14
Table 2 — Electric Heater Data for Units with PSC Motor (cont)
LEGEND
*Cooling coil must be left-hand coil connections only.
NOTES:
1. LAT (leaving air temperature) is at maximum fan speed with
entering air temperature at 70°F.
2. Face and bypass units are available only with 3 elements.
3. Electric heat is available in the reheat only position.
4. The PSC motor is not available on unit size 200.
UNIT
HP
NOMINAL
V/Ph/Hz
NUMBER OF
ELEMENTS
FLA
LAT (F)
MCA
MOCP
TOTAL
CAPACITY (kW)
40UV,UH150
(at 1500 cfm)
1
/
5
208/1/60
3
45.3
89
56.7
60
9.0
4
59.8
96
74.7
80
12.0
5
74.2
102
92.8
100
15.0
6*
88.7
108
110.8
125
18.0
240/1/60
3
52.0
96
65.0
70
12.0
4
68.7
104
85.8
90
16.0
5
85.3
113
106.7
110
20.0
6
—
—
—
—
—
277/1/60
3
44.9
96
56.2
60
12.0
4
59.4
104
74.2
80
16.0
5
73.8
113
92.3
100
20.0
6
—
—
—
—
—
208/3/60
3
27.0
89
33.8
35
9.0
4
41.5
96
51.9
60
12.0
5
52.1
102
65.1
70
15.0
6*
52.1
108
65.1
70
18.0
240/3/60
3
30.9
96
38.6
40
12.0
4
47.6
104
59.5
60
16.0
5
59.8
113
74.8
80
20.0
6*
59.8
121
74.8
80
24.0
460/3/60
3
15.4
96
19.2
20
12.0
4
23.7
104
29.6
30
16.0
5
29.8
113
37.3
40
20.0
6*
29.8
121
37.3
40
24.0
FLA
—
Full Load Amps
LAT
—
Leaving-Air Temperature at 70°F Entering-Air
Temperature
MCA
—
Unit Minimum Circuit Ampacity
MOCP —
Maximum Overcurrent Protection (Maximum Fuse Size
or Circuit Breaker Amps)
PSC
—
Permanent Split Capacitor