
17
Table 3 — Electric Heater Data for Units with ECM Motor (cont)
LEGEND
*Cooling coil must be left-hand coil connections only.
NOTES:
1. LAT (leaving air temperature) is at maximum fan speed with
entering air temperature at 70°F.
2. Face and bypass units are available only with 3 elements.
3. Electric heat is available in the reheat only position.
UNIT
HP
NOMINAL
V/Ph/Hz
NUMBER OF
ELEMENTS
FLA
LAT (F)
MCA
MOCP
TOTAL
CAPACITY (kW)
40UV,UH150
(at 1500 cfm)
1
/
2
208/1/60
3
46.7
89
58.3
60
9.0
4
61.1
96
76.4
80
12.0
5
75.6
102
94.4
100
15.0
6*
90.0
108
112.5
125
18.0
240/1/60
3
53.3
96
66.6
70
12.0
4
70.0
104
87.5
90
16.0
5
86.6
113
108.3
110
20.0
6
—
—
—
—
—
277/1/60
3
46.2
96
57.8
60
12.0
4
60.7
104
75.8
80
16.0
5
75.1
113
93.9
100
20.0
6
—
—
—
—
—
208/3/60
3
28.3
89
35.4
40
9.0
4
42.8
96
53.5
60
12.0
5
53.4
102
66.7
70
15.0
6*
53.4
108
66.7
70
18.0
240/3/60
3
32.2
96
40.3
45
12.0
4
48.9
104
61.1
70
16.0
5
61.1
113
76.4
80
20.0
6*
61.1
121
76.4
80
24.0
460/3/60
3
15.6
96
19.5
20
12.0
4
24.0
104
30.0
30
16.0
5
30.1
113
37.6
40
20.0
6*
30.1
121
37.6
40
24.0
40UH200
(at 2000 cfm)
3
/
4
208/1/60
3
50.1
84
62.7
70
9.0
4
64.6
89
80.7
90
12.0
5
79.0
94
98.8
100
15.0
6*
93.5
99
116.8
125
18.0
240/1/60
3
56.8
89
71.0
80
12.0
4
73.5
96
91.8
100
16.0
5
90.1
102
112.7
125
20.0
6
—
—
—
—
—
277/1/60
3
48.8
89
61.0
70
12.0
4
63.3
96
79.1
80
16.0
5
77.7
102
97.1
100
20.0
6
—
—
—
—
—
208/3/60
3
31.8
84
39.8
40
9.0
4
46.3
89
57.9
60
12.0
5
56.9
94
71.1
80
15.0
6*
56.9
99
71.1
80
18.0
240/3/60
3
35.7
89
44.6
45
12.0
4
52.4
96
65.5
70
16.0
5
64.6
102
80.8
90
20.0
6*
64.6
108
80.8
90
24.0
460/3/60
3
16.9
89
21.1
25
12.0
4
25.2
96
31.5
35
16.0
5
31.3
102
39.1
40
20.0
6*
31.3
108
39.1
40
24.0
ECM
—
Electronically Commutated Motor
FLA
—
Full Load Amps
LAT
—
Leaving-Air Temperature at 70°F Entering-Air
Temperature
MCA
—
Unit Minimum Circuit Ampacity
MOCP —
Maximum Overcurrent Protection (Maximum Fuse Size
or Circuit Breaker Amps)