
16
Table 3 — Electric Heater Data for Units with ECM Motor (cont)
LEGEND
*Cooling coil must be left-hand coil connections only
NOTES:
1. LAT (leaving air temperature) is at maximum fan speed with
entering air temperature at 70°F.
2. Face and bypass units are available only with 3 elements.
3. Electric heat is available in the reheat only position.
UNIT
HP
NOMINAL
V/Ph/Hz
NUMBER OF
ELEMENTS
FLA
LAT (F)
MCA
MOCP
TOTAL
CAPACITY (kW)
40UV,UH100
(at 1000 cfm)
1
/
3
208/1/60
3
31.5
89
39.4
40
6.0
4
41.1
95
51.4
60
8.0
5
50.8
102
63.4
70
10.0
6
60.4
108
75.5
80
11.9
240/1/60
3
35.9
96
44.9
45
8.0
4
47.1
104
58.8
60
10.7
5
58.2
112
72.7
80
13.3
6
69.3
121
86.6
90
16.0
277/1/60
3
31.2
96
39.0
40
8.0
4
40.8
104
51.0
60
10.7
5
50.4
112
63.1
70
13.3
6
60.1
121
75.1
80
16.0
208/3/60
3
19.3
89
24.1
25
6.0
4
28.9
95
36.2
40
8.0
5
36.0
102
45.0
50
10.0
6
36.0
108
45.0
50
11.9
240/3/60
3
21.9
96
27.3
30
8.0
4
33.0
104
41.2
45
10.7
5
41.1
112
51.4
60
13.3
6
41.1
121
51.4
60
16.0
460/3/60
3
10.6
96
13.3
15
8.0
4
16.2
104
20.2
25
10.7
5
20.3
112
25.3
30
13.3
6
20.3
121
25.3
30
16.0
40UV,UH125
(at 1250 cfm)
1
/
2
208/1/60
3
39.4
89
49.3
50
7.5
4
51.5
96
64.3
70
10.0
5
63.5
102
79.4
80
12.5
6*
75.5
108
94.4
100
15.0
240/1/60
3
45.0
96
56.2
60
10.0
4
58.9
104
73.6
80
13.3
5
72.7
113
90.9
100
16.7
6*
86.6
121
108.3
110
20.0
277/1/60
3
39.0
96
48.7
50
10.0
4
51.0
104
63.8
70
13.3
5
63.1
113
78.8
80
16.7
6*
75.1
121
93.9
100
20.0
208/3/60
3
24.2
89
30.2
35
7.5
4
36.2
96
45.3
50
10.0
5
45.0
102
56.3
60
12.5
6*
45.0
108
56.3
60
15.0
240/3/60
3
27.4
96
34.2
35
10.0
4
41.3
104
51.6
60
13.3
5
51.5
113
64.3
70
16.7
6*
51.5
121
64.3
70
20.0
460/3/60
3
13.2
96
16.5
20
10.0
4
20.2
104
25.2
30
13.3
5
25.3
113
31.6
35
16.7
6*
25.3
121
31.6
35
20.0
ECM
—
Electronically Commutated Motor
FLA
—
Full Load Amps
LAT
—
Leaving-Air Temperature at 70°F Entering-Air
Temperature
MCA
—
Unit Minimum Circuit Ampacity
MOCP —
Maximum Overcurrent Protection (Maximum Fuse Size
or Circuit Breaker Amps)