Operating sequence for 48HJ004-007 units

Cooling, units without economizer — 

When thermo-

stat calls for cooling, terminals G and Y1 and the compres-
sor contactor (C) are energized. The indoor (evaporator)
fan motor (IFM), compressor, and outdoor (condenser) fan
motor (OFM) start. The OFM runs continuously while the
unit is in cooling. When the thermostat is satisfied, C is
deenergized and the compressor and OFM shut off. After a
30-second delay, the IFM shuts off. If the thermostat fan
selector switch is in the ON position, the evaporator motor
will run continuously.

Cooling, units with Durablade economizer — 

When

the outdoor-air temperature is above the outdoor-air tem-
perature (OAT) setting and the room thermostat calls for
cooling, the compressor contactor is energized to start the
compressor and outdoor (condenser) fan motor (OFM).
The indoor (evaporator) fan motor (IFM) is energized and
the economizer damper moves to the minimum position.
After the thermostat is satisfied, the damper moves to the
fully closed position when IFM is deenergized.

When the outdoor-air temperature is below the OAT set-

ting and the thermostat calls for Y1 and G, the economizer
damper moves to the minimum position when the evapo-
rator fan starts. The first stage of cooling is provided by the
economizer. If the supply-air temperature is above 57 F, a
switch on the supply-air thermostat is closed between the
T2 terminal and the 24 vac terminal. This causes the
damper to continue to modulate open until the supply-air
temperature falls below 55 F or the damper reaches the
fully-open position.

When the supply-air temperature is between 55 F and

52 F, the supply-air thermostat has open switches between
the T2 and 24 vac terminals and between the T1 and
24 vac terminals. This causes the economizer damper to
remain in an intermediate open position.

If the supply-air temperature falls below 52 F, a switch

on the supply-air thermostat is closed between the T1 ter-
minal and the 24 vac terminal. This causes the damper to
modulate closed until the supply-air temperature rises
above 55 F or the damper reaches the minimum position.

When the supply-air temperature is between 55 F and

57 F, the supply-air thermostat has open switches between
the T2 and 24 vac terminals. This causes the economizer
damper to remain in an intermediate open position.

If the outdoor air alone cannot satisfy the cooling re-

quirements of the conditioned space, economizer cooling
is integrated with mechanical cooling, providing second
stage cooling. The compressor and condenser fan will be
energized and the position of the economizer damper will
be determined by the supply-air temperature.

When the second stage of cooling is satisfied, the com-

pressor and condenser-fan motor will be deenergized. The
damper position will be determined by the supply-air
temperature.

When the first stage of cooling is satisfied, the IFM shuts

off after a 30-second delay. The damper then moves to
fully closed position.

Cooling, units with EconoMi$er

When the outdoor-air temperature (OAT) is above the
ECON SP set point and the room thermostat calls for
Stage 1 cooling (R to G + Y1), the indoor (evaporator) fan
motor (IFM) is energized and the EconoMi$er damper
modulates to minimum position. The compressor contac-
tor is energized to start the compressor and outdoor (con-
denser) fan motor (OFM). After the thermostat is satisfied,
the damper modulates to the fully closed position when the
IFM is deenergized.

When the OAT is below the ECON SP setting and the

room thermostat calls for Stage 1 cooling (R to G + Y1),
the EconoMi$er modulates to the minimum position when
the IFM is energized. The EconoMi$er provides Stage 1 of
cooling by modulating the return and outdoor-air dampers
to maintain a 55 F supply air set point. If the supply-air
temperature (SAT) is greater than 57 F, the EconoMi$er
modulates open, allowing a greater amount of outdoor air
to enter the unit. If the SAT drops below 53 F, the outdoor
air damper modulates closed to reduce the amount of out-
door air. When the SAT is between 53 and 57 F, the
EconoMi$er maintains its position.

If outdoor-air alone cannot satisfy the cooling require-

ments of the conditioned space, and the OAT is above the
MECH CLG LOCKOUT set point, the EconoMi$er inte-
grates free cooling with mechanical cooling. This is accom-
plished by the strategies below.

NOTE: Compressor has a two minute Minimum On, Mini-
mum Off, and Interstage delay timer.

1. If Y1 is energized, and the room thermostat calls for

Y2 (2-stage) thermostat), the compressor and OFM
are energized. The position of the EconoMi$er
damper is maintained at its current value.

