12.3 Electrical heaters

● The auxiliary electrical heaters are ready for operation in two 

power  stages.  This  heaters  are  managed  by  the  electronic 
control of the unit that can activate them in the following cases:

-  As support in HEATING mode, following the input of all the 

available compressors.

-  In HEATING mode, instead of compressors.

-  During the defrosting operation if selected as support.

-  As support in COOLING mode in accordance with the return 

and outlet temperatures.

● Assembly and connection inside the unit. The electrical heaters 

acquired with the unit will be incorporated to it modifying the 
electric panel in the factory, so that it is compatible with the 
electronic control.

● The electrical heaters requested for units already shipped will 

be sent in a kit, and the installer will need to assemble the 
necessary elements for the operation of the unit to assemble 
and  for  the  compliance  with  the  legal  regulations  that  are 
applied to the modifi ed unit in terms of safety.

Note:

 Consult the available capacities in the technical brochure.

Kit assembly:

When the frame with the electrical heaters is provided in a kit, 
follow the steps below for connecting it:

Step  1:  the  resistors  are  sent  divided  into  1,  2  or  4  frames, 
depending  on  the  required  power,  as  shown  in  the  following 
table:

To attach these frames to the unit, four supports are provided. 
In the case of 2 frames, screw each one of them to 2 supports 
with the 4 Allen M4 screws included in the kit.

The height of the frame on the support will depend on the position 
of the discharge, since it should never be behind the fan volute. 

For example, in the following diagram, the frame location will 
be valid for lower and side discharge.

Step 3: Take the hoses with the electric power supplies to the 
main electric panel of the unit. On the wiring diagram supplied 
with the unit an illustration is included with the implantation in 
the platen of all the components.

Important:

 The connection of the necessary elements for the 

adequacy to the operation of the unit must be performed by the 
installer.  The kit is supplied with the required electric material: 
thermistors, contactors, hoses, etc.

Output (kW)

27

36

45

54

72

90

Stages (kW)

9 + 18

18 + 18 18 + 27 27 + 27 36 + 36 45 + 45

No. of frames

1

2

2

2

4

4

Step 2: attach the supports with the frames linked inside the 
unit. To that extent, drills have been made in the unit to which 
the supports must be screwed.

Supports attached to the unit

Access panel

Supports 

attached to 

the unit

Safety thermistor 

location

Holes for screws M4 for 

attaching to the unit

Electric power 

supply outlet 

Holes for M4 

screws for 

attaching to the 

unit

Supports for 

attaching to the 

unit 

Holes for M4 

screws for 

attaching to the 

unit

12 - FACTORY OPTIONS AND ACCESSORIES

Содержание 50EH 1100

Страница 1: ...E N A N C E I N S T R U C T I O N S Translation of the original document 80049 12 2018 Packaged rooftop units and separated gas module option 50EN EH 415 1200 Nominal cooling capacity 92 8 287 0 kW No...

Страница 2: ...ntrifugal fans optional 17 9 4 Air ducts connections 18 10 CONDENSATE DRAIN 19 11 SAFETY ELEMENTS 20 12 FACTORY OPTIONS AND ACCESSORIES 22 12 1 Filters 22 12 2 Hot water coil 22 12 3 Electrical heater...

Страница 3: ...serial Nbr A o An Year Producto Product Produit Ref Produit Item Nbr Max Intensidad Intensit Current Kit Elec Tension Voltage Refrig KG F brica Factory Usine Co2 Teq Refrigerant NoBo Peso Poids Weight...

Страница 4: ...1 optional 2 optional Assembly Assemblies with mixing box and free cooling Standard assembly M0 assemblies Change of supply and or return air position in the indoor circuit ME assemblies Axial air ex...

Страница 5: ...stics or in the regulatory documentation provided with the product The compressor and line surfaces can reach temperatures above 100 C causing burns to the body In the same fashion under certain condi...

Страница 6: ...he weight and the gravity centre coordinates of each model stated in the following page The recommended length for the forks will be bigger than the unit width so that the entire weight bearing struct...

Страница 7: ...lies MRC1 assembly Centre of gravity Weight kg Centre of gravity Weight kg Centre of gravity Weight kg Centre of gravity Weight kg X mm Y mm Z mm X mm Y mm Z mm X mm Y mm Z mm X mm Y mm Z mm 415 1 566...

Страница 8: ...85 385 385 385 475 475 Gas burner module PCH065 414 414 414 PCH080 440 440 440 440 440 440 440 440 PCH105 468 468 468 468 468 468 468 468 PCH130 504 504 504 504 504 504 504 504 520 520 PCH160 555 555...

Страница 9: ...en installed These units can be installed on the oor or on a brick curb or steel pro le Based on the xing solution de ned in the installation project it will be necessary to plan the placement in the...

Страница 10: ...9 314 412 648 273 960 423 598 254 364 539 195 411 627 275 402 619 267 466 711 326 425 671 286 466 711 326 425 671 286 50EN EH MC0 Assembly MRC0 Assembly MC1 MWC1 Assemblies MRC1 Assembly R1 R2 R3 R4 R...

