Carrier 50EH 1100 Скачать руководство пользователя страница 29

29

Caution: Do not work on any electrical components 
without fi rst turning off  the main door switch in the 
electric panel.

14 - MAINTENANCE

The minimal maintenance operations and their periodicity 
will be made in accordance with national regulations. 

All  work  on  the  unit’s  electrical  or  refrigerant  systems  must 
be  carried  out  by  a  qualifi ed  authorised  technician.  See  the 
standard EN 378-4.

It is advisable to sign a maintenance contract with the installer 
or an approved maintenance company.

14.1 General recommendations

Safety instructions 

● Technicians  working  on  the  unit  must  wear  the  necessary 

safety gear (e.g. gloves, eye protection, insulating clothing, 
safety shoes).

● Similarly,  it  is  recommended  that  personnel  working  close 

to sources of high noise emission wear ear defenders. The 
ear defenders should in no way impede the wearing of other 
protective equipment.

● The  surfaces  of  the  compressor  and  pipes  may  reach 

temperatures  of  over  100°C  and  cause  burns  if  touched. 
Likewise, the surfaces of the compressor may in some cases 
drop to freezing temperatures which can cause frostbite. It is 
therefore  important  to  take  special  care  when  carrying  out 
maintenance work.

● Do not climb on the machine; use a platform to work at the 

necessary height.

● Do not climb on the copper refrigerant pipes.

Preliminary advise

● Keep the unit clean. 

● To avoid accidents and ensure proper ventilation of the coil, 

keep the unit and the space around it clean and clear of clutter.

● Check the fouling level of the coil.

Oil

Oils for refrigeration units do not pose any health risks if they 
are used in compliance with the precautions for use:

● Avoid unnecessary handling of components lubricated with 

oil. Use protective creams.

● Oils are fl ammable and must be stored and handled with care. 

Disposable rags or cloths used in cleaning must be kept away 
from open fl ames and disposed of in the appropriate manner.

● Containers must be stored with their caps on. Avoid using oil 

from an opened container stored under incorrect conditions.

● Check the oil level and aspect. In case of a colour change, 

check the oil quality using a contamination test. 

● In the case of the presence of acid, water or metallic particles, 

replace the aff ected circuit oil, as well as the fi lter dryer. 

● If all the oil must be emptied, replace it imperatively with new 

oil of the same grade as the original oil which has been stored 
in a hermetically sealed container until its time of use.

  The oil type recommended for these units is: 

Copeland 3MAF 32cST, Danfoss POE 160SZ, ICI Emkarate 
RL 32CF, Mobil EAL Artic 22CC.

The following table indicates the required volume:

Refrigerant

Only qualifi ed personnel must perform a periodic leak testing, in 
accordance with the regulation (EC) 

No. 517/2014.

● The frequency of checks is no longer related to the refrigerant 

charge but to its global warming potential: 

Charge kg x GWP =  t CO2e 

Carbon  dioxide  equivalency  (t  CO2e)  is  a  quantity  that 
describes,  for  a  given  mixture  and  amount  of  greenhouse 
gas, the amount in tonnes of CO2 that would have the same 
global warming potential (GWP).

The  number  of  tonnes  of  CO2  equivalent  (t  CO2e)  can  be 
consulted in the following table:

● Operators shall ensure that the unit is checked for leaks ad 

minima according to the following frequency:
•  t CO2e < 5  ......... not subjected
•  t CO2e 5 to 50  ... every year
•  t CO2e 50 to 500  every 6 months
•  t CO2e > 500 ...... every 3 months

● Where  a  leakage  detection  system  has  been  installed  the 

frequency of checks is halved.

Note: These machines use R410A. It is essential that technicians 
use equipment which is compatible with R410A with a working 
pressure which is approximately 1.5 times higher than that of 
units using R407C.

● Always  remember  that  refrigeration  systems  contain 

pressurised  liquids  and  vapours. All  necessary  provisions 
must be made when the system is partially opened: ensure 
the part of the circuit concerned is not pressurised.

● Partial  opening  of  the  primary  refrigerating  circuit  will 

cause  a  certain  quantity  of  refrigerant  to  be  released  into 
the  atmosphere.  It  is  essential  to  keep  the  amount  of  lost 
refrigerant  as  low  as  possible  by  pumping  the  charge  and 
isolating it in another part of the system.