2. If Y1 is energized for more than 20 minutes, and Y2

is not energized (whether or not a 2-stage thermostat
is used), the compressor and OFM are energized. The
position of the EconoMi$er damper is maintained at
its current value.

3. If Y1 is energized, and the compressor is already

energized (see Step 2) and the room thermostat calls
for Y2, the compressor continues to operate.

4. If the compressor is energized and the thermostat is

satisfied, the compressor, OFM, and IFM are deener-
gized and the EconoMi$er modulates closed.

When the OAT is below the MECH CLG LOCKOUT set

point, the compressors remain off.

Heating, units without economizer — 

When the ther-

mostat calls for heating, terminal W1 is energized. The
induced-draft motor is energized and the burner ignition
sequence begins. The indoor (evaporator) fan motor (IFM)
is energized 45 seconds after a flame is ignited. On units
equipped for two stages of heat, when additional heat is
needed, W2 is energized and the high-fire solenoid on the
main gas valve (MGV) is energized. When the thermostat is
satisfied and W1 is deenergized, the IFM stops after a
45-second time-off delay.

Controls

Содержание 48HJD005

Страница 1: ...Standard belt driven evaporator fan motors on all units Ease of maintenance achieved by self diagnostics on the Integrated Gas Controller IGC optional direct digital controls standard size filters to...

Страница 2: ...s of charge switch high pressure switch freeze protection thermostat internal compressor overload exclusive Carrier Cycle LOC circuit board that provides anti compressor cycling refrigerant filter dri...

Страница 3: ...izing roof penetrations to prevent water leaks Power gas and control connections are made on the same side of the unit to simplify installation The non corrosive sloped con densate drain pan is made i...

Страница 4: ...rigeration system 5 Carrier s exclusive Acutrol meter ing device which precisely controls refrigerant flow preventing slug ging and floodback while maintain ing optimum unit performance by metering th...

Страница 5: ...air conditioning systems that bring in minimal fresh air In 1989 IAQ concerns caused ASHRAE to recommend increased ventilation for all public buildings Sim ply introducing fresh air into a building h...

Страница 6: ...v circuit breaker on 48HJ008 014 units allows room for error without replacing transform ers or fuses Single side utility connections provide easy access to perform any necessary service Color coded...

Страница 7: ...tuh First Stage Second Stage OUTPUT CAPACITY Btuh TEMPERATURE RISE F AFUE STEADY STATE EFFICIENCY CALIFORNIA SEASONAL EFFICIENCY Single Phase Units First Stage Second Stage 3 Phase Units First Stage S...

Страница 8: ...1 17 1 17 1 17 1 17 Total Face Area sq ft 3 9 3 9 3 9 3 9 EVAPORATOR FAN Centrifugal Type Belt Drive Quantity Size in 1 10 x 10 1 10 x 10 1 10 x 10 1 10 x 10 Nominal Cfm 1200 1600 2000 2400 Maximum C...

Страница 9: ...Thermostat Heat Anticipator Setting amps 208 230 460 v First Stage 14 14 14 14 Second Stage 14 14 14 14 Gas Input Btuh First Stage 50 000 82 000 50 000 82 000 120 000 50 000 82 000 120 000 50 000 82 0...

Страница 10: ...midification Package Rows Fins in 1 17 1 17 1 17 1 17 Total Face Area sq ft 6 3 6 3 8 4 8 4 EVAPORATOR FAN Centrifugal Size in 15 x 15 15 x 15 15 x 15 15 x 15 Type Drive Belt Belt Belt Belt Nominal Cf...

Страница 11: ...00 90 000 120 000 180 000 120 000 180 000 200 000 180 000 200 000 Stage 2 125 000 180 000 224 000 125 000 180 000 224 000 180 000 224 000 250 000 224 000 250 000 Efficiency Steady State 82 82 82 82 82...

Страница 12: ...cusensor II Enthalpy Control X Accusensor III Differential Enthalpy Sensor X Liquid Propane Conversion Kit X Condenser Coil Hail Guard X NOx Reduction Kit X Flue Discharge Deflector X Coil Guard Grill...

Страница 13: ...estarting for at least 5 minutes after a shutdown Field installed accessory pre vents short cycling of compressor if thermostat is rapidly changed Time Guard II device mounts in the control compartmen...

Страница 14: ...TAT ACCUSENSOR II ENTHALPY CONTROL Field installed wall mounted humidistat is used to control operation of the MoistureMiser dehumidification package The humid istat controls the occupied space humidi...

