101
APPENDIX A — LOCAL DISPLAY AND CCN TABLES (cont)
MODE — TIME CLOCK
CCN ONLY TABLES
ITEM
EXPANSION
RANGE
UNITS
DEFAULT
CCN TABLE/
SUB-TABLE
CCN
POINT
TIME CLOCK
CONFIGURATION
TIME
Time of Day
TIME
Hour and Minute
xx.xx
hh.mm
(not in CCN table)
DATE
Current Date
MNTH
Month of Year
1 to 12 = January to December
(not in CCN table)
DOM
Day of Month
1 to 31
(not in CCN table)
YEAR
Year
xxxx
(not in CCN table)
DAY
Day of Week
1 to 7 = Monday to Sunday
(not in CCN table)
DST
Daylight Savings Config
BRODEFS
Daylight Savings Start:
STR.M
Start Month
1 to 12 = January to December
4
STARTM
STR.W
Start Week
1 to 5
1
STARTW
STR.D
Start Day
1 to 7
7
STARTD
M.ADD
Minutes to Add
0 to 90
60
MINADD
Daylight Savings Stop:
STP.M
Stop Month
1 to 12 = January to December
10
STOPM
STP.W
Stop Week
1 to 5
5
STOPW
STP.D
Stop Day
1 to 7
7
STOPD
M.SUB
Minutes to Subtract
0 to 90
60
MINSUB
SCH.L
Occupancy Schedule
(SCH.L = Display only)
PER.x
Occupancy Period x
OCC.x
Occupied From
00.00 to 23.59
hh.mm
00.00
UNC.x
Occupied To
00.00 to 23.59
hh.mm
00.00
MON.x
Monday in Period
Yes/No
No
TUE.x
Tuesday in Period
Yes/No
No
WED.x
Wednesday in Period
Yes/No
No
THU.x
Thursday in Period
Yes/No
No
FRI.x
Friday in Period
Yes/No
No
SAT.x
Saturday in Period
Yes/No
No
SUN.x
Sunday in Period
Yes/No
No
HOL.x
Holiday in Period
Yes/No
No
(repeat up to x=
8 Periods)
(OCCFECS = CCN only)
Occupancy Supervisory
OCCDEFCS
Period x DOW
(MTWTFSSH)
xxxxxxxx
00000000
DOWx
Occupied From
00.00 to 23.59
hh.mm
00.00
OCCTODx
Occupied To
00.00 to 23.59
hh.mm
00.00
UNOCTODx
(repeat up to x=
8 Periods)
HOL.L
Holiday Schedule
HOLIDAY
HOL.x
Holiday x
HOLDYxxS
MON.x
Holiday Start Month
1 to 12 = January to December
0
HOL_MON
DAY.x
Holiday Start Day
1 to 31
0
HOL_DAY
LEN.x
Holiday Duration (days)
1 to 99
0
HOL_LEN
(repeat up to x=
9 Holidays)
(repeat up to xx=
30 Holidays)
ITEM
EXPANSION
RANGE
UNITS
DEFAULT
CCN TABLE/
SUB-TABLE
CCN
POINT
(ALARMDEF = CCN only)
ALARMDEF
Alarm Routing Control
00000000 to 11111111
11000000
ALRM_CNT
Equipment Priority
0 to 7
5
EQP_TYPE
Comm Failure Retry Time
1 to 240
min
10
RETRY_TM
Re-Alarm Time
1 to 255
min
180
RE-ALARM
Alarm System Name
up to 8 alphanum
48_50_PG
ALRM_NAM
(CTLRID = CCN only)
CTLR-ID
Device Name:
48_50_PG
Description:
text string
Location:
text string
Software Part Number:
CESR131320-XX-XX
Model Number:
Serial Number:
Reference Number:
Содержание 48PG24
Страница 68: ...68 Fig 14 Low Voltage Control Schematic 48PG20 28 Units without Humidi MiZer System a48 7627...
Страница 69: ...69 Fig 15 Low Voltage Control Schematic 48PG20 28 Units with Humidi MiZer System a48 8227...
Страница 70: ...70 Fig 16 Low Voltage Control Schematic 50PG20 28 Units without Humidi MiZer System a48 7778...
Страница 71: ...71 Fig 17 Low Voltage Control Schematic 50PG20 28 Units with Humidi MiZer System a50 8101...
Страница 72: ...72 Fig 18 Power Schematic Units without Humidi MiZer System a48 7628...
Страница 73: ...73 Fig 19 Power Schematic Units with Humidi MiZer System a48 8228...
Страница 74: ...74 Fig 20 Component Arrangement Units without Humidi MiZer System a48 8229...
Страница 75: ...75 Fig 21 Component Arrangement Units with Humidi MiZer System a48 8230...
Страница 105: ......