52
STANDARD MOTOR UNITS WITH ELECTRICAL CONVENIENCE OUTLET
LEGEND
*Used to determine minimum disconnect per NEC.
†Fuse or HACR circuit breaker per NEC.
**Units have 2 condenser-fan motors.
NOTES:
1. In compliance with NEC requirements for multimotor and combina-
tion load equipment (refer to NEC Articles 430 and 440), the over-
current protective device for the unit shall be fuse or HACR
breaker. The UL, Canada units may be fuse or circuit breaker.
2. Electrical data based on 95 F ambient outdoor-air temperature
± 10% voltage.
UNIT
NOMINAL
VOLTAGE
(V-Ph-Hz)
VOLTAGE
RANGE
COMPRESSOR
OFM
IFM
COMBUSTION
FAN MOTOR
POWER
SUPPLY
WITH OUTLET
MINIMUM UNIT
DISCONNECT
SIZE*
Min
Max
RLA
LRA
FLA
FLA
FLA
MCA
MOCP
FLA
LRA
48HJE/HJF004
(3 Tons)
208/230-1-60
187
254
16.0
88.0
0.7
4.9
.57
31.6/31.6
40/40†
30/30
106/106
208/230-3-60
187
254
10.3
77.0
0.7
4.9
.57
24.5/24.5
30/30†
24/24
95/95
460-3-60
414
508
5.1
39.0
0.4
2.2
.30
11.7
15†
11
48
575-3-60
518
632
4.2
31.0
0.4
2.2
.30
9.5
15†
9
38
48HJD/HJE/HJF005
(4 Tons)
208/230-1-60
187
254
23.7
129.0
0.7
4.9
.57
41.2/41.2
50/50†
39/39
147/147
208/230-3-60
187
254
13.5
99.0
0.7
4.9
.57
28.5/28.5
35/35†
27/27
117/117
460-3-60
414
508
7.4
49.5
0.4
2.2
.30
14.6
20†
14
58
575-3-60
518
632
5.8
40.0
0.4
2.2
.30
11.5
15†
11
47
48HJD/HJE/HJF006
(5 Tons)
208/230-1-60
187
254
28.8
169.0
1.5
8.8
.57
52.3/52.3
60/60†
50/50
221/221
208/230-3-60
187
254
17.3
123.0
1.5
5.8
.57
34.9/34.9
40/40†
34/34
173/173
460-3-60
414
508
9.0
62.0
0.8
2.6
.30
17.4
20†
17
86
575-3-60
518
632
7.1
50.0
0.8
2.6
.30
13.8
20†
13
69
48HJD/HJE/HJF007
(6 Tons)
208/230-3-60
187
254
20.5
156.0
1.4
5.8
.57
38.8/38.8
45/45†
35/35
205/205
460-3-60
414
508
9.6
70.0
0.6
2.6
.30
17.9
20†
17
94
575-3-60
518
632
7.7
56.0
0.6
2.6
.30
14.3
20†
15
79
48HJD/HJE/HJF008
(7
1
/
2
Tons)**
208/230-3-60
187
254
12.4
88.0
1.4
7.5
.57
44.2/44.2
50/50†
46/46
247/247
460-3-60
414
508
6.4
44.0
0.7
3.4
.30
21.9
25†
23
124
575-3-60
518
632
4.8
34.0
0.7
3.4
.30
16.8
20†
17.5
97
48HJD/HJE/HJF009
(8
1
/
2
Tons)**
208/230-3-60
187
254
15.0
99.0
1.4
7.5
.57
50.1/50.1
60/60†
52/52
269/269
460-3-60
414
508
8.2
49.5
0.7
3.4
.30
26.0
30†
27
135
575-3-60
518
632
5.8
40.0
0.7
3.4
.30
19.1
25†
20
109
48HJD/HJE/HJF012
(10 Tons)**
208/230-3-60
187
254
17.3
123.0
1.4
10.6
.57
58.3/58.3
70/70
61/61
341/341
460-3-60
414
508
9.0
62.0
0.7
4.8
.30
29.2
35†
30
172
575-3-60
518
632
7.1
50.0
0.7
4.8
.30
23.1
25†
24
139
48HJD/HJE014
(12
1
/
2
Tons)**
208/230-3-60
187
254
19.0
156.0
1.4
15.0
.57
66.6/66.6
70/70
70/70
430/430
460-3-60
414
508
9.0
70.0
0.7
7.4
.30
31.8
35†
33
199
575-3-60
518
632
7.4
54.0
0.7
7.4
.30
25.9
30†
27
156
FLA
— Full Load Amps
HACR — Heating, Air Conditioning and Refrigeration
IFM
— Indoor (Evaporator) Fan Motor
LRA
— Locked Rotor Amps
MCA
— Minimum Circuit Amps
MOCP — Maximum Overcurrent Protection
NEC
— National Electrical Code
OFM
— Outdoor (Condenser) Fan Motor
RLA
— Rated Load Amps
UL
— Underwriters’ Laboratories
Electrical data (cont)