Страница 15: ...coil located on the leaving air side of the evaporator coil The location of this coil in the indoor air stream enhances the latent capacity of the 48HJ units by as much as 40 The MoistureMiser package...

Страница 16: ...ermits quick and simple compressor access COMPRESSOR HINGED PANEL OPTION 48HJ008 014 UNITS SHOWN EVAPORATOR FAN HINGED PANEL OPTION This is included as a factory installed option It per mits quick and...

Страница 17: ...using accessory flue discharge deflector b Bottom of unit to combustible surfaces when not using curb 1 inch Bottom of base rail to combustible surfaces when not using curb 0 inches c Condenser coil...

Страница 18: ...urb 0 inches c Condenser coil for proper airflow 36 in one side 12 in the other The side getting the greater clearance is optional d Overhead 60 in to assure proper condenser fan operation e Between u...

Страница 19: ...TMPWR002A00 1 2 NPT CRBTMPWR003A00 ROOF CURBS NOTES 1 Roof curb accessory is shipped unassembled 2 Insulated panels 3 Dimensions in are in millimeters 4 Roof curb galvanized steel 5 Attach ductwork to...

Страница 20: ...PT CRBTMPWR001A00 3 4 NPT 11 4 NPT 1 2 NPT CRBTMPWR002A00 3 4 NPT CRBTMPWR004A00 ROOF CURBS NOTES 1 Roof curb accessory is shipped unassembled 2 Insulated panels 3 Dimensions in are in millimeters 4 R...

Страница 21: ...he simplified method below calculate the approximate mixed air temperature for the SRT evaporator coil Using the outdoor air entering cfm the room cfm and the room exhaust airflow with their respectiv...

Страница 22: ...tep II 4 851 Btuh Optional Energy Recycler Supply Fan Motor Heat none Net Sensible Capacity 48 659 Btuh IX Determine the operating watts of the unit a Cooling with Energy Recycler in operation Rooftop...

Страница 23: ...62AQ is sized for a minimum of 33 larger than the overcurrent protection device value i e 60 amps x 0 33 20 amps no further subfusing would be required If the overcurrent protection device is greater...

Страница 24: ...Temp F Air Ent Condenser Edb Temp F Air Entering Evaporator Cfm BF 1200 0 17 1450 0 19 1600 0 21 2000 0 24 Temp F Air Entering Evaporator Ewb F 72 67 62 72 67 62 72 67 62 72 67 62 75 TC 54 0 50 7 44...

Страница 25: ...62 2 56 8 53 5 SHC 30 0 37 2 43 1 31 7 40 4 46 2 33 3 43 4 48 9 36 4 48 9 53 4 kW 6 27 6 19 6 09 6 28 6 21 6 13 6 29 6 24 6 17 6 31 6 27 6 22 48HJ007 6 TONS Temp F Air Ent Condenser Edb Temp F Air En...

Страница 26: ...Condenser Edb Temp F Air Entering Evaporator Cfm BF 2550 0 08 3000 0 09 3400 0 11 4250 0 13 Temp F Air Entering Evaporator Ewb 72 67 62 72 67 62 72 67 62 72 67 62 75 TC 119 5 105 7 94 8 123 1 109 1 9...

Страница 27: ...5 0 87 3 65 8 85 1 96 0 72 5 96 9 104 8 kW 12 99 12 77 12 50 13 02 12 81 12 55 13 10 12 92 12 74 13 19 13 01 12 91 48HJ014 121 2 TONS Temp F Air Ent Condenser Edb Temp F Air Entering Evaporator Cfm BF...

Страница 28: ...Temp F Air Ent Condenser Edb Temp F Air Entering Evaporator Cfm BF 1200 0 17 1450 0 19 1600 0 21 2000 0 24 Temp F Air Entering Evaporator Ewb 72 67 62 72 67 62 72 67 62 72 67 62 75 TC 52 9 47 5 41 5 5...

Страница 29: ...56 9 49 2 45 9 SHC 10 9 19 6 28 0 12 5 22 2 31 5 13 5 24 0 34 0 16 5 28 0 38 8 kW 6 26 6 12 6 02 6 28 6 18 6 09 6 33 6 18 6 13 6 33 6 27 6 22 48HJ007 6 TONS Temp F Air Ent Condenser Edb Temp F Air En...

Страница 30: ...Ent Condenser Edb Temp F Air Entering Evaporator Cfm BF 2550 0 08 3000 0 09 3400 0 11 4250 0 13 Temp F Air Entering Evaporator Ewb 72 67 62 72 67 62 72 67 62 72 67 62 75 TC 112 4 102 2 92 6 115 2 106...

