Table 43 — ComfortLink™ Alarm Codes
LEGEND
ALARM OR
ALERT
NUMBER
DESCRIPTION
ACTION TAKEN
BY CONTROL
RESET
METHOD
PROBABLE CAUSE
T051
Compressor A1 Safety Trip
Add Strike for Circuit A
Automatic
High-pressure switch open. Compressor internal protection open. Wiring
error
Compressor A1 Current Detected After Turnoff
Turn off all compressors
Automatic
Welded contactor
T052
Compressor A2 Safety Trip
Add Strike for Circuit A
Automatic
High pressure switch open. Compressor internal protection open.
Wiring error.
Compressor A2 Current Detect After Turnoff
Turn off all compressors
Automatic
Welded contactor
T055
Compressor B1 Safety Trip
Add Strike for Circuit B
Automatic
High-pressure switch open. Compressor internal protection open. Wiring
error
Compressor B1 Current Detected After Turnoff
Turn off all compressors
Automatic
Welded contactor
T059
Compressor C1 Safety Trip
Add Strike for Circuit C
Automatic
High-pressure switch open. Compressor internal protection open. Wiring
error
Compressor C1 Current Detected After Turnoff
Turn off all compressors
Automatic
Welded contactor
T064
Circuit A Saturated Condensing Temp Thermistor
Failure
Use OAT to control Outdoor fans
Automatic
Faulty, shorted, or open thermistor caused by wiring error or loose
connection.
T065
Circuit B Saturated Condensing Temp Thermistor
Failure
Use OAT to control Outdoor fans
Automatic
Faulty, shorted, or open thermistor caused by wiring error or loose
connection.
T073
Outdoor Air Temperature Thermistor Failure
No cooling with economizer
Automatic
Faulty, shorted, or open thermistor caused by wiring error or loose
connection.
T074
Space Temperature Thermistor Failure
If U.CTL = 3, then no
heating or cooling
Automatic
Faulty, shorted, or open thermistor caused by wiring error or loose
connection.
T075
Supply Air Temperature Thermistor Failure
No cooling with economizer and
No adaptive compressor staging
Automatic
Faulty, shorted, or open thermistor caused by wiring error or loose
connection.
T076
Return Air Thermistor Failure
If RAT.S = Yes, then
no return air display
Automatic
Faulty, shorted, or open thermistor caused by wiring error or loose
connection.
T077
Space Relative Humidity Sensor Failure
If RH.S = Yes, then no
indoor humidity control
Automatic
Faulty sensor or wiring error
T080
Circuit C Saturated Condensing Temp Thermistor
Failure
Use OAT to control Outdoor fans
Automatic
Faulty, shorted, or open thermistor caused by wiring error or loose
connection.
T092
Circuit A Suction Pressure Transducer Failure
Shutdown Circuit A
Manual
Faulty transducer, faulty 5-V power supply, or loose connection
T093
Circuit B Suction Pressure Transducer Failure
Shutdown Circuit B
Manual
Faulty transducer, faulty 5-V power supply, or loose connection
T101
Circuit C Suction Pressure Transducer Failure
Shutdown Circuit C
Manual
Faulty transducer, faulty 5-V power supply, or loose connection
T102
Compressor A1 Current Sensor Failure
If CS.A1 = Enable, then no
T051 current alarm
Automatic
Faulty current sensor caused by wiring error or loose connection
Compressor A2 Current Sensor Failure
If CS.A2 = Enable, then no
T052 current alarm
Automatic
Faulty current sensor caused by wiring error or loose connection
T103
Compressor B1 Current Sensor Failure
If CS.B1 = Enable, then no
T055 current alarm
Automatic
Faulty current sensor caused by wiring error or loose connection
T104
Compressor C1 Current Sensor Failure
If CS.C1 = Enable, then no
T059 current alarm
Automatic
Faulty current sensor caused by wiring error or loose connection
T110
Circuit A Loss of Charge
Shutdown Circuit A
Manual
Low refrigerant or faulty suction pressure transducer
T111
Circuit B Loss of Charge
Shutdown Circuit B
Manual
Low refrigerant or faulty suction pressure transducer
T126
Circuit A High Refrigerant Pressure
Shutdown Circuit A
Automatic
An overcharged system, high outdoor ambient temperature coupled with
dirty outdoor coil, plugged filter drier, or a faulty high-pressure switch.
T127
Circuit B High Refrigerant Pressure
Shutdown Circuit B
Automatic
An overcharged system, high outdoor ambient temperature coupled with
dirty outdoor coil, plugged filter drier, or a faulty high-pressure switch.
