occupancy control command
ENABLE UNIT OPERATION
Used to enable or disable unit operation
• On - unit can enter occupied or unoccupied mode
• Off - unit is disabled and will not enter any mode
EMERGENCY SHUTDOWN
Used to force an emergency shutdown of the unit.
• Off - Unit operation is enabled
• On - Unit is placed in emergency shutdown. All compo
-
nents will be disabled.
EMERGENCY HEAT ENABLE (62H AND 62W HEAT
PUMPS ONLY)
Allows an auxiliary heat source to be used an emergency heat if
the heat pump heating is disabled.
• Off - emergency heat disabled
• On - emergency heat enabled
SF MINIMUM SETTING
Sets the minimum operating speed for the supply fan for all oper
-
ating modes (except heat pump heating on 62H and 62W units).
The minimum speed is based on an operating range of 0-100%.
SF HP MINIMUM SETTING
Sets the minimum operating speed for the supply fan during
heat pump heating mode (62H and 62W units only). The mini
-
mum speed is based on an operating range of 0-100%. The de
-
fault setting is 50%. The default setting is 80%.
ZAT/SAT RESET
Allows the 62X to reset the supply air temperature set point based
on an external temperature input. ZAT reset requires the use of a
Carrier ZS sensor or other Rnet sensor. See SAT Reset screen
(
Home
Setup
SAT Reset
) for SAT reset set points. Below are
the available configurations for SAT reset:
• None - SAT reset disabled
• ZAT CLG - SAT reset is active for cooling mode based on
zone air temp
• ZAT HTG - SAT reset is active for heating mode based on
zone air temp
• ZAT DEH - SAT reset is active for dehum mode based on
zone air temp
• OAT CLG - SAT reset is active for cooling mode based on
outdoor air temp
• OAT HTG - SAT reset is active for heating mode based on
outdoor air temp
• OAT DEH - SAT reset is active for dehum mode based on
outdoor air temp
HWV MINIMUM OUTPUT
Sets the minimum output for the hot water valve during heating
mode. The minimum output is based on an operating range of 0-
100%. Setting a minimum output is recommended for preventing
freezing of the hot water coil.
SUPPLY FAN OCCCUPIED/UNOCCUPIED OPERATION
Determines how the supply fan will behave during occupied and
unoccupied mode. Unoccupied mode is only with night setback
ETO.
1 = Continuous/ Demand - the supply fan operates continuously
during occupied mode, only on demand for cooling, heating, or
dehum during unoccupied mode.
2 = Continuous/ Continuous - the supply fan operates continuous
-
ly during occupied mode and unoccupied mode.
3 = Demand/ Demand - the supply fan only operates with demand
for cooling, heating, or dehum during occupied or unoccupied
mode (not used with 62X).
SCHEDULES
The Schedules screen (
Home
Setup
Schedule
) displays the
active local schedule and allows a user to add new schedules. See
Fig. 33 — Monthly Schedule
Fig. 34 — Daily Schedule
VIEWING LOCAL SCHEDULES
See Table 7.
Table 7 — Local Schedule Options
Click on the View Schedule
button to change between daily,
weekly, or monthly view
Click on the forward and
backwards arrow to change the
date range of the schedule in
view
Click on any day to view the
effective schedule for the day