Страница 31: ...29 0 52 9 69 7 35 0 62 4 82 2 kW 12 35 12 15 11 94 12 38 12 13 11 92 12 48 12 27 12 25 12 53 12 30 12 28 48HJ014 121 2 TONS Temp F Air Ent Condenser Edb Temp F Air Entering Evaporator Cfm BF 3750 0 0...

Страница 32: ...J004 3 TONS STANDARD MOTOR BELT DRIVE cont Airflow Cfm External Static Pressure in wg 0 7 0 8 0 9 1 0 1 1 1 2 Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp 900 957 0 39 988 0 43 1039 0 47 1061 0 51...

Страница 33: ...Static Pressure in wg 0 9 1 0 1 1 1 2 1 4 1 6 1 8 Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp 1200 993 0 65 1028 0 69 1056 0 72 1083 0 74 1134 0 80 1185 0 88 1331 0 99 1300 1021 0 74 1058...

Страница 34: ...0 2 0 4 0 6 0 8 1 0 1 2 1 4 1 6 Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp 1500 771 0 37 828 0 44 935 0 58 1027 0 73 1107 0 88 1185 1 04 1257 1 20 1330 1 38 1411 1 59 1600...

Страница 35: ...7 2 35 1710 2 54 2400 1174 1 37 1237 1 41 1292 1 55 1392 1 81 1460 1 90 1532 2 14 1584 2 28 1671 2 55 1756 2 70 2500 1201 1 48 1272 1 53 1335 1 71 1427 1 94 1518 2 16 1575 2 35 1633 2 53 1698 2 72 260...

Страница 36: ...0 712 1 59 774 1 90 830 2 23 881 2 56 930 2 90 976 3 25 3600 729 1 71 790 2 03 845 2 37 895 2 71 943 3 05 988 3 41 3700 745 1 84 805 2 17 860 2 52 909 2 87 956 3 22 3750 754 1 91 813 2 24 868 2 59 917...

Страница 37: ...6 Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp 2550 559 0 72 634 0 97 700 1 21 759 1 48 814 1 74 864 2 01 915 2 34 968 2 81 2600 567 0 75 641 1 00 706 1 25 764 1 52 819 1 79 869 2 0...

Страница 38: ...0 830 2 23 881 2 56 930 2 90 3600 729 1 71 790 2 03 845 2 37 895 2 71 943 3 05 3700 745 1 84 805 2 17 860 2 52 909 2 87 956 3 22 3750 754 1 91 813 2 24 868 2 59 917 2 95 963 3 30 3800 762 1 98 821 2 3...

Страница 39: ...6 820 1 80 875 2 01 928 2 29 979 2 55 1029 2 80 1079 3 07 1128 3 34 1173 3 60 1214 3 83 4000 777 1 67 836 1 92 889 2 14 941 2 40 991 2 68 1040 2 94 1089 3 22 1137 3 49 1183 3 76 1225 4 00 4100 793 1 7...

Страница 40: ...58 48HJ004 3 TONS STANDARD MOTOR BELT DRIVE cont Airflow Cfm External Static Pressure in wg 0 7 0 8 0 9 1 0 1 1 1 2 Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp 900 924 0 32 953 0 35 989 0 38 1028...

Страница 41: ...Pressure in wg 0 9 1 0 1 1 1 2 1 4 1 6 1 8 Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp 1200 987 0 64 1030 0 70 1068 0 79 1106 0 87 1134 0 98 1189 1 12 1245 1 21 1300 1006 0 71 1044 0 77 10...

Страница 42: ...2 1 4 1 6 Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Bhp Rpm Bhp Rpm Bhp Rpm 1500 741 0 38 798 0 43 895 0 54 990 0 67 1073 0 80 1154 0 95 1218 1 12 1295 1 36 1360 1 40 1600 783 0 45 838 0 51 933...

Страница 43: ...1604 2 42 2500 1183 1 43 1201 1 50 1284 1 65 1338 1 75 1402 1 99 1469 2 04 1524 2 24 1585 2 42 1638 2 60 2600 1210 1 58 1243 1 67 1312 1 76 1366 1 96 1435 2 10 1494 2 19 1552 2 40 1616 2 63 1671 2 80...

