CORRECTION OF REFRIGERANT PIPING LENGTH
38VMA***RD system can extend the piping flexibly within its limitation to suit the actual situation. However, it will cause
a decrease in cooling/heating capacity due to pressure loss because of the longer piping length. Use the following
correction factor to calculate the capacity (approximately).
Table 65 —Cooling Capacity Correction
38VMA072RDS5-1(RDS6-1)
38VMA096RDS5-1(RDS6-1)
38VMA120RDS5-1(RDS6-1)
38VMA144RDL5-1(RDL6-1)
38VMA168RDS5-1(RDS6-1)
38VMA192RDS5-1(RDS6-1)