50EN/EH 415 420 480 485 540 600 650 720 840 960 1100 1200

Charge 

(kg)

2 x 

17,0

2 x 

17,0

2 x 

14,5

2 x 

17,0

2 x 

21,0

2 x 

21,5

2 x 

26,5

2 x 

26,0

4 x 

14,5

4 x 

14,5

4 x 

14,3

4 x 

15,5

Environ. 

impact 

(t CO2e)

71,0 71,0 60,6 71,0 87,7 89,8 110,7 108,6 121,1 121,1 119,4 129,5

Main circuits:

50EN/EH 415 420 480 485 540 600 650 720 840 960 1100 1200

Volume (l)

3,0

3,3

4

6,2

6,2

50EN/EH 415 420 480 485 540 600 650 720 840 960 1100 1200

Volume (l)

4 x 3,3

4 x 6,2

Recovery circuit (optional):

50EN/EH 415 420 480 485 540 600 650 720 840 960 1100 1200

Charge 

(kg)

8,0 8,5 8,2 9,0 10,0 10,0 10,0 10,0 9,5

9,5 10,5 10,5

Environ. 

impact 

(t CO2e)

16,7 17,7 17,1 18,8 20,9 20,9 20,9 20,9 19,8 19,8 21,9 21,9

Main circuits:

Recovery circuit (optional):

Содержание 50EH 1100

Страница 1: ...E N A N C E I N S T R U C T I O N S Translation of the original document 80049 12 2018 Packaged rooftop units and separated gas module option 50EN EH 415 1200 Nominal cooling capacity 92 8 287 0 kW No...

Страница 2: ...ntrifugal fans optional 17 9 4 Air ducts connections 18 10 CONDENSATE DRAIN 19 11 SAFETY ELEMENTS 20 12 FACTORY OPTIONS AND ACCESSORIES 22 12 1 Filters 22 12 2 Hot water coil 22 12 3 Electrical heater...

Страница 3: ...serial Nbr A o An Year Producto Product Produit Ref Produit Item Nbr Max Intensidad Intensit Current Kit Elec Tension Voltage Refrig KG F brica Factory Usine Co2 Teq Refrigerant NoBo Peso Poids Weight...

Страница 4: ...1 optional 2 optional Assembly Assemblies with mixing box and free cooling Standard assembly M0 assemblies Change of supply and or return air position in the indoor circuit ME assemblies Axial air ex...

Страница 5: ...stics or in the regulatory documentation provided with the product The compressor and line surfaces can reach temperatures above 100 C causing burns to the body In the same fashion under certain condi...

Страница 6: ...he weight and the gravity centre coordinates of each model stated in the following page The recommended length for the forks will be bigger than the unit width so that the entire weight bearing struct...

Страница 7: ...lies MRC1 assembly Centre of gravity Weight kg Centre of gravity Weight kg Centre of gravity Weight kg Centre of gravity Weight kg X mm Y mm Z mm X mm Y mm Z mm X mm Y mm Z mm X mm Y mm Z mm 415 1 566...

Страница 8: ...85 385 385 385 475 475 Gas burner module PCH065 414 414 414 PCH080 440 440 440 440 440 440 440 440 PCH105 468 468 468 468 468 468 468 468 PCH130 504 504 504 504 504 504 504 504 520 520 PCH160 555 555...

Страница 9: ...en installed These units can be installed on the oor or on a brick curb or steel pro le Based on the xing solution de ned in the installation project it will be necessary to plan the placement in the...

Страница 10: ...9 314 412 648 273 960 423 598 254 364 539 195 411 627 275 402 619 267 466 711 326 425 671 286 466 711 326 425 671 286 50EN EH MC0 Assembly MRC0 Assembly MC1 MWC1 Assemblies MRC1 Assembly R1 R2 R3 R4 R...

Страница 11: ...R8 1100 330 536 475 288 357 564 502 316 330 536 475 288 357 564 502 316 1200 349 567 481 292 375 592 507 318 349 567 481 292 375 592 507 318 50EN EH MC0 Assembly MRC0 Assembly R1 R2 R3 R4 R5 R6 R7 R8...

Страница 12: ...nd 960 50EN EH 1100 and 1200 LEGEND Indoor air coil Outdoor air coil Air supply Air return Condensates outlet 2 2 1 2000m m 2500mm 1500mm 1500mm 3 4 5 3500mm 2 2 1 1500mm 1500mm 3000m m 3 4 5 7 POSITI...