Страница 44: ...942 2 89 989 3 26 1034 3 63 3400 684 1 41 747 1 70 807 2 04 857 2 35 882 2 51 907 2 66 954 3 02 1000 3 40 1044 3 79 3500 701 1 53 762 1 82 821 2 16 871 2 48 895 2 64 919 2 80 966 3 15 1011 3 55 1054...

Страница 45: ...057 4 18 1098 4 60 4000 783 2 18 838 2 50 891 2 86 942 3 26 964 3 45 986 3 63 1028 3 99 1070 4 36 1110 4 78 4100 800 2 34 854 2 66 905 3 02 956 3 43 978 3 62 1000 3 81 1042 4 18 1082 4 56 1122 4 97 42...

Страница 46: ...1102 3 20 1143 3 42 1174 3 59 4000 720 1 47 786 1 71 847 1 97 902 2 19 957 2 50 1011 2 79 1064 3 07 1112 3 34 1155 3 59 1190 3 80 4100 734 1 56 800 1 82 860 2 09 914 2 31 967 2 60 1021 2 91 1072 3 20...

Страница 47: ...70 950 925 905 880 860 014 1260 1220 1185 1155 1130 1100 1075 1045 1015 990 960 930 900 HIGH STATIC MOTOR UNIT 48HJ MOTOR PULLEY TURNS OPEN 0 1 2 1 11 2 2 21 2 3 31 2 4 41 2 5 51 2 6 004 1455 1423 139...

Страница 48: ...ee 2 90 2615 208 230 7 9 460 3 6 575 3 6 007 Three 2 90 2615 208 230 6 4 460 3 6 575 3 6 008 009 Three 4 20 3775 208 230 12 6 460 5 7 575 5 7 012 Three 5 25 4400 208 230 15 0 460 7 4 575 7 4 UNIT 48HJ...

Страница 49: ...3 18 009 81 2 10 15 22 012 10 08 13 18 014 121 2 11 18 26 FIOP Factory Installed Option UNIT SIZE 48HJ EFFICIENCY 004 005 75 006 74 84 007 84 008 009 80 012 85 014 87 watts bhp 746 motor efficiency 0...

Страница 50: ...7 000 35 44 35 43 8 000 36 44 36 44 9 000 37 45 37 44 10 000 38 46 38 45 11 000 39 47 39 45 12 000 40 47 40 46 13 000 41 48 41 47 14 000 42 48 42 47 Performance data cont FLOW cfm 0 0 1 0 2 0 3 0 4 0...

Страница 51: ...45 45 216 216 208 230 3 60 187 254 17 3 123 0 1 5 5 8 57 28 9 28 9 35 35 28 28 168 168 460 3 60 414 508 9 0 62 0 0 8 2 6 30 14 7 20 14 84 575 3 60 518 632 7 1 50 0 0 8 2 6 30 11 6 15 11 67 48HJD HJE H...

Страница 52: ...50 221 221 208 230 3 60 187 254 17 3 123 0 1 5 5 8 57 34 9 34 9 40 40 34 34 173 173 460 3 60 414 508 9 0 62 0 0 8 2 6 30 17 4 20 17 86 575 3 60 518 632 7 1 50 0 0 8 2 6 30 13 8 20 13 69 48HJD HJE HJF...

Страница 53: ...2 6 0 3 9 7 15 9 57 48HJD HJE HJF006 208 230 3 60 187 254 17 3 123 0 1 5 7 5 0 6 30 6 35 30 187 460 3 60 414 508 9 0 62 0 0 8 3 4 0 3 15 5 20 15 94 575 3 60 518 632 7 1 50 0 0 8 3 4 0 3 12 2 15 12 76...

Страница 54: ...8 15 11 59 48HJD HJE HJF006 208 230 3 60 187 254 17 3 123 0 1 5 7 5 0 6 36 6 40 36 192 460 3 60 414 508 9 0 62 0 0 8 3 4 0 3 18 2 20 18 96 575 3 60 518 632 7 1 50 0 0 8 3 4 0 3 14 4 20 14 77 48HJE HJF...

Страница 55: ...55 Typical piping and wiring UNITS WITH MOISTUREMISER OPTION...

Страница 56: ...56 Typical piping and wiring cont VERTICAL DISCHARGE HORIZONTAL DISCHARGE...

Страница 57: ...osition will be determined by the supply air temperature When the first stage of cooling is satisfied the IFM shuts off after a 30 second delay The damper then moves to fully closed position Cooling u...

Страница 58: ...2 and 24 vac terminals and between the T1 and 24 vac terminals This causes the economizer damper to remain in an intermediate open position If the supply air temperature falls below 52 F a switch on t...

