background image

21

I

Determine cooling and heating loads at design
conditions.

Given:
Required Cooling Capacity (TC)  . . . . . .67,000 Btuh
Sensible Heat Capacity (SHC). . . . . . . .46,000 Btuh
Required Heating Capacity . . . . . . . . . .85,000 Btuh
Outdoor Entering-Air Temperature db . . . . . . . .95 F
Outdoor Entering-Air Temperature wb. . . . . . . .75 F
Outdoor-Air Entering Airflow Cfm  . . . . . .  450 Cfm
Outdoor-Air Winter Design Temperature . . . . . . 0° F
Indoor-Air Winter Design Temperature  . . . . . . .70 F
Air to room including outdoor air  . . . . . .  2000 Cfm
External Static Pressure . . . . . Supply — 0.60 in. wg

Return —  0.2 in. wg

Indoor-Air Temperature db (room air)  . . . . . . . .78 F
Indoor-Air Temperature wb (room air) . . . . . . . .65 F
Indoor-Air Exhaust Cfm . . . . . . . . . . . . . .  450 Cfm
Electrical Characteristics (V-Ph-Hz)  . . . . . . 230-1-60
Vertical discharge unit with Energy$Recycler
required.

II

Determine fan speed and power requirements
at design conditions.

Before entering the Fan Performance tables, calculate
the total static pressure required based on unit com-
ponent. From the given and the Economizer Static
Pressure tables on page 48 find:

External static pressure supply

0.6 in. wg

External static pressure return

0.2 in. wg

Accessory static — None

0.0 in. wg

Total Static

0.8 in. wg

Enter the Fan Performance table for vertical
discharge, standard motor, 48HJ006 at 0.80 in. wg
and 2000 cfm. The rpm is 1303 and bhp is 1.41.
NOTE: Convert bhp to Fan Heat and Watts using the
formula found in the note following the Evaporator-
Fan Motor Efficiency table on page 49.
For this example:
Watts = (746 x Bhp)/(motor efficiency)
Watts = (746 x 1.41)/(0.74) = 1421 watts
Indoor Fan Heat = watts x 3.413 Btuh/watt

= 1421 x 3.413 = 4851 Btuh

III

Select Energy$Recycler based on outdoor
entering cfm.

Using Energy$Recycler cooling rating tables found in
the Energy$Recycler Product Data choose 62AQ060
unit.

Using 450 cfm outdoor supply airflow, 95 F OD db,
and 75 F OD wb find performance of the 62AQ060
at these conditions:
Energy$Recycler Gross Cooling

Capacity is

13,000 Btuh

Energy$Recycler Gross Sensible

Capacity is

10,100 Btuh

Compressor power is

1.06 kW

Energy$Recycler Leaving db is

73 F

Energy$Recycler Leaving wb is

66.9 F

IV

Using the simplified* method below, calculate
the approximate mixed air temperature for the
SRT evaporator coil.

Using the outdoor air entering cfm, the room cfm and
the room exhaust airflow with their respective db and
wb temperatures determine the db and wb entering
the rooftop evaporator coil.
a) Estimate the mixed air db to the evaporator coil.

t mix db = ((cfm oa x t oa db) + ((cfm ra – cfm exh)
x    t rm db)) / ((cfm ao + (cfm ra – cfm exh)))
= ((450 cfm x 73.0 F) + ((2000 cfm – 450 cfm)

x 78 F)) / ((450 cfm + (2000 cfm – 450 cfm)))

= 76.9 F 

mixed air into the rooftop evaporator

coil

b) Estimate the mixed air wb to the evaporator coil.

t mix wb* = ((cfm oa x t oa wb) + ((cfm ra  – cfm
exh) x t rm wb)) / ((cfm oa + (cfm ra – cfm exh)))
= ((450 cfm x 66.9 F) + ((2000 cfm – 450 cfm)

x  65 F)) / ((450 cfm + (2000 cfm – 450 cfm)))

= 65.4 F wb 

mixed air temperature into the

rooftop evaporator

*Simplified method of determining wet bulb (wb)

temperature of mixture. This approximation is
used because the wb lines in the area of the psy-
chrometric chart in the area used in the calcula-
tion is relatively linear, providing a close approxi-
mation. A more accurate solution can be found
using the E-Cat program.

LEGEND

V

Determine the cooling load requirement for the
rooftop unit.