Страница 11: ...R8 1100 330 536 475 288 357 564 502 316 330 536 475 288 357 564 502 316 1200 349 567 481 292 375 592 507 318 349 567 481 292 375 592 507 318 50EN EH MC0 Assembly MRC0 Assembly R1 R2 R3 R4 R5 R6 R7 R8...

Страница 12: ...nd 960 50EN EH 1100 and 1200 LEGEND Indoor air coil Outdoor air coil Air supply Air return Condensates outlet 2 2 1 2000m m 2500mm 1500mm 1500mm 3 4 5 3500mm 2 2 1 1500mm 1500mm 3000m m 3 4 5 7 POSITI...

Страница 13: ...tures refer to the technical brochure and the name plate The distance between the unit and its power source The protection to be placed at the power source Neutral operating conditions The electrical...

Страница 14: ...the indoor circuit are connected Electric power supply inputs Main panel Auxiliary panel Main panel Electric power supply inputs Optionally these units can change the electronic control to CARRIERrtc...

Страница 15: ...the cover clockwise g 4 Reversing valve heat pump Outdoor fan Compressor Low pressure High pressure Outdoor temperature probe B2 B7 Press transducer in the outdoor coil cir 1 Discharge T klixon switch...

Страница 16: ...f the control board connector J18 Recommended cable section 1 5 mm2 V GND RH T CO2 GND 1 2 3 4 5 6 22 21 23 B10 J18 S13 Electric panel V GND GND CO2 NC Tpassive Tpassive 1 2 3 4 5 6 7 22 21 23 B10 J18...

Страница 17: ...eck the operation conditions pressures ows and consumptions The coupling of characteristic curves of the fan and the room is very important so that the ows and pressures provided to the duct network a...

Страница 18: ...Belt tension After xing the pulleys on the same plane the belt tension is made by tightening the tensor screw Excessive tension on the belt can lead to premature wear on the assembly Insu cient belt t...

Страница 19: ...te pan is placed The drain piping must be slightly sloped to ease circulation towards the drain The original diameter of the piping must be respected No reduction can be made CONNECT SIPHON METTRE SIP...

Страница 20: ...th low outdoor temperatures condensation control or in heating mode with high outdoor temperatures evaporation control This aids the unit s operation in all the seasons In the case of EC electronic fa...

Страница 21: ...ction of the mixing box dampers optional mandatory for an outdoor temperature lower than 12 C WB Activation temperature 12 C WB Hot water coil circuit optional with anti freeze technology based on the...

Страница 22: ...unit Note Refer to the operation mode of the pump with the GREAT COLD option in the chapter Safety elements Coil lling The coil lling must be made with the bleeder valve open until water runs through...

Страница 23: ...the following table To attach these frames to the unit four supports are provided In the case of 2 frames screw each one of them to 2 supports with the 4 Allen M4 screws included in the kit The heigh...

Страница 24: ...op The stop drop can be installed in the indoor air coil and on the fresh air intake Indoor air coil available for models 415 to 960 and included in models 1100 and 1200 recommended in cases where a h...

Страница 25: ...rews supplied with the unit Profiles for the attachment of the module For the transport and lifting to the roof using a crane cloth slings with rings will be used with the appropriate resistance separ...

Страница 26: ...ame plate featuring the main gas characteristics as well as the 50EN EH unit serial number on which it is to be mounted Important All the necessary information about the installation commissioning and...

Страница 27: ...nection of the sensors supplied with the unit consult the chapter on Electrical connection That they are no cables close to heat sources Once the above veri cations have been carried out the control c...

Страница 28: ...s signi cant temperatures in the cooling circuit see attached table other aspects considered interesting such as alarms detected by the electronic control of the unit The recording of these parameters...

Страница 29: ...inal oil which has been stored in a hermetically sealed container until its time of use The oil type recommended for these units is Copeland 3MAF 32cST Danfoss POE 160SZ ICI Emkarate RL 32CF Mobil EAL...

Страница 30: ...opened Use safety gloves for this task Take care with the sharp parts of the coil V 220005 Centrifugal fan optional Verify that the turbine and the motor remain clean Foresee having a spare belt set...

Страница 31: ...lable tighten them until they are snug then tighten a further turn Solder the suction and discharge piping Connect the compressor in accordance with the wiring diagram Make vacuum and next reload the...

Страница 32: ...the module incorporate stainless steel quarter turn latches with 8 mm triangular inserts The procedure for extraction and cleaning of lters is equal to that described in the previous section Tabs in d...

Страница 33: ...c Timing of anti cycle short does not allow the starting d Open contact e Contactor coil burnt f Indoor klixon open a Check di erential fuses b Verify the safety chain of the electronic control c Ver...

Страница 34: ...ecovered for treatment Refrigerant Energy transfer uid depending on the installation water glycol water mix Compressor oil Important In order to recycle these units follow the stipulations of Directiv...

Страница 35: ......

Страница 36: ...tured for CARRIER in Spain Manufacturer reserves the right to change any product specifications without notice Printed in the European Union CARRIER participates in the ECP programme for RT Check ongo...

Отзывы: