14
Customer connection
8 - ELECTRICAL CONNECTION
In this case, it´s posible to install the TCO terminal on the electrical cabinet.
It’s necessary that the terminal uses the same power supply that the
control board.
Up to four RS485 ambient sensors can be connected in series on the
fi eld-bus of the control board.
8.5 Electric panel
All units include a fully wired electrical panel, with forced
ventilation.
The access door is insulated to prevent condensation. This door
has quarter-turn latches.
Note:
all models have a plug of 230 Vac in the main electric
panel.
These latches of stainless steel have triangular
insert 8 mm (supplied wrench). The closing is
done by rotating 90º (anti-clockwise): it brings
the latch to the locked position.
50EN/EH - 650, 720, 840, 960, 1100 and 1200
50EN/EH - 415, 420, 480, 485, 540 and 600
Position of the electric panel in the units
● Models 650 to 1200 include two fully wired electric panels:
- a main panel to which there is an electrical power supply,
- an auxiliary panel in which the optional elements of the
indoor circuit are connected.
Electric power supply inputs
Main panel
Auxiliary panel
Main panel
Electric power supply inputs
Optionally, these units can change the electronic control to
CARRIERrtc medium
(available for models 415 to 720). This
control is fi tted with the TCO terminal as standard, and the pGD1
terminal as an option. Consult the technical brochure.
Note:
for more detailed information on these controls, please
refer to their brochures.
TCO user terminal (optional):
This terminal can be installed on the electric panel, instead of
pGD1 terminal. In this case, the remote connection of the pGD1
terminal is posible.
No.
50EN/EH
415 to 1200
1
Main power
supply
400 III (±10%)
3 wires + ground
2
Remote connection of pGD1
terminal (by default installed
on the electrical cabinet)
telephone cable 6 wires standard
(RJ12 connector)
3
Connection of TCO user
terminal on the electrical
cabinet (optional)
2 wires for power supply 230V + 1
shielded cable for communication
type AGW20 / 22 (1 braided pair
+ dra shielding)
4
Remote off /on (optional)
2 wires
5
General fault signal (optional)
2 wires
6
Circulation pump signal for
HWC (antifreeze sec.) (opt.)
1 wire
7
Ambient
probe
NTC (std)
2 wires
RS485 (opt.)
5 wires
8
Air quality sensor (opt.)
3 wires