Required Cooling Capacity is

67,000 Btuh

Less Cooling Capacity supplied
by the Energy$Recycler

–13,000 Btuh

Rooftop cooling load required is

54,000 Btuh

VI

Select the rooftop unit based on mixed air
entering conditions and cooling load.

Enter cooling capacity table at outdoor entering tem-
perature 95 F, mixed air entering evaporator at
2000 cfm, 76.9 F db, and 65.4 F wb.
The 48HJ006 will provide a total gross cooling
capacity of 59,420 Btuh and sensible cooling of
43,420 Btuh.
Because these values were not at 80 F entering db,
they were calculated based on the notes following the
Cooling Capacity tables.

NOTE: Unit ratings are gross capacities and do not
include the effect of evaporator-fan motor heat. To
calculate net capacities see Steps VII and VIII.

cfm —

cubic feet per minute of air

db

dry bulb

exh —

Energy$Recycler discharge

mix —

mixture of o return air

oa

outside air leaving Energy$Recycler

ra

return air

sa

supply air at coil (sa = oa + ra – exh)

t

temperature

TC

total capacity gross

SHC —

sensible capacity

wb

wet bulb

Selection procedure (with 48HJ006 example)

Содержание 48HJD005

Страница 1: ...Standard belt driven evaporator fan motors on all units Ease of maintenance achieved by self diagnostics on the Integrated Gas Controller IGC optional direct digital controls standard size filters to...

Страница 2: ...s of charge switch high pressure switch freeze protection thermostat internal compressor overload exclusive Carrier Cycle LOC circuit board that provides anti compressor cycling refrigerant filter dri...

Страница 3: ...izing roof penetrations to prevent water leaks Power gas and control connections are made on the same side of the unit to simplify installation The non corrosive sloped con densate drain pan is made i...

Страница 4: ...rigeration system 5 Carrier s exclusive Acutrol meter ing device which precisely controls refrigerant flow preventing slug ging and floodback while maintain ing optimum unit performance by metering th...

Страница 5: ...air conditioning systems that bring in minimal fresh air In 1989 IAQ concerns caused ASHRAE to recommend increased ventilation for all public buildings Sim ply introducing fresh air into a building h...

Страница 6: ...v circuit breaker on 48HJ008 014 units allows room for error without replacing transform ers or fuses Single side utility connections provide easy access to perform any necessary service Color coded...

Страница 7: ...tuh First Stage Second Stage OUTPUT CAPACITY Btuh TEMPERATURE RISE F AFUE STEADY STATE EFFICIENCY CALIFORNIA SEASONAL EFFICIENCY Single Phase Units First Stage Second Stage 3 Phase Units First Stage S...

Страница 8: ...1 17 1 17 1 17 1 17 Total Face Area sq ft 3 9 3 9 3 9 3 9 EVAPORATOR FAN Centrifugal Type Belt Drive Quantity Size in 1 10 x 10 1 10 x 10 1 10 x 10 1 10 x 10 Nominal Cfm 1200 1600 2000 2400 Maximum C...

Страница 9: ...Thermostat Heat Anticipator Setting amps 208 230 460 v First Stage 14 14 14 14 Second Stage 14 14 14 14 Gas Input Btuh First Stage 50 000 82 000 50 000 82 000 120 000 50 000 82 000 120 000 50 000 82 0...

Страница 10: ...midification Package Rows Fins in 1 17 1 17 1 17 1 17 Total Face Area sq ft 6 3 6 3 8 4 8 4 EVAPORATOR FAN Centrifugal Size in 15 x 15 15 x 15 15 x 15 15 x 15 Type Drive Belt Belt Belt Belt Nominal Cf...

Страница 11: ...00 90 000 120 000 180 000 120 000 180 000 200 000 180 000 200 000 Stage 2 125 000 180 000 224 000 125 000 180 000 224 000 180 000 224 000 250 000 224 000 250 000 Efficiency Steady State 82 82 82 82 82...

Страница 12: ...cusensor II Enthalpy Control X Accusensor III Differential Enthalpy Sensor X Liquid Propane Conversion Kit X Condenser Coil Hail Guard X NOx Reduction Kit X Flue Discharge Deflector X Coil Guard Grill...

Страница 13: ...estarting for at least 5 minutes after a shutdown Field installed accessory pre vents short cycling of compressor if thermostat is rapidly changed Time Guard II device mounts in the control compartmen...

Страница 14: ...TAT ACCUSENSOR II ENTHALPY CONTROL Field installed wall mounted humidistat is used to control operation of the MoistureMiser dehumidification package The humid istat controls the occupied space humidi...