Страница 13: ...tures refer to the technical brochure and the name plate The distance between the unit and its power source The protection to be placed at the power source Neutral operating conditions The electrical...

Страница 14: ...the indoor circuit are connected Electric power supply inputs Main panel Auxiliary panel Main panel Electric power supply inputs Optionally these units can change the electronic control to CARRIERrtc...

Страница 15: ...the cover clockwise g 4 Reversing valve heat pump Outdoor fan Compressor Low pressure High pressure Outdoor temperature probe B2 B7 Press transducer in the outdoor coil cir 1 Discharge T klixon switch...

Страница 16: ...f the control board connector J18 Recommended cable section 1 5 mm2 V GND RH T CO2 GND 1 2 3 4 5 6 22 21 23 B10 J18 S13 Electric panel V GND GND CO2 NC Tpassive Tpassive 1 2 3 4 5 6 7 22 21 23 B10 J18...

Страница 17: ...eck the operation conditions pressures ows and consumptions The coupling of characteristic curves of the fan and the room is very important so that the ows and pressures provided to the duct network a...

Страница 18: ...Belt tension After xing the pulleys on the same plane the belt tension is made by tightening the tensor screw Excessive tension on the belt can lead to premature wear on the assembly Insu cient belt t...

Страница 19: ...te pan is placed The drain piping must be slightly sloped to ease circulation towards the drain The original diameter of the piping must be respected No reduction can be made CONNECT SIPHON METTRE SIP...

Страница 20: ...th low outdoor temperatures condensation control or in heating mode with high outdoor temperatures evaporation control This aids the unit s operation in all the seasons In the case of EC electronic fa...

Страница 21: ...ction of the mixing box dampers optional mandatory for an outdoor temperature lower than 12 C WB Activation temperature 12 C WB Hot water coil circuit optional with anti freeze technology based on the...

Страница 22: ...unit Note Refer to the operation mode of the pump with the GREAT COLD option in the chapter Safety elements Coil lling The coil lling must be made with the bleeder valve open until water runs through...

Страница 23: ...the following table To attach these frames to the unit four supports are provided In the case of 2 frames screw each one of them to 2 supports with the 4 Allen M4 screws included in the kit The heigh...

Страница 24: ...op The stop drop can be installed in the indoor air coil and on the fresh air intake Indoor air coil available for models 415 to 960 and included in models 1100 and 1200 recommended in cases where a h...

Страница 25: ...rews supplied with the unit Profiles for the attachment of the module For the transport and lifting to the roof using a crane cloth slings with rings will be used with the appropriate resistance separ...

Страница 26: ...ame plate featuring the main gas characteristics as well as the 50EN EH unit serial number on which it is to be mounted Important All the necessary information about the installation commissioning and...

Страница 27: ...nection of the sensors supplied with the unit consult the chapter on Electrical connection That they are no cables close to heat sources Once the above veri cations have been carried out the control c...

Страница 28: ...s signi cant temperatures in the cooling circuit see attached table other aspects considered interesting such as alarms detected by the electronic control of the unit The recording of these parameters...

Страница 29: ...inal oil which has been stored in a hermetically sealed container until its time of use The oil type recommended for these units is Copeland 3MAF 32cST Danfoss POE 160SZ ICI Emkarate RL 32CF Mobil EAL...

Страница 30: ...opened Use safety gloves for this task Take care with the sharp parts of the coil V 220005 Centrifugal fan optional Verify that the turbine and the motor remain clean Foresee having a spare belt set...

Страница 31: ...lable tighten them until they are snug then tighten a further turn Solder the suction and discharge piping Connect the compressor in accordance with the wiring diagram Make vacuum and next reload the...

Страница 32: ...the module incorporate stainless steel quarter turn latches with 8 mm triangular inserts The procedure for extraction and cleaning of lters is equal to that described in the previous section Tabs in d...

Страница 33: ...c Timing of anti cycle short does not allow the starting d Open contact e Contactor coil burnt f Indoor klixon open a Check di erential fuses b Verify the safety chain of the electronic control c Ver...

Страница 34: ...ecovered for treatment Refrigerant Energy transfer uid depending on the installation water glycol water mix Compressor oil Important In order to recycle these units follow the stipulations of Directiv...

Страница 35: ......

Страница 36: ...tured for CARRIER in Spain Manufacturer reserves the right to change any product specifications without notice Printed in the European Union CARRIER participates in the ECP programme for RT Check ongo...

Отзывы: