53
HIGH-STATIC MOTOR UNITS WITHOUT ELECTRICAL CONVENIENCE OUTLET
LEGEND
*Used to determine minimum disconnect per NEC.
†Fuse or HACR circuit breaker per NEC.
**Units have 2 condenser-fan motors.
NOTES:
1. In compliance with NEC requirements for multimotor and combina-
tion load equipment (refer to NEC Articles 430 and 440), the over-
current protective device for the unit shall be fuse or HACR
breaker. The UL, Canada units may be fuse or circuit breaker.
2. Electrical data based on 95 F ambient outdoor-air temperature
± 10% voltage.
UNIT
NOMINAL
VOLTAGE
(V-Ph-Hz)
VOLTAGE
RANGE
COMPRESSOR
(each)
OFM
IFM
COMBUSTION
FAN MOTOR
POWER
SUPPLY
MINIMUM UNIT
DISCONNECT
SIZE*
Min
Max
RLA
LRA
FLA
FLA
RLA
MCA
MOCP
FLA
LRA
48HJE,HJF004
208/230-3-60
187
254
10.3
77.0
0.7
5.8
0.6
19.4
25†
19
120
460-3-60
414
508
5.1
39.0
0.4
2.6
0.3
9.4
15†
9
60
575-3-60
518
632
4.2
31.0
0.4
2.6
0.3
7.7
15†
8
48
48HJD/HJE/HJF005
208/230-3-60
187
254
13.5
99.0
0.7
5.8
0.6
23.4
30†
23
142
460-3-60
414
508
7.4
49.5
0.4
2.6
0.3
12.3
15†
12
71
575-3-60
518
632
5.8
40.0
0.4
2.6
0.3
9.7
15†
9
57
48HJD/HJE/HJF006
208/230-3-60
187
254
17.3
123.0
1.5
7.5
0.6
30.6
35†
30
187
460-3-60
414
508
9.0
62.0
0.8
3.4
0.3
15.5
20†
15
94
575-3-60
518
632
7.1
50.0
0.8
3.4
0.3
12.2
15†
12
76
48HJE/HJF/HJD007
208/230-3-60
187
254
20.5
156.0
1.4
7.5
0.6
30.6
35†
30
187
460-3-60
414
508
9.6
70.0
0.6
3.4
0.3
15.5
20†
15
94
575-3-60
518
632
7.7
56.0
0.6
3.4
0.3
12.2
15†
12
76
48HJD/HJE/HJF008**
208/230-3-60
187
254
12.4
88.0
1.4
10.6
0.6
41.3
45†
44
267
460-3-60
414
508
6.4
44.0
0.7
4.8
0.3
20.6
25†
22
134
575-3-60
632
518
4.8
34.0
0.7
4.8
0.3
15.8
20†
17
95
48HJD/HJE/HJF009**
208/230-3-60
187
254
15.0
99.0
1.4
10.6
0.6
47.2
60†
50
264
460-3-60
414
508
8.2
49.5
0.7
4.8
0.3
24.7
30†
26
132
575-3-60
518
632
5.8
40.0
0.7
4.8
0.3
18.0
20†
19
107
48HJD/HJF/HJE012**
208/230-3-60
187
254
17.3
125.0
1.4
15.0
0.6
56.7
70
61
360
460-3-60
414
508
9.0
62.0
0.7
7.4
0.3
29.1
35†
29
181
575-3-60
518
632
7.1
50.0
0.7
7.4
0.3
23.0
25†
23
136
FLA
— Full Load Amps
HACR — Heating, Air Conditioning and Refrigeration
IFM
— Indoor (Evaporator) Fan Motor
LRA
— Locked Rotor Amps
MCA
— Minimum Circuit Amps
MOCP — Maximum Overcurrent Protection
NEC
— National Electrical Code
OFM
— Outdoor (Condenser) Fan Motor
RLA
— Rated Load Amps
UL
— Underwriters’ Laboratories