Страница 15: ...coil located on the leaving air side of the evaporator coil The location of this coil in the indoor air stream enhances the latent capacity of the 48HJ units by as much as 40 The MoistureMiser package...

Страница 16: ...ermits quick and simple compressor access COMPRESSOR HINGED PANEL OPTION 48HJ008 014 UNITS SHOWN EVAPORATOR FAN HINGED PANEL OPTION This is included as a factory installed option It per mits quick and...

Страница 17: ...using accessory flue discharge deflector b Bottom of unit to combustible surfaces when not using curb 1 inch Bottom of base rail to combustible surfaces when not using curb 0 inches c Condenser coil...

Страница 18: ...urb 0 inches c Condenser coil for proper airflow 36 in one side 12 in the other The side getting the greater clearance is optional d Overhead 60 in to assure proper condenser fan operation e Between u...

Страница 19: ...TMPWR002A00 1 2 NPT CRBTMPWR003A00 ROOF CURBS NOTES 1 Roof curb accessory is shipped unassembled 2 Insulated panels 3 Dimensions in are in millimeters 4 Roof curb galvanized steel 5 Attach ductwork to...

Страница 20: ...PT CRBTMPWR001A00 3 4 NPT 11 4 NPT 1 2 NPT CRBTMPWR002A00 3 4 NPT CRBTMPWR004A00 ROOF CURBS NOTES 1 Roof curb accessory is shipped unassembled 2 Insulated panels 3 Dimensions in are in millimeters 4 R...

Страница 21: ...he simplified method below calculate the approximate mixed air temperature for the SRT evaporator coil Using the outdoor air entering cfm the room cfm and the room exhaust airflow with their respectiv...

Страница 22: ...tep II 4 851 Btuh Optional Energy Recycler Supply Fan Motor Heat none Net Sensible Capacity 48 659 Btuh IX Determine the operating watts of the unit a Cooling with Energy Recycler in operation Rooftop...

Страница 23: ...62AQ is sized for a minimum of 33 larger than the overcurrent protection device value i e 60 amps x 0 33 20 amps no further subfusing would be required If the overcurrent protection device is greater...

Страница 24: ...Temp F Air Ent Condenser Edb Temp F Air Entering Evaporator Cfm BF 1200 0 17 1450 0 19 1600 0 21 2000 0 24 Temp F Air Entering Evaporator Ewb F 72 67 62 72 67 62 72 67 62 72 67 62 75 TC 54 0 50 7 44...

Страница 25: ...62 2 56 8 53 5 SHC 30 0 37 2 43 1 31 7 40 4 46 2 33 3 43 4 48 9 36 4 48 9 53 4 kW 6 27 6 19 6 09 6 28 6 21 6 13 6 29 6 24 6 17 6 31 6 27 6 22 48HJ007 6 TONS Temp F Air Ent Condenser Edb Temp F Air En...

Страница 26: ...Condenser Edb Temp F Air Entering Evaporator Cfm BF 2550 0 08 3000 0 09 3400 0 11 4250 0 13 Temp F Air Entering Evaporator Ewb 72 67 62 72 67 62 72 67 62 72 67 62 75 TC 119 5 105 7 94 8 123 1 109 1 9...

Страница 27: ...5 0 87 3 65 8 85 1 96 0 72 5 96 9 104 8 kW 12 99 12 77 12 50 13 02 12 81 12 55 13 10 12 92 12 74 13 19 13 01 12 91 48HJ014 121 2 TONS Temp F Air Ent Condenser Edb Temp F Air Entering Evaporator Cfm BF...

Страница 28: ...Temp F Air Ent Condenser Edb Temp F Air Entering Evaporator Cfm BF 1200 0 17 1450 0 19 1600 0 21 2000 0 24 Temp F Air Entering Evaporator Ewb 72 67 62 72 67 62 72 67 62 72 67 62 75 TC 52 9 47 5 41 5 5...

Страница 29: ...56 9 49 2 45 9 SHC 10 9 19 6 28 0 12 5 22 2 31 5 13 5 24 0 34 0 16 5 28 0 38 8 kW 6 26 6 12 6 02 6 28 6 18 6 09 6 33 6 18 6 13 6 33 6 27 6 22 48HJ007 6 TONS Temp F Air Ent Condenser Edb Temp F Air En...

Страница 30: ...Ent Condenser Edb Temp F Air Entering Evaporator Cfm BF 2550 0 08 3000 0 09 3400 0 11 4250 0 13 Temp F Air Entering Evaporator Ewb 72 67 62 72 67 62 72 67 62 72 67 62 75 TC 112 4 102 2 92 6 115 2 106...