Страница 59: ...is desired a field installed wall mounted humidistat is required If the MoistureMiser humidistat is installed and calls for the MoistureMiser subcooler coil to operate the humidistat internal switch...

Страница 60: ...t food chains schools and hotels a TEMP System is a cost effective way to maintain comfortable building envi ronments See Typical TEMP System on page 62 Variable Volume Variable Temperature VVT system...

Страница 61: ...S LPS Low Pressure Switch Subcooler Only TRAN Transformer Factory Wiring Accessory or Optional Wiring TYPICAL MOISTUREMISER DEHUMIDIFICATION PACKAGE HUMIDISTAT WIRING 48HJ008 014 208 230 V UNIT SHOWN...

Страница 62: ...MONITOR THERMOSTAT WITH TIMECLOCK ZONE DAMPER ZONE DAMPER ZONE DAMPER ZONE CONTROLLER ZONE CONTROLLER ZONE CONTROLLER ROOFTOP UNIT WITH APOLLO COMMUNICATING CONTROL RETURN SUPPLY BYPASS DAMPER MIXED...

Страница 63: ...EGEND C Contactor NOTE Refer to Product Support Bulletin No 93 005 or contact your local Carrier representative for shielded wire applications when wiring the thermostat to the Apollo control and for...

Страница 64: ...08 014 LEGEND C Contactor CHAS Ground CLO Compressor Lockout COM Common DX Direct Expansion ECON Economizer GND Ground HT Heat IAQ Indoor Air Quality NC Normally Closed NO Normally Open OAT Outdoor Ai...

Страница 65: ...and the notes following each Fan Performance table can be utilized with extreme confidence Using Carrier motors to the values listed in the Physical Data Fan Performance and Evaporator Fan Motor Data...

Страница 66: ...the unit latent capacity is increased The refrigerant cycle follows the same path from point no 1 to point no 2 as the stan dard refrigerant cycle without a subcooler see the pressure enthalpy curve...

Страница 67: ...o low suction pres sure conditions The MoistureMiser dehumidification package contains a low pressure switch that deactivates the MoistureMiser under low suction pressure condi tions without deactivat...

Страница 68: ...68 Application data cont PRESSURE ENTHALPY CURVE NOTE Numbers 1 through 4 indicate point numbers referred to in MoistureMiser Dehumidification Package Design Effects section...

Страница 69: ...CHROMETRIC CHART 48HJ006 SHOWN Point 1 Entering Air F 80 db 67 wb Point 2 Leaving Air F 58 9 db 56 4 wb Without Subcooler Point 3 Leaving Air F 63 0 db 56 8 wb With Subcooler LEGEND db Dry Bulb wb Wet...

Страница 70: ...pical wiring schematic 008 014 460 3 60 shown CIRCUIT BREAKER VOLTS MFG PT NO MUST TRIP AMPS CB 24 V POTTER BRUMFIELD 3 2 W2BX 1024 3 2 CB1 014 Std 460 3 60 Heinemann Airpax 8 5 CF3 Z228 41 219 3 2600...

Страница 71: ...t Ground ER Economizer Relay FPT Freeze Protection Thermostat FS Flame Sensor FSS Filter Status Switch FU Fuse GV Gas Valve GVR Gas Valve Relay HPS High Pressure Switch HS Hall Effect Sensor HV High V...

Страница 72: ...interior surfaces on all panels 2 Evaporator fan cabinet interior shall be insu lated with a minimum 1 2 in thick flexible fiber glass insulation coated on the air side Aluminum foil faced fiberglass...

Страница 73: ...tch 3 Freeze protection thermostat evapora tor coil 4 High pressure switch The lockout protection shall be easily discon nected at the control board if necessary b Heating section shall be provided wi...

Страница 74: ...s d Equipped with barometric relief damper 7 Solid State Enthalpy Control Capable of sensing outdoor air enthalpy con tent temperature and humidity and control ling economizer cut in point to have min...

Страница 75: ...shall contain all the necessary hard ware and instructions to convert a standard nat ural gas unit for use with liquid propane 25 NOx Reduction Kit Package shall contain all necessary hardware and ins...

Страница 76: ...t any time specifications or designs without notice and without incurring obligations New Pg 76 Catalog No 524 894 Printed in U S A PC 111 Form 48HJ 11PD Replaces 48HJ 10PD Book 1 4 Tab 1a 6a Carrier...

Отзывы: