97
APPENDIX A — LOCAL DISPLAY AND CCN TABLES (cont)
MODE — CONFIGURATION
LEGEND
FIOP — Factory-Installed Option
ITEM
EXPANSION
RANGE
UNITS
DEFAULT
CCN TABLE/SUB-TABLE
CCN POINT
PAGE NO.
CONFIGURATION
SERVICE CONFIGURATION
DISP
Display Configuration
DISPLAY
METR
Metric Display
On/Off
Off
DISPUNIT
39
LANG
Language Selection
0=English
1=Spanish
2=French
3=Portuguese
0
LANGUAGE
39
PROT
Password Enable
Enable/Disable
Enable
PASS_EBL
39
PSWD
Service Password
0000 to 9999
1111
PASSWORD
39
TEST
Test Display LEDs
On/Off
Off
DISPTEST
39
UNIT
Unit Configuration
UNIT
S.DLY
Start Up Delay
0 to 600
sec
30
STARTDLY
39
U.CTL
Unit Control Type
1=Auto Select
2=Thermostat
3=Space Sensor
2
CTL_TYPE
35, 39, 41,
43, 47
T.CTL
Thermostat Control Type
0=Adaptive
1=1 Stage Y1
2=2 Stage Y1
0
STATTYPE
38, 39, 41
OC.FN
Fan On When Occupied
Yes/No
Yes
OCC_FAN
39, 41, 43
IDF.F
Shut Down on IDF Failure
Yes/No
Yes
FATALFAN
40, 56
EC.EN
Economizer Installed
Yes/No
No: no FIOP
Yes: FIOP
ECONO
40, 41
FN.SW
Fan Status Switch
0=No Switch
1=Normally Open
2=Normally Closed
0: no FIOP
1: FIOP
FANSTCFG
40, 56, 82
FL.SW
Filter Status Switch
0=No Switch
1=Normally Open
2=Normally Closed
0: no FIOP
1: FIOP
FILSTCFG
40, 82
FS.SW
Fire Shutdown Switch
0=No Switch
1=Normally Open
2=Normally Closed
0: no FIOP
1: FIOP
SHTDNCFG
38, 40
RM.SW
Remote Occupancy Switch
0=No Switch
1=Normally Open
2=Normally Closed
0
REMOCCFG
38, 40
SAT.T
SAT Settling Time
10 to 900
sec
240
SAT_SET
40, 42
SAT.H
SAT Heat Mode Sensing
Enable/Disable
Disable
SAT_HEAT
40, 44
RAT.S
RAT Sensor On SPTO Input
Yes/No
No
RAT_SPTO
40, 82
RH.S
RH Sensor ON OAQ Input
Yes/No
No
RH_OAQ
35, 38, 40,
47, 82
RH.SW
Space Humidity Switch
0=No Switch
1=Normal Open
2=Normal Closed
0: no Humidi-MiZer FIOP
1: Humidi-MiZer FIOP
HUMSTCFG
35, 38, 40,
47, 82
TCS.C
Temp Cmp Strt Cool Factr
0 to 60
mins
0
TCSTCOOL
40, 51
TCS.H
Temp Cmp Strt Heat Factr
0 to 60
mins
0
TCSTHEAT
40, 41
COOL
Cooling Configuration
COOL_CFG
N.CIR
Number of Circuits
1 to 3
2
NUM_CIRC
56
N.A
Compressors on Circuit A
1 to 2
1
A_COMPS
56
MRT.C
Compressor Min On Time
120 to 999
sec
180
MIN_ON
41, 42
MOT.C
Compressor Min Off Time
300 to 999
sec
300
MIN_OFF
41, 42
RST.C
Runtime to Reset Strikes
120 to 999
sec
300
MIN_ON_S
C.DEC
Cool Stage Decrease Rate
120 to 999
sec
300
STAGEDEC
41, 42
C.INC
Cool Stage Increase Rate
120 to 999
sec
450
STAGEINC
41, 42
FOD.C
Fan-off Delay, Mech Cool
0 to 600
sec
60
COOL_FOD
CA.LO
Circuit A Lockout Temp
0 to 100
dF
0
OATLCMPA
41
CB.LO
Circuit B Lockout Temp
0 to 100
dF
0: no Humidi-MiZer FIOP
Humidi-MiZer FIOP:
0
OATLCMPB
41
CC.LO
Circuit C Lockout Temp
0 to 100
dF
0
OATLCMPC
41
ALM.N
Alert Each Strike
Yes/No
Yes
ALM_NOW
52
SAT
Supply Air Temperature
SA.PD
SAT Cool Demand (+) Level
0.5 to 10
^F
1
SAT_POS
SA.ND
SAT Cool Demand (–) Level
–10 to –0.5
^F
–1
SAT_NEG
SAT.U
Minimum SAT Upper Level
35.0 to 65.0
dF
58
SATMIN_H
SAT.L
Minimum SAT Lower Level
35.0 to 65.0
dF
48
SATMIN_L
SPT
Space Temperature
CL.PD
SPT Cool Demand (+) Level
0.5 to 5
^F
1
DEM_POS
CL.ND
SPT Cool Demand (–) Level
–5 to –0.5
^F
–1
DEM_NEG
C.LAG
Cool Thermal Lag Factor
0 to 5
min
1
COOL_LAG
CIR.A
Circuit A
42
CS.A1
A1 Current Sensing
Enable/Disable
Disable (1-phase)
Enable (3-phase)
A1_SENSE
55
CS.A2
A2 Current Sensing
Enable/Disable
Disable
A2_SENSE
A1.FN
A Circuit Level 1 Fans
0 to 7
1: No Humidi-MiZer FIOP
(20, 24)
5: No Humidi-MiZer FIOP
(28)
1: Humidi-MiZer FIOP
CIR_A_1
A2.FN
A Circuit Level 2 Fans
0 to 7
No Humidi-MiZer FIOP
3 (20)
2 (24, 28)
Humidi-MiZer FIOP
3 (20)
2 (24, 28)
CIR_A_2
A3.FN
A Circuit Level 3 Fans
0 to 7
No Humidi-MiZer FIOP
3 (20, 24)
7 (28)
Humidi-MiZer FIOP
3
CIR_A_3
Содержание 48PG24
Страница 68: ...68 Fig 14 Low Voltage Control Schematic 48PG20 28 Units without Humidi MiZer System a48 7627...
Страница 69: ...69 Fig 15 Low Voltage Control Schematic 48PG20 28 Units with Humidi MiZer System a48 8227...
Страница 70: ...70 Fig 16 Low Voltage Control Schematic 50PG20 28 Units without Humidi MiZer System a48 7778...
Страница 71: ...71 Fig 17 Low Voltage Control Schematic 50PG20 28 Units with Humidi MiZer System a50 8101...
Страница 72: ...72 Fig 18 Power Schematic Units without Humidi MiZer System a48 7628...
Страница 73: ...73 Fig 19 Power Schematic Units with Humidi MiZer System a48 8228...
Страница 74: ...74 Fig 20 Component Arrangement Units without Humidi MiZer System a48 8229...
Страница 75: ...75 Fig 21 Component Arrangement Units with Humidi MiZer System a48 8230...
Страница 105: ......