T133
Circuit A Low Refrigerant Pressure
Add Strike for Circuit A
Automatic
Low refrigerant charge, dirty filters, evaporator fan turning backwards,
loose or broken fan belt, plugged filter drier, faulty transducer, exces-
sively cold return air, or stuck open economizer when the ambient tem-
perature is low.
T134
Circuit B Low Refrigerant Pressure
Add Strike for Circuit B
Automatic
Low refrigerant charge, dirty filters, evaporator fan turning backwards,
loose or broken fan belt, plugged filter drier, faulty transducer, exces-
sively cold return air, or stuck open economizer when the ambient tem-
perature is low.
T140
Circuit C Loss of Charge
Shutdown Circuit C
Manual
Low refrigerant or faulty suction pressure transducer
T141
Circuit C Low Refrigerant Pressure
Add Strike for Circuit C
Automatic
Low refrigerant charge, dirty filters, evaporator fan turning backwards,
loose or broken fan belt, plugged filter drier, faulty transducer, exces-
sively cold return air, or stuck open economizer when the ambient tem-
perature is low.
T142
Circuit C High Refrigerant Pressure
Shutdown Circuit C
Automatic
An overcharged system, high outdoor ambient temperature coupled with
dirty outdoor coil, plugged filter drier, or a faulty high-pressure switch.
T143
Circuit A Failure To Pressurize
Add Strike for Circuit A
Automatic
Wiring causing reverse rotation or faulty compressor
T144
Circuit B Failure To Pressurize
Add Strike for Circuit B
Automatic
Wiring causing reverse rotation or faulty compressor
T145
Circuit C Failure To Pressurize
Add Strike for Circuit C
Automatic
Wiring causing reverse rotation or faulty compressor
T153
Real Timeclock Hardware Failure
No time and date
schedule operation
Automatic
No time/date configured, software failure, or MBB failure
A154
Serial EEPROM Hardware Failure
Unit Shutdown
Automatic
Software failure or MBB failure
T155
Serial EEPROM Storage Failure Error
Unit operation errors
Automatic
Software failure or MBB failure
A156
Critical Serial EEPROM Storage Fail Error
Unit Shutdown
Automatic
Software failure or MBB failure
A157
A/D Hardware Failure
Unit Shutdown
Automatic
Software failure or MBB failure
A163
Circuit A Down Due to Failure
Shutdown Circuit A
Manual
Circuit has 3 strikes or has been locked out by another alarm
A164
Circuit B Down Due to Failure
Shutdown Circuit B
Manual
Circuit has 3 strikes or has been locked out by another alarm
A165
Circuit C Down Due to Failure
Shutdown Circuit C
Manual
Circuit has 3 strikes or has been locked out by another alarm
T179
Loss of communication with the Economizer
Control Board
No economizer operation
Automatic
Communication wiring problem with ECB or faulty MBB or ECB
T180
Loss of communication with the Economizer
Actuator
No economizer operation
Automatic
Communication wiring problem with actuator.
A404
Fire Shutdown
Unit Shutdown
Automatic
Smoke detected by smoke detector
T408
Dirty Filter
—
Automatic
Dirty Filter
T409
Fan Status Switch ON, Contactor OFF
If IDF.F = Yes,
then Unit Shutdown
If IDF.F = YES,
then Manual,
otherwise
automatic
Bad Fan Status Switch.
Configuration incorrect.
Fan Status Switch OFF, Contactor ON
If IDF.F = Yes,
then Unit Shutdown
If IDF.F = YES,
then Manual,
otherwise
automatic
Tripped Circuit Breaker.
Broken belt.
Bad indoor fan motor.
Configuration incorrect. Bad fan status switch.
ECB — Economizer Control Board
MBB —
Main Base Board
IGC
— Integrated Gas Controller
OAT
—
Outdoor-Air Thermistor
Содержание 48PG24
Страница 68: ...68 Fig 14 Low Voltage Control Schematic 48PG20 28 Units without Humidi MiZer System a48 7627...
Страница 69: ...69 Fig 15 Low Voltage Control Schematic 48PG20 28 Units with Humidi MiZer System a48 8227...
Страница 70: ...70 Fig 16 Low Voltage Control Schematic 50PG20 28 Units without Humidi MiZer System a48 7778...
Страница 71: ...71 Fig 17 Low Voltage Control Schematic 50PG20 28 Units with Humidi MiZer System a50 8101...
Страница 72: ...72 Fig 18 Power Schematic Units without Humidi MiZer System a48 7628...
Страница 73: ...73 Fig 19 Power Schematic Units with Humidi MiZer System a48 8228...
Страница 74: ...74 Fig 20 Component Arrangement Units without Humidi MiZer System a48 8229...
Страница 75: ...75 Fig 21 Component Arrangement Units with Humidi MiZer System a48 8230...
Страница 105: ......