Страница 31: ...29 0 52 9 69 7 35 0 62 4 82 2 kW 12 35 12 15 11 94 12 38 12 13 11 92 12 48 12 27 12 25 12 53 12 30 12 28 48HJ014 121 2 TONS Temp F Air Ent Condenser Edb Temp F Air Entering Evaporator Cfm BF 3750 0 0...

Страница 32: ...J004 3 TONS STANDARD MOTOR BELT DRIVE cont Airflow Cfm External Static Pressure in wg 0 7 0 8 0 9 1 0 1 1 1 2 Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp 900 957 0 39 988 0 43 1039 0 47 1061 0 51...

Страница 33: ...Static Pressure in wg 0 9 1 0 1 1 1 2 1 4 1 6 1 8 Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp 1200 993 0 65 1028 0 69 1056 0 72 1083 0 74 1134 0 80 1185 0 88 1331 0 99 1300 1021 0 74 1058...

Страница 34: ...0 2 0 4 0 6 0 8 1 0 1 2 1 4 1 6 Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp 1500 771 0 37 828 0 44 935 0 58 1027 0 73 1107 0 88 1185 1 04 1257 1 20 1330 1 38 1411 1 59 1600...

Страница 35: ...7 2 35 1710 2 54 2400 1174 1 37 1237 1 41 1292 1 55 1392 1 81 1460 1 90 1532 2 14 1584 2 28 1671 2 55 1756 2 70 2500 1201 1 48 1272 1 53 1335 1 71 1427 1 94 1518 2 16 1575 2 35 1633 2 53 1698 2 72 260...

Страница 36: ...0 712 1 59 774 1 90 830 2 23 881 2 56 930 2 90 976 3 25 3600 729 1 71 790 2 03 845 2 37 895 2 71 943 3 05 988 3 41 3700 745 1 84 805 2 17 860 2 52 909 2 87 956 3 22 3750 754 1 91 813 2 24 868 2 59 917...

Страница 37: ...6 Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp 2550 559 0 72 634 0 97 700 1 21 759 1 48 814 1 74 864 2 01 915 2 34 968 2 81 2600 567 0 75 641 1 00 706 1 25 764 1 52 819 1 79 869 2 0...

Страница 38: ...0 830 2 23 881 2 56 930 2 90 3600 729 1 71 790 2 03 845 2 37 895 2 71 943 3 05 3700 745 1 84 805 2 17 860 2 52 909 2 87 956 3 22 3750 754 1 91 813 2 24 868 2 59 917 2 95 963 3 30 3800 762 1 98 821 2 3...

Страница 39: ...6 820 1 80 875 2 01 928 2 29 979 2 55 1029 2 80 1079 3 07 1128 3 34 1173 3 60 1214 3 83 4000 777 1 67 836 1 92 889 2 14 941 2 40 991 2 68 1040 2 94 1089 3 22 1137 3 49 1183 3 76 1225 4 00 4100 793 1 7...

Страница 40: ...58 48HJ004 3 TONS STANDARD MOTOR BELT DRIVE cont Airflow Cfm External Static Pressure in wg 0 7 0 8 0 9 1 0 1 1 1 2 Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp 900 924 0 32 953 0 35 989 0 38 1028...

Страница 41: ...Pressure in wg 0 9 1 0 1 1 1 2 1 4 1 6 1 8 Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp 1200 987 0 64 1030 0 70 1068 0 79 1106 0 87 1134 0 98 1189 1 12 1245 1 21 1300 1006 0 71 1044 0 77 10...

Страница 42: ...2 1 4 1 6 Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Bhp Rpm Bhp Rpm Bhp Rpm 1500 741 0 38 798 0 43 895 0 54 990 0 67 1073 0 80 1154 0 95 1218 1 12 1295 1 36 1360 1 40 1600 783 0 45 838 0 51 933...

Страница 43: ...1604 2 42 2500 1183 1 43 1201 1 50 1284 1 65 1338 1 75 1402 1 99 1469 2 04 1524 2 24 1585 2 42 1638 2 60 2600 1210 1 58 1243 1 67 1312 1 76 1366 1 96 1435 2 10 1494 2 19 1552 2 40 1616 2 63 1671 2 80...

