39
IAQ Switch —
For units with the economizer option or
accessory and the ECB control board, the IAQ switch input
is provided on the field connection terminal board (TB2). The
IAQ Switch Input configuration,
Configuration
→
AIR.Q
→
II.CF,
identifies the normally open or normally closed status
of this input when the indoor air quality value is low (good)
and also selects the unit response to this input.
6 = 24 VAC source for dry contact
7 = 24 VAC signal input
NOTE: An IAQ switch cannot be used if an enthalpy switch is
already on this input.
IAQ Sensor —
For units with the economizer option or
accessory and the ECB control board, the IAQ sensor input
is provided on the field connection terminal board (TB2). The
IAQ Analog Input configuration,
Configuration
→
AIR.Q
→
IA.CF
selects the unit response to this input. Default conver-
sion to 0 to 2000 ppm can be changed in the configurations.
2 = 4-20 mA + signal
3 = 4-20 mA – common
OAQ Sensor —
For units with the economizer option or
accessory and the ECB control board, the OAQ sensor input is
provided on the field connection terminal board (TB2). The
OAQ Analog Input configuration,
Configuration
→
AIR.Q
→
OA.CF
selects the unit response to this input. Default con-
version to 0 to 2000 ppm can be changed in the configurations.
3 = 4-20 mA – common
4 = 4-20 mA + signal
NOTE: An OAQ sensor cannot be used if a humidity sensor is
used.
CONTROLS OPERATION
Display Configuration —
The
Configuration
→
DISP
submenu is used to configure the local display settings.
Metric Display (
METR
) — This variable is used to change
the display from English units to Metric units.
Language Selection (
LANG
) — This variable is used to
change the language of the
Comfort
Link display. At this time,
only English is available.
Password Enable (
PROT
) — This variable enables or dis-
ables the use of a password. The password is used to restrict
use of the control to change configurations.
Service Password (
PSWD
) — This variable is the 4-digit
numeric password that is required if enabled.
Test Display LEDs (
TEST
) — This is used to test the opera-
tion of the
Comfort
Link display.
Modes —
The
Comfort
Link controls operate under a hierar-
chy of command structure as defined by four main elements:
the System Mode, the HVAC Mode, the Occupied status, and
the Unit Control Type.
The System Mode is the top level that defines three main
states of the control system: Disabled, Enabled, or Test.
The HVAC Mode is the next level that defines four main
states of functional operation: Disabled, Fan Only, Cool, and
Heat.
The Occupied status affects set points for cooling and
heating in Space Sensor control mode and operation of the
economizer for indoor air quality ventilation and free cooling.
The Unit Control Type (
Configuration
→
UNIT
→
U.CTL
)
defines if temperature control is based on thermostat inputs or
space temperature sensor input.
The general operating mode of the control and the status of
some related operation lockouts are located on the display at
two locations:
Run Status
→
MODE
and
Operating Modes
→
MODE
.
System Mode (
SYS
) — In Run Status, the current system
mode is displayed as a number with expandable text. In
Operating Modes, system mode is displayed as expandable
text.
HVAC Mode (
HVAC
) — In Run Status, the current allowed
HVAC mode is displayed as a number with expandable text. In
Operating Modes, HVAC mode is displayed as expandable
text.
NOTE: Optional Humidi-MiZer™ operation is included
within Cooling mode.
Currently Occupied (
OCC
) — Displays the current state of
assumed space occupancy based on unit configuration and
inputs.
Timed Override in Effect (
T.OVR
) — Displays if the state of
occupancy is currently occupied due to an override.
Linkage Active (
LINK
) — Displays if a linkage master in a
zoning system has established “linkage” with this unit.
Circuit OAT Lockout (
C.LOC
) — Displays if one or more
refrigerant circuits operation is prevented due to outdoor
temperature limit lockout.
Heat OAT Lockout (
H.LOC
) — Displays if heating operation
is prevented due to outdoor temperature limit lockout.
Econo Cool OAT Lockout (
E.LOC
) — Displays if econo-
mizer operation for cooling is prevented due to outdoor
temperature limit lockout.
Unit Configuration —
Many configurations that indi-
cate what factory options and/or field accessories are installed
and other common operation variables are included in Unit
Configuration (
Configuration
→
UNIT
). Configuration will be
done at the factory for any factory-installed option (FIOP).
Start-Up Delay (
S.DLY
) — This configuration sets the con-
trol start-up delay after the power is interrupted. This can be
used to stagger the start-up of multiple units.
Unit Control Type (
U.CTL
) — This configuration defines if
temperature control is based on thermostat inputs or space
temperature sensor input.
•
U.CTL = 2
(Thermostat) – The unit determines cooling
and heating demand by the state of G, Y1, Y2, W1, and
W2 inputs from a space thermostat. This value is the
factory default.
•
U.CTL = 3
(Space Sensor) – The unit determines cooling
and heating demand based on the space temperature and
the appropriate set point.
Thermostat Control Type (
T.CTL
) — This configuration ap-
plies only if Unit Control Type is Thermostat (
Configuration
→
Unit
→
U.CTL = 2
). The value determines alternative cool-
ing and Humidi-MiZer circuit staging. See the Cooling and
Humidi-MiZer sections for more information. The factory
default value is
T.CTL
= 0
(Adaptive).
Fan On When Occupied (
OC.FN
) — This configuration ap-
plies only if Unit Control Type is Space Sensor (
Configuration
→
Unit
→
U.CTL = 3
). A YES value will operate the indoor fan
whenever the unit is in the Occupied mode. A NO value will
operate the indoor fan only when heating or cooling is neces-
sary. The factory default value is YES.
NUMBER
RUN STATUS
EXPANDED TEXT
OPERATING MODES
EXPANDED TEXT
1
Disabled
Unit Operation Disabled
2
Enabled
Unit Operation Enabled
3
Test
Service Test Enabled
NUMBER
RUN STATUS
EXPANDED TEXT
OPERATING MODES
EXPANDED TEXT
1
Disabled
HVAC Operation Disabled
2
Fan Only
Ventilation (Fan Only)
3
Cool
Cooling or Free Cooling
4
Heat
Heating
Содержание 48PG24
Страница 68: ...68 Fig 14 Low Voltage Control Schematic 48PG20 28 Units without Humidi MiZer System a48 7627...
Страница 69: ...69 Fig 15 Low Voltage Control Schematic 48PG20 28 Units with Humidi MiZer System a48 8227...
Страница 70: ...70 Fig 16 Low Voltage Control Schematic 50PG20 28 Units without Humidi MiZer System a48 7778...
Страница 71: ...71 Fig 17 Low Voltage Control Schematic 50PG20 28 Units with Humidi MiZer System a50 8101...
Страница 72: ...72 Fig 18 Power Schematic Units without Humidi MiZer System a48 7628...
Страница 73: ...73 Fig 19 Power Schematic Units with Humidi MiZer System a48 8228...
Страница 74: ...74 Fig 20 Component Arrangement Units without Humidi MiZer System a48 8229...
Страница 75: ...75 Fig 21 Component Arrangement Units with Humidi MiZer System a48 8230...
Страница 105: ......