18
Table 4 — Motor Data
PSC Motor Data
ECM Motor Data
LEGEND
*Available in vertical configuration only.
†Available in horizontal configuration only.
NOTE: The PSC motor is not available on unit size 200.
UNIT 40UV,UH SIZE
MOTOR Hp
VOLTAGE
FLA
MCA
MOP (Amps)
MAX FUSE SIZE
(Amps)
050*
1
/
5
115
3.7
4.6
8.3
15
208/230
2.0
2.5
4.5
15
265
1.6
2.0
3.6
15
075
1
/
5
115
3.7
4.6
8.3
15
208/230
2.0
2.5
4.5
15
265
1.6
2.0
3.6
15
100
1
/
5
115
3.7
4.6
8.3
15
208/230
2.0
2.5
4.5
15
265
1.6
2.0
3.6
15
125
1
/
5
115
3.7
4.6
8.3
15
208/230
2.0
2.5
4.5
15
265
1.6
2.0
3.6
15
150
1
/
5
115
3.7
4.6
8.3
15
208/230
2.0
2.5
4.5
15
265
1.6
2.0
3.6
15
UNIT 40UV,UH SIZE
MOTOR Hp
VOLTAGE
FLA
MCA
MOP (Amps)
MAX FUSE SIZE
(Amps)
050*
1
/
3
115
1.4
1.8
3.1
15
208/230
1.3
1.6
2.9
15
265
1.1
1.4
2.6
15
075
1
/
3
115
3.7
4.6
8.3
15
208/230
2.3
2.9
5.1
15
265
2.0
2.5
4.5
15
100
1
/
3
115
4.0
5.0
9.1
15
208/230
2.6
3.2
5.8
15
265
2.3
2.9
5.1
15
125
1
/
2
115
4.7
5.9
10.6
15
208/230
3.3
4.1
7.4
15
265
2.9
3.6
6.6
15
150
1
/
2
115
4.7
5.9
10.6
15
208/230
3.3
4.1
7.4
15
265
2.9
3.6
6.6
15
200†
3
/
4
115
9.6
12.0
21.6
20
208/230
6.8
8.5
15.3
15
265
5.5
6.9
12.4
15
ECM —
Electronically Commutated Motor
FLA
—
Full Load Amps
MCA —
Minimum Circuit Amps
MOP —
Maximum Overload Protection
PSC —