Страница 44: ...942 2 89 989 3 26 1034 3 63 3400 684 1 41 747 1 70 807 2 04 857 2 35 882 2 51 907 2 66 954 3 02 1000 3 40 1044 3 79 3500 701 1 53 762 1 82 821 2 16 871 2 48 895 2 64 919 2 80 966 3 15 1011 3 55 1054...

Страница 45: ...057 4 18 1098 4 60 4000 783 2 18 838 2 50 891 2 86 942 3 26 964 3 45 986 3 63 1028 3 99 1070 4 36 1110 4 78 4100 800 2 34 854 2 66 905 3 02 956 3 43 978 3 62 1000 3 81 1042 4 18 1082 4 56 1122 4 97 42...

Страница 46: ...1102 3 20 1143 3 42 1174 3 59 4000 720 1 47 786 1 71 847 1 97 902 2 19 957 2 50 1011 2 79 1064 3 07 1112 3 34 1155 3 59 1190 3 80 4100 734 1 56 800 1 82 860 2 09 914 2 31 967 2 60 1021 2 91 1072 3 20...

Страница 47: ...70 950 925 905 880 860 014 1260 1220 1185 1155 1130 1100 1075 1045 1015 990 960 930 900 HIGH STATIC MOTOR UNIT 48HJ MOTOR PULLEY TURNS OPEN 0 1 2 1 11 2 2 21 2 3 31 2 4 41 2 5 51 2 6 004 1455 1423 139...

Страница 48: ...ee 2 90 2615 208 230 7 9 460 3 6 575 3 6 007 Three 2 90 2615 208 230 6 4 460 3 6 575 3 6 008 009 Three 4 20 3775 208 230 12 6 460 5 7 575 5 7 012 Three 5 25 4400 208 230 15 0 460 7 4 575 7 4 UNIT 48HJ...

Страница 49: ...3 18 009 81 2 10 15 22 012 10 08 13 18 014 121 2 11 18 26 FIOP Factory Installed Option UNIT SIZE 48HJ EFFICIENCY 004 005 75 006 74 84 007 84 008 009 80 012 85 014 87 watts bhp 746 motor efficiency 0...

Страница 50: ...7 000 35 44 35 43 8 000 36 44 36 44 9 000 37 45 37 44 10 000 38 46 38 45 11 000 39 47 39 45 12 000 40 47 40 46 13 000 41 48 41 47 14 000 42 48 42 47 Performance data cont FLOW cfm 0 0 1 0 2 0 3 0 4 0...

Страница 51: ...45 45 216 216 208 230 3 60 187 254 17 3 123 0 1 5 5 8 57 28 9 28 9 35 35 28 28 168 168 460 3 60 414 508 9 0 62 0 0 8 2 6 30 14 7 20 14 84 575 3 60 518 632 7 1 50 0 0 8 2 6 30 11 6 15 11 67 48HJD HJE H...

Страница 52: ...50 221 221 208 230 3 60 187 254 17 3 123 0 1 5 5 8 57 34 9 34 9 40 40 34 34 173 173 460 3 60 414 508 9 0 62 0 0 8 2 6 30 17 4 20 17 86 575 3 60 518 632 7 1 50 0 0 8 2 6 30 13 8 20 13 69 48HJD HJE HJF...

Страница 53: ...2 6 0 3 9 7 15 9 57 48HJD HJE HJF006 208 230 3 60 187 254 17 3 123 0 1 5 7 5 0 6 30 6 35 30 187 460 3 60 414 508 9 0 62 0 0 8 3 4 0 3 15 5 20 15 94 575 3 60 518 632 7 1 50 0 0 8 3 4 0 3 12 2 15 12 76...

Страница 54: ...8 15 11 59 48HJD HJE HJF006 208 230 3 60 187 254 17 3 123 0 1 5 7 5 0 6 36 6 40 36 192 460 3 60 414 508 9 0 62 0 0 8 3 4 0 3 18 2 20 18 96 575 3 60 518 632 7 1 50 0 0 8 3 4 0 3 14 4 20 14 77 48HJE HJF...

Страница 55: ...55 Typical piping and wiring UNITS WITH MOISTUREMISER OPTION...

Страница 56: ...56 Typical piping and wiring cont VERTICAL DISCHARGE HORIZONTAL DISCHARGE...

Страница 57: ...osition will be determined by the supply air temperature When the first stage of cooling is satisfied the IFM shuts off after a 30 second delay The damper then moves to fully closed position Cooling u...

Страница 58: ...2 and 24 vac terminals and between the T1 and 24 vac terminals This causes the economizer damper to remain in an intermediate open position If the supply air temperature falls below 52 F a switch on t...

