16
● It should never be mounted:
- On outside walls.
- In niches or behind curtains.
- Above or near heat sources or shelves.
- On walls covering heat sources such as a chimney.
- In the radiation range of heat sources and lighting bodies
e.g. spotlights.
- In areas exposed to direct solar radiation.
Duct-mounted
M16x1,5
Ø > 13mm
Ø > 0.51“
19mm
0.75“
90
±0.3
mm
3.54
±0.11
“
5mm
0.2“
60
±0.3
mm
2.36
±0.11
“
Ø > 16mm
Ø > 0.63“
6mm
0.24“
This version can be connected to the air duct in these two ways:
Electrical connection
This CO
2
probe (S13) is confi gured as analogue output 4…20
mA (0..2000 ppm), in the analogue input B10 of the control
board (connector J18).
Recommended cable section : 1,5 mm
2.
+V
GND
RH
T
CO2
GND
1
2
3
4
5
6
22
21
23
B10 (J18)
S13
Electric
panel
+V
GND
GND
CO2
NC
Tpassive
Tpassive
1
2
3
4
5
6
7
22
21
23
B10 (J18)
S13
Electric
panel
Environment:
Duct-mounted:
8 - ELECTRICAL CONNECTION
The position of the
terminal box depends
o n t h e a s s e m b l y
selected for the unit.
The installer only has to
insert the cable through
the feedthrough for
wiring it in the PVC box
located inside the unit,
next to the servomotor.
Then the electrical
connection of the probe
should be made.
Connection of the air quality probe
Installation in the environment
● This probe must be fi xed to the interior wall of the room to be
conditioned, at ca. 1.5 m height in the room and at least 50
cm from the next wall.