Страница 59: ...is desired a field installed wall mounted humidistat is required If the MoistureMiser humidistat is installed and calls for the MoistureMiser subcooler coil to operate the humidistat internal switch...

Страница 60: ...t food chains schools and hotels a TEMP System is a cost effective way to maintain comfortable building envi ronments See Typical TEMP System on page 62 Variable Volume Variable Temperature VVT system...

Страница 61: ...S LPS Low Pressure Switch Subcooler Only TRAN Transformer Factory Wiring Accessory or Optional Wiring TYPICAL MOISTUREMISER DEHUMIDIFICATION PACKAGE HUMIDISTAT WIRING 48HJ008 014 208 230 V UNIT SHOWN...

Страница 62: ...MONITOR THERMOSTAT WITH TIMECLOCK ZONE DAMPER ZONE DAMPER ZONE DAMPER ZONE CONTROLLER ZONE CONTROLLER ZONE CONTROLLER ROOFTOP UNIT WITH APOLLO COMMUNICATING CONTROL RETURN SUPPLY BYPASS DAMPER MIXED...

Страница 63: ...EGEND C Contactor NOTE Refer to Product Support Bulletin No 93 005 or contact your local Carrier representative for shielded wire applications when wiring the thermostat to the Apollo control and for...

Страница 64: ...08 014 LEGEND C Contactor CHAS Ground CLO Compressor Lockout COM Common DX Direct Expansion ECON Economizer GND Ground HT Heat IAQ Indoor Air Quality NC Normally Closed NO Normally Open OAT Outdoor Ai...

Страница 65: ...and the notes following each Fan Performance table can be utilized with extreme confidence Using Carrier motors to the values listed in the Physical Data Fan Performance and Evaporator Fan Motor Data...

Страница 66: ...the unit latent capacity is increased The refrigerant cycle follows the same path from point no 1 to point no 2 as the stan dard refrigerant cycle without a subcooler see the pressure enthalpy curve...

Страница 67: ...o low suction pres sure conditions The MoistureMiser dehumidification package contains a low pressure switch that deactivates the MoistureMiser under low suction pressure condi tions without deactivat...

Страница 68: ...68 Application data cont PRESSURE ENTHALPY CURVE NOTE Numbers 1 through 4 indicate point numbers referred to in MoistureMiser Dehumidification Package Design Effects section...

Страница 69: ...CHROMETRIC CHART 48HJ006 SHOWN Point 1 Entering Air F 80 db 67 wb Point 2 Leaving Air F 58 9 db 56 4 wb Without Subcooler Point 3 Leaving Air F 63 0 db 56 8 wb With Subcooler LEGEND db Dry Bulb wb Wet...

Страница 70: ...pical wiring schematic 008 014 460 3 60 shown CIRCUIT BREAKER VOLTS MFG PT NO MUST TRIP AMPS CB 24 V POTTER BRUMFIELD 3 2 W2BX 1024 3 2 CB1 014 Std 460 3 60 Heinemann Airpax 8 5 CF3 Z228 41 219 3 2600...

Страница 71: ...t Ground ER Economizer Relay FPT Freeze Protection Thermostat FS Flame Sensor FSS Filter Status Switch FU Fuse GV Gas Valve GVR Gas Valve Relay HPS High Pressure Switch HS Hall Effect Sensor HV High V...

Страница 72: ...interior surfaces on all panels 2 Evaporator fan cabinet interior shall be insu lated with a minimum 1 2 in thick flexible fiber glass insulation coated on the air side Aluminum foil faced fiberglass...

Страница 73: ...tch 3 Freeze protection thermostat evapora tor coil 4 High pressure switch The lockout protection shall be easily discon nected at the control board if necessary b Heating section shall be provided wi...

Страница 74: ...s d Equipped with barometric relief damper 7 Solid State Enthalpy Control Capable of sensing outdoor air enthalpy con tent temperature and humidity and control ling economizer cut in point to have min...

Страница 75: ...shall contain all the necessary hard ware and instructions to convert a standard nat ural gas unit for use with liquid propane 25 NOx Reduction Kit Package shall contain all necessary hardware and ins...

Страница 76: ...t any time specifications or designs without notice and without incurring obligations New Pg 76 Catalog No 524 894 Printed in U S A PC 111 Form 48HJ 11PD Replaces 48HJ 10PD Book 1 4 Tab 1a 6a Carrier...

Отзывы: